ATD 50 Actuator
®
Operating Instructions
Page 23
3811 N. Holton Street • Milwaukee, WI • 53212 •USA • Phone • 414-906-4000 • Fax 414-906-4100 • www.MPCovers.com
Technical Data (cont.)
OUTPUTS
Relay:
Contact load
28VDC @ 1A or 120VAC @ 0.5A
Contact protection
Must be externally connected.
Required for inductive loads.
RC-element for AC loads. Diode (1N4007) for
DC load.
Terminals
E1 - 6 & I1 - 6. Refer to electrical wiring
diagram.
Available Internal Power Supply
+24VDC
Overload Protection
2.0A Max current (protected by Fuse 1)
Maximum Load for all Output Voltages COMBINED is 12 watts!
Transistor:
Output: Transistor Output
Imax = 100mA for error LEDs
Overload protection
Time-limited protection available
Terminals
B5 through 9
Inputs:
Signal Type:
All inputs must be from potential free contacts.
Terminals:
A2 & 7, C4, 7, & 9, D2, F2