ATD 50 Actuator
®
Operating Instructions
Page 12
3811 N. Holton Street • Milwaukee, WI • 53212 •USA • Phone • 414-906-4000 • Fax 414-906-4100 • www.MPCovers.com
6 Check List for Functional Tests (cont.)
TEST 3:
OPTIMIZE MOVEMENTS
ACTION:
Operate the door for two (2) complete open and close
movements.
EXPECTED BEHAVIOR:
Door should open and close normally. The
microprocessor measures the torque and sets the
internal speed and torque references. These references
are used as safety thresholds for detecting obstructions.
NOTE: The safety reversing function is not active
during the first two (2) open and close cycles!
See Sec. 11.1.
TEST 4:
CHECK ALL FUNCTIONS
ACTION:
Activate all connected functions and options such as
CNC, PLC, pushbuttons, photoeyes, etc.
EXPECTED BEHAVIOR:
Door should operate normally per feature definitions.