Section III
Operation
006-0007207 MPC-1250DC Guide
Rev F
23 of 44
03/03/2022
LEDs on the Front Panel - “Constant Current” Model
The “Constant Current” model has a 13 LED front panel display to indicate the status and
operation of the MPC.
POWER OUT
POWER IN
LOAD
CHARGE
FAN
MPC
A0
C0
B0
B1
B2
B3
D0
D1
F0
E0
E1
E2
E3
Power-In Indicators (LEDs in positions D0 and D1)
The LED in position D0 indicates the status of the optional DC INPUT and the LED in position D1
indicates the status of the AC INPUT, according to the table below:
LED Appearance
Description
Indication
Green
Input is Ready to Provide Load Power
Pulsing Green
Input is the One Presently Selected as the
Source of Power
Amber
Input has Returned within Range and Diagnostic Tests are
Being Performed
Off
Input is Not within Range
Power-Out Indicator (LED in position A0)
The LED in position A0 indicates the status of the DC OUTPUT, according to the table below:
LED Appearance
Description
Indication
Green
MPC is On and the Output Voltage is
Within Range
Amber
MPC is On but the Output Voltage is
Out of Range
Red
MPC is Off and the Output Voltage is Within Range
Off
MPC is Off