Analog Menu
This menu defines the basic settings of the analog output.
This function is only available for devices with option AO or AR.
ANALOG SOURCE
This parameter defines the reference source for analog output
0 SPEED A
Result of frequency measurement on channel A (or A / B 90)
1 COUNTER A
Result of the counter on channel A (or A / B 90)
2 SECOND COUNTER A
Result of the second counter (total counter / batch counter) on channel A
(or A / B 90)
(Only visible if "Second Mode -A" has been activated.)
3 SPEED B
Result of frequency measurement on channel B
(Only visible if corresponding "Operational Mode" has been activated.)
4 COUNTER B
Result of the counter on channel B
(Only visible if corresponding "Operational Mode" has been activated.)
5 SECOND COUNTER B
Result of the second counter (total counter / batch counter) on channel B
(Only visible if "Second Mode -B" has been activated.)
FREQUENCY COLL.
Result of the linked frequency of channel A and B (A + B, A-B, B / A, ...)
(Only visible if corresponding "Operational Mode" has been activated.)
COUNTER COLL
Result of the linked counters of channel A and B (A + B, A-B, B / A, ...)
(Only visible if corresponding "Operational Mode" has been activated.)
SCALED RESULT
Result of the additionally scaled process value
ANALOG FORMAT
This parameter defines the output characteristics. The analogue output is proportional to the display value.
With setting ANALOG FORMAT (-10 … +10 V) in MODE COUNTER the polarity of the analog output depends on
the polarity of the display value.
0
-10…10V
-10 … +10 V
1
0…20M
0 … 20 mA
2
4…20MA
4 … 20 mA
ANALOG START
This parameter defines the start value of the analog conversion. This start value is corresponding to the display
value for an analog output of 0 V or 0/4 mA.
-99999999
Smallest start value
0
Default value
+99999999
Highest start value
ANALOG END
This parameter defines the end value of the analog conversion. This end value is corresponding to the display
value for an analog output of (+/-) 10 V or 20mA.
-99999999
Smallest end value
10000
Default Wert
+99999999
Highest end value