Unconnected NPN inputs are always HIGH (internal pull-up resistor)
Unconnected PNP inputs are always LOW (internal pull-down resistor)
It is mandatory to assign the Cutting Pulse to one of the inputs 1, 2 or 3 (F06.050
or F06.052 or F06.054 = 6). The selected input is no more available for other
purpose.
The Cutting Pulse input must always be edge-triggered, i.e. the corresponding
parameters F06.049, F06.051 or F06.053 be either 2 or 3 or 6 or 7
Where you like visualize the Cutting Pulse Signal on your PC screen by means of
the OS32 Operator Software, you must temporary set the inputs to static
operation as the corresponding light boxes on the screen are not suitable to
display dynamic signals. Please do not forget to return to edge-triggered
operation after the test!
6.2.8.
Serial communication parameters
F07
Range
Default
F07.058 Serial device address (unit number)
11 … 99
11
F07.059 Serial baud rate
0 … 6
0
0= 9600 Baud
1= 4800 Baud
2= 2400 Baud
3= 1200 Baud
4= 600 Baud
5= 19200 Baud
6= 38400 Baud
F07.060 Serial data format
0 … 9
0
0= 7 Data, Parity even, 1 Stop
1= 7 Data, Parity even, 2 Stop
2= 7 Data, Parity odd, 1 Stop
3= 7 Data, Parity odd, 2 Stop
4= 7 Data, no Parity, 1 Stop
5= 7 Data, no Parity, 2 Stop
6= 8 Data, Parity even, 1 Stop
7= 8 Data, Parity odd, 1 Stop
8= 8 Data, no Parity, 1 Stop
9= 8 Data, no Parity, 2 Stop