EN
EVENT TIME DIAGRAM
04. CONFIGURATION
05. MAINTENANCE
DOOR MAINTENANCE TASKS
When performing door maintenance with the sensor connected to the power, on the door controllers
connected to "test" the sensor, be sure to set the DIP switches.
Note •
Remember to return the DIP switch settings to their original state when door maintenance is
performed.
Dip switch Y
Safety ouput
DISCONNECTED
POWER
WITHOUT
DETECTION
DETECTION
Yellow
Blue
Response, by detection, to
the test
T1: Ap.10±1[ms]
High
Safety Output Line 1, 2/ Test Input
Technical sensor problems are indicated by a flashing green/red LED. The flashing frequency indicates
the type of problem.
AUTO-DIAGNOSIS
Flashing frequency
LED
Cause
Fast
Replace the sensor.
Slow
Confirm the sensitivity potenti-
ometer is set and reconnect the
sensor.
If the error persists, set Dip
switch Y #4 to "Low Reflection".
Dip switch Z
Test Input Adjustment
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
Yellow
Blue
WITHOUT
DETECTION
3.
6.
Dip switch Z
Activation Output
2.
Low
N.O.
N.C.
N.O.
N.C.
Activation output line 2, 3, 4, 5
DISCONNECTED
POWER
WITHOUT
DETECTION
DETECTION
Green
White
Green
White
Green
White
Green
White
Green
White
Green
White
T2: Ap.11±1[ms]
Test Input
No test
gray
sensor
brown
When supplying 12 to 24 V DC,
the current flow rate changes
from gray to brown.
gray
sensor
brown
gray
sensor
brown
Turn off current
flow in test state.