TAPS Description
3
Manual # 42-02-U001, Rev C1
For 3kVA systems, the UPS is housed in the base TAPS enclosure. For 6kVA systems, the UPS is housed
in a separate enclosure. 3 or 6kVA units are specified according to traction motor horsepower and over-
all system power consumption (for example, brake size, AC unit size, etc.).
Operating Controls
TAPS operating controls and indicators are visible through a cutout in the cover.
• Normal Power: The Normal Power indicator will light when commercial power is pres-
ent and also indicates that
KM0
contactor coil is energized. All power to the elevator con-
troller will pass through the TAPS unit through contactor
KM0
. A small amount of power
is drawn off to maintain the TAPS UPS batteries.
• Backup Power: Lights when commercial power has failed for the duration set by Param-
eter F1-9 (factory default is 2.0 seconds) and also indicates that the
KM5
contactor coil is
energized. Output power from the UPS will be present on power terminals L1X and L2X.
Because this is a single phase output, terminal L3X will not be energized in this mode. Be
certain that the elevator logic section is powered from lines L1X and L2X.
The BYPASS switch
above is not visible
unless the TAPS cover
is removed
Summary of Contents for TAPS
Page 6: ...2 Manual 42 02 D001 Rev A 1 September 2003...
Page 15: ...Installation 9 Manual 42 02 U001 Rev C1 Figure 5 6kVA UPS Enclosure Base Assembly...
Page 16: ...10 Manual 42 02 U001 Rev C1 Figure 6 6kVA UPS Enclosure Assembly...
Page 40: ...34 Manual 42 02 U001 Rev C1 6kVA Units The 6kVA unit uses an LCD as well as LEDs...
Page 42: ...36 Manual 42 02 U001 Rev C1 6 12 12...
Page 43: ...TAPS Drawings 37 Manual 42 02 U001 Rev C1...
Page 44: ...38 Manual 42 02 U001 Rev C1...