EAS15-806-GB.doc
EAS 15 - 806
REV.1-07/11
3.4 - Setting the MAINS voltage
- Set the board to
- keep on pressing for about 8” the STOP button
until the TEST LED switches on
- Press the button to increase voltage. – Press the button to decrease voltage
- When this setting procedure is over, press button for about 1” to confirm and then exit from the procedure.
3.5 - User menu parameters description
3.6 - User menu parameters description
Setup
Description
Range
Default
Group 1
Panel nominal data
P1.01
Nominal frequency
50Hz= 0 60Hz=1
0
.02
Current Transformer ratio (CT 100/5 = 20)
1…2000
20
.03
System (220V mono-phase, 220V tri-phase, 380V tri-phase)
0=220M 1=220T 2=380T
0
Attention: to check the setting of the parameter P1.03 “System” in case of wrong reading of the voltage on the display
Group 2
Engine starting
P2.01
500 rpm signal from alternator or generator (started engine)
0= from alternator Vac
1= permanent magnet alt. (saprisa)
2= pre-excited alternator (D+)
0
.02
Started engine alternator battery charger voltage threshold
3-30V
10V
.03
Started engine generator voltage threshold
20-500V
20V
.04
Starting with power failure
On=1 Off=0
1
.05
Preheating time
1-60s.
1s.
.06
Number of starting attempts
1-10
5
.07
Duration of starting attempts
1-30s.
5s.
.08
Pause time within starting attempts
1-20s.
5s.
.09
Automatic test enabling with remote stop signal presence
0= start not enable
1= start enable
0
.10
Alarm enabling delay at starting (oil/V/freq.)
1-60s.
8s.
.11
Choke time
0-240s.
3s.
.12
Choke switch-off threshold
30-255V
30V
Group 3
Engine stopping
P3.01
Stopping times (electromagnet closing time / gasoline engine stop
time)
1-30s.
10s.
.02
Decelerated function time
1-60s.
60s.
.03
Cooling time
1 – 300s.
30s.
Setup
Description
Range
Default
Group 1
Test
U.01
Automatic test interval time
1 – 30 days
7 days
U.02
Test duration
1 – 30 min
10 min
U.03
Test start time
00:00 – 23:59
10:00
U.04
Test with load
0=with load 1=without load
1
U.05
Not enable
U.06
Not enable
U.07
Not enable
Group2
Various
U.08
Siren relay closing time
0 – 60 sec
20 sec
U.09
Engine departure delay from EJP start
0 – 99 min
25 min
U.10
Switching delay for EJP/T(1 wire)
0 – 30 min
5 min
Group3
Clock setting
U.11
Time
00:00 – 23:59
22:00
U.12
Not enable