EAS15-806-GB.doc
EAS 15 - 806
REV.1-07/11
Push AUT or verify
that the red led
of
AUT button is
lighting.
Push TEST to enable the
function. The yellow led is
lighting: on display appear
“On” for 1sec:
the test is enabled
ENABLED
Push AUT or verify
that the red led
of
AUT button is
lighting.
Push TEST to disabled the
function. The yellow led goes
off: on display appear “OFF”
for 1sec:
the test is disabled
Setup
Description
Range
Default
U.01
Automatic test interval time
1 – 30days
7 days
U.02
Test duration
1 – 30 min
10 min
U.03
Test start time
00:00 – 23:59
10:00
2.8- Automatic test – Enabled and disabled
When the automatic test parameters are set, you have to enable this test; with EAS electrical board in automatic mode (AUT), keep pressed TEST until
the display shows “ON” and the test led turn ON. From this moment the board starts the counting of the time to make the first test. This test will begin
after the set days in parameter “U.01”, at the set time in parameter “U.03” and for a set duration in parameter “U.02”. To disable the automatic test, with
the board in AUT position, keep pressed TEST button until the display shows “OFF” and the test led turn OFF.
When the EAS electrical board is in Manual (MAN) the automatic test is disabled.
2.9- LED indication decription
If on, it indicates that one or
more alarms are active
If on, it
indicates that
the mains
voltage is ok
If on, it indicates that
the generator voltage
is ok
If on, indicates that
the mains contactor
is closed (the mains
supplies the load)
If on, indicates that the generator
contactor is closed (the generator
supplies the load)
If on, it indicates that
the voltage measured
is about the mains
If on, it indicates that
the voltage measured
is about the
generator
If on, it
indicates that
the automatic
test is enable
If on, it indicates that
the board is in
MANUAL
If on, it indicates that
the board is in
AUTOMATIC
If on, it indicates
that the board is in
RESET
Type of
measurement
showed by the
display
If flashing, it indicate that the
engine is running and the
alarms are not enable. If on,
it indicate that the engine is
running and the alarms are
enable.
4 digit multifunction
display to show
measurement,
function and
alarms status
DISABLED