background image

MORTEX

 

PRODUCTS

 

INC

 

FORT

 

WORTH,

 

TX

 

76106

 

Page

 

5

 

checked every month and replaced as needed. Figures 2 and 3 
indicate the location of the air filters if you have a louvered 
return air door. 

 

Figure 2: Return Air Louvered Door Air Filter Location 

 

 

Figure 3: Return Air Louvered Door 20” x 20” x 1” Air 
Filters 

 

 

Return Air Grille Air Filters 

Follow these easy steps to replace the filters located in the 
return air grille: 
1.

 

Follow the procedure “

To Turn Off the Appliance”

 in 

the Start Up and Shutdown Instructions section of these 
instructions. 

2.

 

Pull on the top of the return air louvered door (upper 
door) until the door strike is removed from the door latch. 

3.

 

Let the top of the door fall towards you then lift up 
slightly pulling towards you and set the door on the floor. 

4.

 

Turn the door upside down and pull the bottom frame out 
of the door to gain access to the air filters. 

5.

 

Remove the air filters. These filters are disposable filters. 
DO NOT attempt to clean the filters and reuse them. 

6.

 

Remove the new pleated air filters from the plastic wrap 
they come in. 

7.

 

Slide the air filters in place in the door so both air filters 
are installed as shown in Figure 3. 

8.

 

Replace the bottom door frame.  

9.

 

Lift the door up to the cooling cabinet and align the two 
tabs on the bottom of the door with the two slots on the 
center shelf. Refer to Figure 6. 

10.

 

Push the upper door forward and tighten with the thumb 
screw until the door is secured to the cabinet. Refer to 
Figure 6. 

11.

 

Follow the instructions to “

Turn On / Start the 

Appliance”

 in the Start Up and Shutdown section of 

these instructions. 

 

Coil Cabinet Top Air Filters 

Follow these easy steps to replace the filters located in the top 
of the coil compartment: 
1.

 

Follow the procedure “

To Turn Off the Appliance”

 in 

the Start Up and Shutdown Instructions section of these 
instructions. 

2.

 

Remove the thumb screw by turning it counter clockwise. 

3.

 

Let the top of the door fall towards you then lift up 
slightly pulling towards you, then set the door on the 
floor. 

4.

 

Remove the air filter at the top of the coil cabinet. The 
20” x 24” x 1” filter is a disposable filter. DO NOT 
attempt to clean the filter and reuse it. Refer to Figure 4 
for filter location. 

5.

 

Remove the new 20” x 24” x 1” pleated air filter from the 
plastic wrap they come in. 

6.

 

Slide the air filter into the filter rack at the top of the coil 
cabinet as shown in Figure 4. 

7.

 

Lift the door up to the cooling cabinet and align the two 
tabs on the bottom of the door with the two slots on the 
furnace top cover. Refer to Figure 6. 

8.

 

Push the upper door forward until aligned with the cabinet 
top flange. Insert the thumb screw onto the hole and 
secure by turning it clockwise. Refer to Figure 6. 

9.

 

Follow the “

Turn On / Start the Appliance”

 in the Start 

Up and Shutdown Instructions section of these 
instructions. 

 

Summary of Contents for E30 SERIES

Page 1: ...Torque Motor 14 9 Replacement Parts List 3 4 HP Constant Torque Motor 19 5 Blower Performance 3 4 HP Constant Torque Motor 15 CONTACT INFORMATION Contact us by mail Manufactured and Distributed by Mo...

Page 2: ...block or obstruct air openings used for ventilation and cooling of the furnace electrical components 8 Refer to the furnace rating plate for the furnace model number for the operating specifications...

Page 3: ...an The furnace s best friend is a qualified service technician If the unit gives any indication of improper operation call the service technician The service technician is allowed to perform the norma...

Page 4: ...of the furnace to make sure there are no flammable materials in the area If you smell vapors of any kind DO NOT turn on the power to the furnace until vapors have been ventilated and removed from the...

Page 5: ...s on the center shelf Refer to Figure 6 10 Push the upper door forward and tighten with the thumb screw until the door is secured to the cabinet Refer to Figure 6 11 Follow the instructions to Turn On...

Page 6: ...ted as to how to clean and reinstall filters washable or replaceable filters for good preventive maintenance Care must be taken that the edges of the washable or replaceable filter are resting on the...

Page 7: ...cause serious injury if clothing or body parts get caught in the moving part The manufacturer or distributer will not be responsible for any repairs due to improper parts changes improper maintenance...

Page 8: ...trol Box Cover Figure 8 Blower Assembly and Mounting Screw Location 8 Check the blower wheel for dust and debris Use the brush and the vacuum cleaner to remove any dust or debris from the wheel Be car...

Page 9: ...heating or cooling operation 9 Thermostat Y Circuit The thermostat Y circuit is used for cooling or high speed indoor fan operation When 24 VAC is placed on the thermostat Y circuit the 24 vac is sen...

Page 10: ...heck all wiring connections especially on any of the components to ensure they are securely fastened If you have 240 VAC coming out of the control box circuit breakers and you have 24 VAC between the...

Page 11: ...tactor check for 24 VAC between the A1 and A2 terminals If 24 VAC is present then replace the heater contactor L1 L2 T1 T2 A 1 A 2 Figure 11 Heater Contactor Terminal Designations Blower Motor FLA 1 3...

Page 12: ...2 741 615 466 LO 764 689 586 507 460 399 332 MED LO 855 807 733 632 571 521 478 416 367 MEDIUM 990 923 878 825 741 672 628 574 520 440 MED HI 1085 1031 988 929 878 789 725 663 603 474 HI 1291 1247 120...

Page 13: ...56 630 494 with Cabinet MEDIUM 1251 1216 1170 1134 1079 1045 1009 860 685 570 97 FLSB 27 MED HI 1450 1410 1380 1335 1303 1221 1139 1056 737 580 or 97 FLSF 27 HI 1549 1506 1457 1410 1335 1246 1165 1056...

Page 14: ...1245 1137 1012 679 551 or 97 FLSF 39 HI 1570 1531 1488 1415 1344 1279 1170 1070 736 562 CFMwith Coil LO 851 813 759 708 618 555 523 458 394 362 98 8Z12W OP MED LO 1021 982 934 884 837 740 684 636 573...

Page 15: ...4 1065 874 711 561 with Cabinet MEDIUM 1404 1350 1327 1294 1251 1211 1145 1005 718 535 97 FSOB 39 MED HI 1601 1538 1468 1400 1327 1241 1148 888 719 541 HI 1725 1613 1530 1442 1360 1283 1190 1088 739 5...

Page 16: ...TON ACCESSORY BLOWER 86MH0025 3 4 HP PSC 5 TON ACCESSORY BLOWER 86MH0026 3 4 HP CONSTANT TORQUE 5 TON ACCESSORY BLOWER 86MH0027 21 1200 CFM BROKE DOWN COOLING COIL CABINET 97 FLSB 21 21 1600 CFM BROK...

Page 17: ...019P R68AB0019P 6 HEATER CONTACTOR 2 R68AB0019P R68AB0019P R68AB0019P 7 TRANSFORMER R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD014 R68BAD016 R68BAD018 R68BAD...

Page 18: ...HEATER CONTACTOR 2 R68AB0019P R68AB0019P R68AB0019P 7 TRANSFORMER R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD015 R68BAD017 R68BAD018 R68BAD015 R68BAD018 R68B...

Page 19: ...AA0003 R68AA0003 R68AA0003 R68AA0003 R68AA0003 8 CIRCUIT BREAKER 1 R68BAD015 R68BAD017 R68BAD018 R68BAD015 R68BAD018 R68BAD018 9 CIRCUIT BREAKER 2 R68BAD014 R68BAD013 R68BAD017 10 LOW VOLTAGE TERMINAL...

Reviews: