3

Morrison Bros. Co.  ‑  Dubuque, IA  ‑  800‑553‑4840

918S‑‑1130 PP     rev 12‑21‑2020

WARNING: 

Interconnect wiring between the gauge and the alarm unit must be kept totally isolated and separate 

from any other wiring. This wiring must not share any junction box, conduit, raceway, or fixtures with circuits 

other than those defined by NEC as being intrinsically safe for all Class 1 locations.

AVERTISSEMENT: 

Le câblage d’interconnexion entre la jauge et l’unité d’alarme doit être complètement

isolé et distinct du reste du câblage. Le câblage ne doit partager aucune boîte de connexion, aucun conduit,

aucune canalisation, ni aucun accessoire avec des circuits autres que ceux défi nis par NEC comme étant

intrinsèquement sécuritaires pour tous les emplacements de classe 1.

Location: 

NEC ARTICLE 501-3-CLASS 1 Locations exempt intrinsically safe enclosures in paragraph

501-3(b)(1)(c), and therefore may be placed in the most convenient location but must be within reach of the 

operator and within audible range.

Mounting: 

Since a general purpose NEMA 4X enclosure is used to protect the alarm circuits and batteries, 

any mounting holes, conduit, or fasteners must be sealed in order to maintain the waterproof integrity of the 

enclosure. All penetrations into the enclosure must be made at the bottom of the Alarm Box.

Steps

1. Wire Input Device

a. Run two 

stranded conductor

 oil and gas resistant wires from each input device to the location where 

the alarm box will be mounted.  Do NOT attach the wires to the wires in the junction box of the input 

device(s) at this time. Although not required, it is recommended to run the wires in some type of conduit 

in order to protect them against possible damage and environmental conditions.  It may be necessary to 

remove the junction box cover of the input device(s).

INPUT DEVICE WIRING WIRE SIZE LIMITS:

Input device wiring shall have a minimum cross section of 0.4 mm

2

 (equivalent of a single 26 AWG wire)

to a maximum cross section of 1.0 mm

2

 (the equivalent of a single 18 AWG wire).  

b. Do NOT attach the wires to the wires in the junction box of the input device at this time. 

2. Mount the Alarm

a. 

Separate

 the two halves of the Alarm Unit box by loosening the Phillips head fasteners visible at the four 

corners of the front panel.  

b. 

Support

 the front panel while mounting the rear half.

c. 

Attach

 the rear half of the box to a suitable fixture. 

d. 

Seal

 any penetrations made into the interior of the box to prevent moisture ingress.

3. Test the Alarm.

a. 

Turn on

 the power switch, SW5 (see Figure 1).

b. 

Press and hold 

the “Test/Cancel” button until the alarm sounds at least three times while observing the 

Channel Alarm and BATTERY LOW Indicators (see Figure 1).

c. 

Observe 

the 918 Series Alarm indicates the following:

•  The BATTERY LOW indicator will flash momentarily at the beginning of the cycle.

•  If the Audible Alarm is configured to sound with an alarm condition, it is loud and strong.

Fig. 1 Power Switch (SW5) ... Channel Alarm Indicators, Battery Low Indicator 

and Test/Cancel Button on the 918D

SW5

ON

OFF

Channel Alarm 

Indicators

Low Battery 

Indicator

Test/Cancel 

Button

Summary of Contents for 918D Series

Page 1: ...mer à l un ou l autre des avertissements ou à l une ou l autre des directives apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux lesquels pourraient engendrer des dommages matériels des risques de contamination environnementale d incendie ou d explosion des blessures graves ou la mort Specifications The 918S 918D and 918Q are intrinsically safe devices for ...

Page 2: ...te unité autres que celles indiquées dans ces directives engendreront l annulation de la garantie du produit Pour assurer votre sécurité il est important de vous conformer à la réglementation locale d État fédérale ou OSHA régissant les travaux à l intérieur au dessus ou autour du réservoir de stockage et de la zone de canalisation Utilisez tout l équipement de protection individuelle exigé pour t...

Page 3: ...x will be mounted Do NOT attach the wires to the wires in the junction box of the input device s at this time Although not required it is recommended to run the wires in some type of conduit in order to protect them against possible damage and environmental conditions It may be necessary to remove the junction box cover of the input device s INPUT DEVICE WIRING WIRE SIZE LIMITS Input device wiring...

Page 4: ...ill does not sound or the BATTERY LOW indicator illuminates replace the Alarm Box or call Morrison Bros Co Customer Service e Turn off the power switch SW5 before proceeding see Figure 1 4 Connect the two wires from each input device to the Input of the Alarm a Connect the two wires from each input device to their respective Channel Input Connector s see Figure 2 b Verify that the wires are secure...

Page 5: ...ED 918S 918D 918Q 2 Auto Silence ON default ENABLED OFF DISABLED 918S 918D 918Q 3 Channel 1 Normally Closed Open ON Normally Closed Contacts OFF default Normally Open Contacts 918S 918D 918Q 4 Channel 2 Normally Closed Open ON Normally Closed Contacts OFF default Normally Open Contacts 918D 918Q 5 Channel 3 Normally Closed Open ON Normally Closed Contacts OFF default Normally Open Contacts 918Q 6 ...

Page 6: ...sabled the Alarm will flash its Channel Alarm Indicator s and sound the Audible Alarm if so configured until the battery can no longer power the Alarm Box Operational verification should be checked on a more frequent schedule if the Autosilence feature is disabled c CONTACT MODE OPTION i Normally Open Contact Input Devices default If the input device s to be connected to the 918 Series Alarm utili...

Page 7: ...is fitted with this alarm Failure to follow any or all of the warnings and instructions in this document could result in a hazardous liquid spill which could result in property damage environmental contamination fire explosion serious injury or death Le fait de ne pas se conformer à l un ou l autre des avertissements ou à l une ou l autre des directives apparaissant dans ce document pourrait donne...

Page 8: ... Autosilence feature is NOT enabled and the alarm is not silenced by the operator then the 918 Series Alarm will continue to alarm until the battery can no longer power the device 3 To check for an alarm state once the Alarm has silenced itself press and hold the Test Cancel button until the alarm sounds at least three times while observing the Channel Alarm Indicators a If there is an interstitia...

Page 9: ...maintenance operations MONTHLY Test the battery level and overall operation of the Alarm see 2 below YEARLY Check the Enclosure for water ingress see 3 below Battery replacement instructions are in 4 below 1 If necessary clean the Alarm Box with a damp cloth 2 Test the battery level and overall operation of the Alarm no less than once per month a Press and hold the Test Cancel button until the ala...

Page 10: ...clicked into place h Turn on the power switch SW5 see Figure 1 NOTE If the 918 Series Alarm has been configured to operate with Normally Closed Contacts the Alarm should go into the alarm state when the power switch is turned on silence this by pressing the Test Cancel button i Test the Alarm by pressing and holding the Test Cancel button until the alarm sounds at least three times while observing...

Page 11: ...us liquid spill which could result in property damage environmental contamination fire explosion serious injury or death Le fait de ne pas se conformer à l un ou l autre des avertissements ou à l une ou l autre des directives apparaissant dans ce document pourrait donner lieu à des déversements de liquides dangereux lesquels pourraient engendrer des dommages matériels des risques de contamination ...

Page 12: ...12 Morrison Bros Co Dubuque IA 800 553 4840 918S 1130 PP rev 12 21 2020 ...

Page 13: ...13 Morrison Bros Co Dubuque IA 800 553 4840 918S 1130 PP rev 12 21 2020 ...

Reviews: