background image

3.0

Installation and Commissioning

20

GenStar MPPT 

21

             

CAUTION:  Equipment Damage

              

Locate  battery  breakers  or  fused  disconnects  for  easy  access  and  free  from  hydrogen                     

             gas/sulfuric acid fumes.

STEP 2:

(A)

  Fit a positive wire between the battery bank (+) post or busbar and the GenStar battery (+)     

terminal.  

(B)  

Using a short wire on the battery side, install a correctly sized in-line breaker or fused disconnect 

switch in the OPEN position as close to the battery (+) post or busbar as possible.

(C)

  Connect the long wire from (A) to the vacant breaker terminal from (B), and then the other end 

to the GenStar battery (+) terminal. 

(D)

  Where GenStar battery terminals are more than five (5) feet from the battery, or where circuits 

from these terminals pass through a wall or partition, U.S. NEC requires that overcurrent protection 

be provided at the solar controller in addition to providing overcurrent protection at the DC battery 

power source. 

STEP 3:

 

(A)

   Fit a negative wire between the battery (-) post and GenStar MPPT battery (-) terminal. 

(B)

   Connect the controller end to the GenStar battery (-) terminal. 

DO NOT CONNECT THE     

BATTERY END OF THE NEGATIVE WIRE AT THIS TIME. 

 

3.4.5  SOLAR CONNECTIONS - 

refer to Figure 3-4 above

          

WARNING: SHOCK HAZARD

 - 

LIVE EQUIPMENT GROUND CONNECTION

            

Keep the PV array (-) wiring disconnected during installation, and when system  

           wires are exposed. 

STEP 1: 

  Wire the PV array according to NEC Section 690 or applicable local regulations or code. 

Use caution, since the solar array will produce current whenever it is in sunlight.

STEP 2: 

  According to the combiner installation instructions, wire the PV array string (+) wire(s) to 

a solar combiner box that includes fuse holders or breakers. 

DO NOT INSTALL COMBINER FUSES 

OR CLOSE COMBINER BREAKERS AT THIS TIME.

STEP 3: 

  Fit and connect a positive wire between the GenStar PV input (+) terminal and the 

OPEN/DISCONNECTED combiner PV (+) disconnect switch or breaker. 

DO NOT CLOSE THE                

DISCONNECT AT THIS TIME.        

STEP 4: 

  Fit and connect a negative wire between the GenStar PV (-) input terminal and the PV 

(-) busbar or combiner terminal. 

DO NOT CONNECT THE THE ARRAY STRING (-) WIRE(S) TO 

THE COMBINER BOX AT THIS TIME.

 This can be achieved by not connecting the PV (-) MC-4            

connectors or the PV (-) wire(s) to the transition box, combiner box or the PV (-) Disconnect.

3.4.6  LOAD CONNECTIONS 

-

 refer to Figure 3-4 above

  

  

             

CAUTION:  Equipment Damage

 

 

              

Do not wire any AC inverter to the load terminals of the GenStar-MPPT. Damage to the load 

control circuit may result. An inverter should be wired directly to the battery. If there is a possibility 

that any other load will sometimes exceed the GenStar’s maximum load current rating, the device 

should be wired directly to the battery or battery bank. If load control is required, contact Morningstar 

Technical Support for assistance.

SYSTEM GROUNDING

The DC system should be bonded to ground with a connection to the primary battery circuit. It can be 

bonded to ground directly or through an AC service panel if there is an inverter installed in the system. For 

the DC system grounding electrode conductor (GEC) sizing requirements, refer to NEC Section 250.166, or 

applicable local regulations or code.

WARNING:

  

Shock Hazard

 

This unit is not provided with a GFDI device. This charge controller must be used with an external 

GFDI device as required by the Article 690 of the National Electrical Code for the installation 

location.

WARNING:

  

Shock Hazard

 

When a ground fault is indicated, battery terminals and connected circuits might be 

ungrounded and hazardous..

WARNING:

  

Risk Of Electrical Shock

.

 

NO  POWER OR ACCESSORY TERMINALS ARE  ELECTRICALLY ISOLATED FROM DC 

INPUT, AND MAY BE ENERGIZED WITH HAZARDOUS SOLAR VOLTAGE. UNDER CERTAIN 

FAULT CONDITIONS, BATTERY COULD BECOME OVER-CHARGED. TEST BETWEEN ALL 

TERMINALS AND GROUND BEFORE TOUCHING. 

NOTE:

  

Follow local electrical installation code and use green/yellow, green or transparent 

insulated grounding-earthing wire. 

EQUIPMENT GROUNDING

Use copper wire to connect the grounding terminal in the case, and other dead metal, to earth 

ground. The grounding terminal is identified by the ground symbol on the case, just above the      

terminal, as shown below:

 

 

 

 

 

 

          Ground Symbol

Recommended minimum sizes for equipment copper grounding wire: 

•  GenStar MPPT-60   8 AWG  (8.37 mm

2

)

•  GenStar MPPT-80   6 AWG  (13.3 mm

2)

     

•  GenStar MPPT-100 4 AWG  (21.1 mm

2

)

3.4.4  BATTERY CONNECTIONS - 

refer to Figure 3-4 above

STEP 1:  

 Before wiring, verify that all system breakers and disconnect switches are in the                    

OPEN/DISONNECTED position, and that all fuses are removed from their holders.

              

WARNING:  SHOCK HAZARD - LIVE EQUIPMENT GROUND CONNECTION

             Keep the battery (-) cable and GEC disconnected from the battery bank  

             (-) post while installing the system or while system wires are exposed.

 

Summary of Contents for REAKSTAR GenStar GS-MPPT-60M-200V

Page 1: ...nance Manual Solar DC System Controller Solar Battery Charger Load Controller With TrakStarTM Maximum Power Point Tracking Technology MAXIMUM POWER POINT TRACKING MODELS GS MPPT 60M 200V GS MPPT 80M 2...

Page 2: ...y Block Installation 22 3 4 8 Final Connnections 24 3 4 9 Power Up and Verify System Operation 24 3 4 10 Power Down 25 3 5 Commissioning Initial Configuration 25 3 5 1 Methodology 25 3 5 2 Commissioni...

Page 3: ...arging Variables 49 5 3 Load Control Information 52 5 4 Soft key Use 53 Cont 5 5 Factory Reset Procedure 53 5 6 LED Indications 53 5 6 1 General LED Indications 53 5 6 2 Battery Charging LED Indicatio...

Page 4: ...T AND MAY BE ENERGIZED WITH HAZARDOUS SOLAR VOLTAGE UNDER CERTAIN FAULT CONDITIONS BATTERY COULD BECOME OVER CHARGED TEST BETWEEN ALL TERMINALS AND GROUND BEFORE TOUCHING WARNING THE COMMUNICATIONS PO...

Page 5: ...nnecting battery terminals Determine if battery is inadvertently grounded If so remove the source of contact with ground Contact with any part of a grounded battery can result in electrical shock The...

Page 6: ...d meter key functions Terminals sized for 1 0 AWG 53 5 mm2 wire Digital meter display 5 year warranty see Section 7 0 2 2 Versions and Ratings There are three versions of the GenStar MPPT controller G...

Page 7: ...activation 5 State of charge LEDs General battery state of charge1 2 indicators 1 See future Morningstar ReadyShunt updates for precise battery voltage measurements 2 See Morningstar ReadyBMS accessor...

Page 8: ...data reporting 1 and 2 MS CAN In Out Ports Proprietary Morningstar deWvice communication protocol ports 3 Ethernet Port RJ 45 socket for LAN Internet connection 4 Coin Cell CR 2032 Back up battery for...

Page 9: ...e GenStar MPPT in an enclosure ensure sufficient ventilation Installation in a sealed enclosure will lead to over heating and a decreased product lifetime CAUTION Equipment Damage When installing the...

Page 10: ...ximum voltage of the circuit or higher These devices are external to the GenStar MPPT controller BATTERY OVER CURRENT PROTECTION DEVICE SIZING The U S NEC requires the installation of DC breakers or f...

Page 11: ...zes 8 1 0 AWG 10 50mm2 Load terminal wire sizes 14 6 AWG 2 5 16mm2 Conductor ampacity current carrying capacity must be greater than the maximum current expected in the power circuits Battery breakers...

Page 12: ...ugh conduit with the power conductors Observing correct polarity connect both battery voltage sense wires to the GenStar MPPT at the 2 position Battery Sense terminal and to battery and terminals No d...

Page 13: ...attery temperature varies by just 5 C the charging target regulation voltage should change by 0 15 Volts for a 12 Volt battery This is a substantial change in battery charging so it is important to al...

Page 14: ...nnect 3 4 6 LOAD CONNECTIONS refer to Figure 3 4 above CAUTION Equipment Damage Do not wire any AC inverter to the load terminals of the GenStar MPPT Damage to the load control circuit may result An i...

Page 15: ...tallation and operation instructions As seen in Figure 2 1 and then as described in Section 2 3 A Loosen screw 7 B Remove the cover 9 by pressing in the tabs 10 C Use a knife to cut out the dead panel...

Page 16: ...make the GEC connection at the battery post also STEP 2 Confirm that the PV array wire polarity is correct and that the PV disconnect switch or breaker is in the OPEN position Connect the PV array neg...

Page 17: ...R Table 3 3 GenStar MPPT Start up Behavior Table 3 4 GenStar MPPT Run time Behavior RTS START UP and RUN TIME BEHAVIOR TABLES 12V 24V or 48V BMS Block Battery Charging Profile 1 RTS Required is the de...

Page 18: ...staller Setup on board meter menus shown below in Figure 4 1 CAUTION To effect changes always use the Save Button in upper right corner of the settings area 4 1 1 Using the Meter Display To adjust LCD...

Page 19: ...ernal clock UTC time and date are entered and an offset for local time zone is entered Note that the local offset must be adjusted when a time zone changes to DST and back 4 1 2 Using LiveView LiveVie...

Page 20: ...ar MPPT is connected to a DHCP router and the DHCP option is selected network settings will automatically be assigned To modify inverter settings remotely over Ethernet use the Installer Setup screen...

Page 21: ...harging current The low temperature 100 limit defines the highest temperature at which the controller will deliver 100 of the controller s rated output charging current Charging current is tapered lin...

Page 22: ...ReadyRelay assingments will govern which mode can be used 1 DISABLED External Source Control function is disabled Absorption End Amps set a net current threshold below which the controller will trans...

Page 23: ...GEN 2 MANUAL External Source starting can be triggered manually via Command or Soft key Once a ReadyRelay has been designated as a Command Schedule signal use Commands or Soft key see Section 4 2 7 5...

Page 24: ...ramming Prohibit Charging ONLY On Schedule timing Start Charging Charging 1 2 and 3 can be designated using On Schedule timing Conditions can be customized Low Battery complete Bulk voltage and time C...

Page 25: ...For example a system may have 2 amps of solar current flowing into the GenStar MPPT and five amps of charge current flowing out to the battery The GenStar MPPT does not create current Rest assured th...

Page 26: ...nufacturer for optimal battery charge settings Table 5 2 shows all preset high voltage disconnect and reconnect settings Table 5 3 shows the shared settings that are common to all GenStar charging pre...

Page 27: ...nk once per second during Absorption charging The battery must remain in the Absorption charging stage for a cumulative 150 180 minutes depending on battery type before transition to the Float stage w...

Page 28: ...charging battery age temperature and other factors One very broad guide is to equalize flooded batteries every 1 to 3 months or every 5 to 10 deep discharges Some batteries such as the L 16 group will...

Page 29: ...battery voltage below Float voltage for a combined sixty minutes duration will also force an exit from the Float stage Custom Charging The float exit time out and voltage can also be custom programme...

Page 30: ...lth of the battery LVD set point If the battery discharges to the LVD set point the load will disconnect and a solid red Battery Status LED indication will be displayed General Load Control Notes Do n...

Page 31: ...ack to 0 amps if needed to reduce the heatsink temperature The Appendix B de rating graphs indicate maximum ambient temperatures at which the GenStar MPPT will operate with full rated current as indic...

Page 32: ...pproximately 10 seconds apart If the overload remains after two 2 attempts the load will remain disconnected until power is removed and re applied Remote Temperature Sensor RTS Status LED Flashing red...

Page 33: ...ivate System commands Reboot Control Software resets the GenStar MPPT All controller functions including battery charging and power to the loads will cease until the reboot is complete 5 9 5 External...

Page 34: ...Once extracted save the GenStar firmware file to an easily accessible location e g desktop Serial Firmware Updates For USB C and RS 232 connections the MS Load Firmware Utility must be installed downl...

Page 35: ...for web page and real time clock support Hardware and third party software that supports the MODBUSTM protocol can be used to communicate with a GenStar MPPT Multiple communication ports can be used...

Page 36: ...B and GND wires to GenStar EIA 485 terminals Connect Data A B and GND wires to a desired bus connected controller e g another GenStar NOTE If a desired bus connected EIA 485 compatible controller is...

Page 37: ...ernet network diagrams Ethernet Cable Factory Default Network Settings DHCP Enabled LiveView Web Address http gsmppt serial number1 IP 192 168 1 253 if DHCP is not enabled Subnet Mask 255 255 255 0 Ga...

Page 38: ...its and the load is disconnected The load will automatically reconnect when the heatsink cools to a safe temperature 7 0 TROUBLESHOOTING High Solar Voltage Disconnect Status LED None Battery Status LE...

Page 39: ...ill be limited only to the duration of the original product coverage Morningstar Essentials SeriesTM and SureSineTM inverter products are warrantied to be free from defects in materials and workmanshi...

Page 40: ...8 Volts 12 24 48 Volts 12 24 48 Volts 800 1600 3200 1075 2150 4300 1350 2700 5400 Mechanical 16 45 7 46 Wire Size Range Battery voltage sense and RTS Battery voltage sense and RTS Enclosure IP20 Type...

Page 41: ...size as indicated in Section 310 15 GenStar power terminals are rated for 75 C When wires with a 90 C temperature rating are used with terminals that have a 75 C temperature rating wire ampacity at 7...

Page 42: ...randed Copper Wire Maximum 1 way distance feet 12 Volt system multiply values by 2 for 24 Volt and by 4 for 48V system Wire Size AWG 100A 90A 80A 70A 60A 55A 50A 45A 40A 35A 30A 25A 20A 15A 4 01 23 5...

Page 43: ...5 8 1 10 8 16 1 5 1 7 1 9 2 1 2 3 2 6 2 9 3 4 4 1 5 2 6 9 10 1 3 1 4 1 6 1 8 2 2 2 6 3 2 4 3 6 1 3 1 5 1 9 2 6 4 1 0 1 3 1 7 2 5 0 8 1 1 1 Wires sizes larger than 50 mm2 must be terminated at a splice...

Reviews: