20
INSTALLER
13.6- WATER AND GAS CONNECTIONS
The water and gas pipes must be copper. Do not connect plastic pipes directly to
the heater. It is recommended that the copper is extended to below the floor of
the caravan/vehicle before connecting to plastic.
Ensure the gas pipe complies with the requirements in section 12.7.
Remove any swarf or other residues in the pipes.
Connect the heater using the corresponding joints and connectors supplied in the
bag of accessories.
Mount the cover and fix it to the appliance.
Mount the gas and temperature dial knobs.
13.7- FLUE SYSTEM
The standard horizontal flue kit for the F-11E L is part number RSF003. There are
various other options available, including a vertical flue kit and other variations
on the horizontal kit. Please ask for details. Never use a flue kit not specifically
approved for use with this appliance.
The horizontal pipe may be cut down to size to a minimum of 100 mm, to suit
the installation or extended to a maximum of a straight run of 4 meters. Elbows
are available but each will reduce the available length by 0.8 m.
Installation in a caravan/vehicle will generally require only the use of part no
RSF003.
An external aluminium collar, part no RSF063 can be supplied to make the seal
between the flue pipe and the external wall.
IMPORTANT:
The flue assembly must be installed with a slight downwards incline to prevent the
ingress of rain water, which may damage the heater.