Manual Part No: 932971-01 MD Gas Convection Oven
Page 14 of 32
Manual Rev No: 1
Installation (cont.)
Positioning
Place the appliance in position allowing a minimum gap of 150mm (6
”
) at the rear and at least 150mm
(6
”
) between the sides of the appliance and any adjacent wall. If the appliance is being suited then please
refer to the separate instructions. The minimum distance between the top of the unit and any overshelf
or ceiling constructed of a combustible material must be 600mm (24”), or 450mm (17.7”) for non-
combustible material.
Adequate ventilation is essential for safe operation of a gas appliance. A supply of fresh air is necessary
for the correct combustion of the gas and there must be a means of exhausting the heat and the
products of combustion from the kitchen. It is recommended that the appliance be sited below a
ventilating hood, one preferably connected to an extractor system incorporating a grease filter.
These appliances are to be installed with sufficient ventilation to prevent the occurrence of unacceptable
concentrations of substances harmful to health in the room in which they are installed.
Important Note
The appliance
MUST NOT
be connected
DIRECTLY
to a flue or ventilating system, although the flue
products of two or more appliances may be directed into a common outlet when building suite of
appliances (see separate instructions for suited appliances).
Ensure that the appliance is level in two places – front to rear and side to side. To check the level it is
recommended that a spirit level be placed on a shelf in the open oven –
NOT
on top of the hotplate!
Level can be achieved by adjusting any or all of the screw in feet in each corner of the base. Turn anti-
clockwise to lower and clockwise to raise the corner.
Gas Connection
Natural Gas: The size of the supply pipe should be no smaller than ½” BSP and an easily accessible
stopcock must be fitted in the gas line adjacent to the appliance.
Although a rigid gas pipe is recommended, armoured flexible pipe of a
GAS COUNCIL APPROVED
PATTERN
may be used.
NOTE:
Due to the pressure loss through the snap connection fitting on flexible hoses you must ensure
that the flexible hose, if fitted is capable of passing the required gas flow rate. Check the
requirement on the data plate.