TIY

The Interface Solution Experts   3

Programmable Isolated 

Thermocouple Transmitter

Introduction

Moore Industries’ Programmable Isolated Thermo-
couple Transmitter (TIY) is a 2-wire, microprocessor-
based instrument that converts thermocouple or 
millivolt input into 4-20 mA output.  The output is 
field-configurable to be linear with temperature or 
millivolt input.

The highly accurate TIY features easy-to-use mem-
brane push buttons (referred to as “push buttons” in 
the manual) and solderless jumpers for easy field 
calibration and configuration.   

This manual contains the information necessary to 
calibrate, install, operate, maintain, and troubleshoot 
the TIY.  It includes a brief unit description, a table 
of performance and operational specifications, and 
an explanation of Moore Industries’ model/serial 
number-based product data tracking system. 

The following guidelines are used throughout the 
manual:

WARNING – Hazardous procedure or condition that 
could injure the operator.

Caution – Hazardous procedure or condition that 
could damage or destroy the unit.

Note – Information that is helpful for a procedure, 
condition, or operation of the unit.

Description

The TIY is a loop-powered, thermocouple transmit-
ter that accepts input from standard ISA thermo-
couples (types J, K, E, T, R, S, or N) or a millivolt 
source, and produces proportional 4-20 mA output.  

Front panel push buttons set zero and span (full-
scale) values.  These values remain until they are 
changed by the user.

An LCD provides readouts of the applied input (ei-
ther in temperature or millivolts), displays problem 
codes, and is used for quick ranging. 

Several functions of the TIY are configured with 
solderless jumpers. Each of these jumpers is ac-
cessible without disassembling the unit.  The jump-
er-selectable features include:

•  Reference junction compensation/no reference 

junction compensation

•  Degrees Fahrenheit/Celsius 

•  Upscale/downscale burnout

•  Linearization/no linearization of the output

•  Quick/standard ranging

The TIY is available in two housing styles:  Hockey-
puck (HP) and DIN-style.  The TIY’s application will 
determine which housing style is suitable.

The HP-style housing is equipped with spring clips 
for mounting in an explosion-proof enclosure.  The 
TIY packaged in an HP-style housing and equipped 
with flange plates (FL housing option) is designed 
to mount on a flat surface or on relay tracks (refer 
to the Installation Section).  The all-aluminum DIN-
style housing snaps directly onto standard G-type 
or Top Hat rail.  

The performance and operational specifications for 
the TIY are next.  Refer to the Installation Section 
for the outline dimensions of both housing styles 
and to the Calibration section for span accuracy 
information.

Summary of Contents for TIY

Page 1: ...TIY TIY Programmable Isolated Thermocouple Transmitter May 2016 140 715 00G Programmable Isolated Thermocouple Transmitter...

Page 2: ...ration 7 Setting the Configuration Jumpers 8 Calculating the TIY s Accuracy 10 LCD Readings 11 Standard and Quick Ranging 11 Standard Ranging 12 Quick Ranging 14 Installation 17 Mounting the TIY 17 HP...

Page 3: ...couples types J K E T R S or N or a millivolt source and produces proportional 4 20 mA output Front panel push buttons set zero and span full scale values These values remain until they are changed b...

Page 4: ...ding to SAMA Standard PMC 33 1 protection rates DIN and HP FL Housings 10V m ABC2 0 1 of maximum span for 30V m protection on DIN housing see the RF option 2LG and 2LS HP housing in explosion proof en...

Page 5: ...ied ND No display indicator not provided NL Configured to provide output linear with input rather than linear with temperature jumper selectable RF DIN housing rates 30v m ABC 0 01 of maximum span whe...

Page 6: ...0 21 F 0 60 C 1 08 F 0 50 C 0 90 F 0 40 C 0 72 F 0 15 C 0 27 F 0 08 C 0 14 F Output3 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of span 0 05 of sp...

Page 7: ...ed to ensure that the unit has not sustained any damage during transit and to set zero and span for your application Every unit should be Checked to verify that the appropriate TIY model has been orde...

Page 8: ...echnician s bench or a similar lab type environment Setting the Configuration Jumpers Solderless jumpers are used to configure the TIY s user selectable operating features Figure 1 shows the layout of...

Page 9: ...ORED INSTALLED INSTALLED INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED STORED J309 INSTALLED STORED STORED INSTALLED STORED INSTALLED STORED INSTALLED STORED INSTALLED INSTALLED STORED INS...

Page 10: ...s not temperature and the LCD readings are no longer valid J305 Ranging Method Calibration Stored Standard Ranging Installed Quick Ranging Standard Ranging requires an input source an output monitorin...

Page 11: ...mocouple Range Input Codes Input Code J1 J2 J3 K1 K2 E1 E2 E3 T1 T2 T3 R1 S1 N1 N2 B1 Narrow Input Span 0 15 38 75 C 68 135 F 100 200 C 180 360 F 25 50 C 45 90 F 50 100 C 90 180 F 125 250 C 225 450 F...

Page 12: ...with an LCD the user should disregard the LCD readings and respond only to the readings of the calibration equipment Storing jumper J305 configures the TIY for standard ranging See Figure 1 Figure 2...

Page 13: ...e calibrating 5 Set input to the zero temperature value for the configured TIY range or to the millivolt equivalent as derived from standard thermocouple tables 6 Simultaneously press both ZERO push b...

Page 14: ...TIY output 16 Disconnect calibration equipment If you used a millivolt source to calibrate the unit remove store jumper J301 enable RJC before placing the calibrated unit into service If you will need...

Page 15: ...imultaneously the TIY is configured for Standard Ranging Check J305 See Figure 1 and Table 3 5 Set zero shown on LCD to desired setting using the Up or Down ZERO push button to increment or decrement...

Page 16: ...input value 10 Press either ZERO push button to verify the zero setting Note If the zero input value is incremented too close to the full scale input setting the full scale setting will automatically...

Page 17: ...units hold the unit in place when mounted in explosion proof enclosures The spring clips are squeezed inward to allow for positioning of the unit in the base of the explosion proof enclosure When rel...

Page 18: ...elding the shield should be run all the way from the signal source to the receiving device see Note below The maximum length of un shielded input and output signal wiring should be 2 inches Note Some...

Page 19: ...ions Figure 6 Installing the TIY The LCD During normal operation the LCD typically displays the applied input value As the input changes the readout of the LCD changes accordingly The LCD also display...

Page 20: ...f any Moore Industries product fails to perform up to rated specifications call us for help Our highly skilled staff of trained technicians and engineers pride themselves on their ability to provide t...

Page 21: ...allation diagram for the TIY carrying the intrinsically safe option It also includes guidelines for setting up zener barriers necessary in these types of applications This diagram must be used to augm...

Page 22: ...DIES FOR BREACH OF ANYWARRANTY CONCERNINGTHE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EV...

Reviews: