20 The Interface Solution Experts
Programmable Isolated
Thermocouple Transmitter
TIY
Table 7.
Self-diagnostic Problem Codes
Maintenance
The TIY is designed to operate reliably with a
minimum of field maintenance.
Field maintenance is limited to keeping the unit clean
and the wire terminals free of oxidation. Periodic
visual inspections should be performed to ensure
the unit is clean and the electrical connections are
in good repair. The frequency of these inspections
is based on the environment in which the unit is
operated.
If the TIY is mounted in an explosion-proof enclosure,
the unit will remain cleaner for a longer period of
time than if it is directly exposed to environmental
elements.
To perform a thorough calibration of the TIY, the unit
must be removed from the system and checked out
using standard ranging methods.
Customer Support
Moore Industries is recognized as the industry leader
in delivering top quality to its customers in products
and services. We perform a battery of stringent
quality assurance checks on every unit we ship. If
any Moore Industries product fails to perform up
to rated specifications, call us for help. Our highly
skilled staff of trained technicians and engineers
pride themselves on their ability to provide timely,
accurate, and practical answers to your process
instrumentation questions. Factory phone numbers
are on the back cover.
If problems involve a particular TIY, there are several
pieces of information you can gather before you call
the factory that will help our staff get you answers
more efficiently. When you call, please have:
• The model number of the unit in question.
• The serial number of the unit in question.
• The job number (if available).
• The purchase order under which the unit was
shipped (if available).
Code
P1
P2
P3
P4
P5
Problem
Failed RAM test on power up
Failed ROM checksum on power up
Failed EEPROM checksum on power up
EPROM did not write properly
Bad RJC circuit
Remedy
Cycle DC power; if the problem persists, return unit per instruc-
tions on the back cover of this manual
If power is lost during calibration, repeat calibration; otherwise,
cycle DC power; if the problem persists, return unit per instruc-
tions on the back cover of this manual
Cycle DC power; if the problem persists, return unit per instruc-
tions on the back cover of this manual