Field Installation Diagram: TDZ2 [HP] & THZ2 [HPP] Intrinsically Safe System
For Hazardous 'Classified' Locations
100-100-71
A
CONTROL DRAWING
INITIAL RELEASE
CATEGORY
TITLE
DRAWING NUMBE
R
REVISED BY
DATE
BY
APPROVAL
REVISION
DECIMALS
.X
.XX
.XXX
HOLES
:
=+.003-.002/+.08-.05
ANGLES
:
NOTICE RE PROPRIETARY INFORMATION: This drawing and the inform
-
ation contained herein are the proprietary property of Moore Industries
-
International, Inc. (MII) and should not be reproduced or disclosed to any
third party without the written consent of an authorized officer of MII.
DRAW
N
CHECKE
D
ENGINEER
SCAL
E
DO NOT SCALE DRAWING
TOLERANCE
S
(UNLESS NOTED
)
= ±inch
= ±.1
= ±.03
= ±.01
0
= ± 30
'
/m
m
/2.54
/0.76
/0.25
NONE
06/0
7
Gus H. Elias
S.K.
CB
06/0
7
06/0
7
06/07
G.E
.
Gus H. Elias
CERTIFIED PRODUCT
This is a controlled 'Related' or 'Schedule'
drawing. No modifications are permitted
without the notification and final approval
of the Certification Engineer (related dwgs.)
or the Certifying Agency (schedule dwgs.).
(1)
- Apparatus which is unspecified except that it
must not
be supplied from, or contain under normal or abnormal conditions a source of potential with respect to earth in excess of 250
V
RMS or 250 VD
C
which is considered to be the Safe Area's maximum voltage.
(2)
- The Barrier or other Associated Apparatus
must
be agency-approved (CSA/FM/SAA/SIRA/UL, etc..) per the
"specific"
installation area for Intrinsically Safe connections (Zones 0/1, Class I / Div. 1)
.
US barriers for USA, Canadian barriers for Canada, ATEX bariers for Europe, IECEx barriers where applicable. The outpu
t voltage
(Voc, Vt or Vo)
must no
t exceed
30 VD
C
& the output
current
(Isc, It or Io)
must not
exceed
110 mA
. Also, it
must
be installed per the manufacturer's guidelines.
A Shunt Zener Barrier is NOT required for Non-Incendive / Type N installations
.
(3)
- The combined Capacitance and Inductance of the inter-connecting cables of the device (hazardous area)
must no
t exceed the values indicated on the Associated Apparatus (safe area).
4- For US applications, installation
must
be in accordance to
'ANSI-P12.6'
(Installation of I.S. Systems for Hazardous 'Classified' Locations) and the National Electric Code
'ANSI/NFPA 70
'. Also,
a
dust-tight conduit seal
must
be used when installed in Class II and Class III environments. For applications in Canada, adhere to the 'Canadian Electric
C
ode C22.1' most current publication on I.S.
installationguidelines. For CENELEC/ATEX and IECEx applications, adhere to 'EN 60079-14:1997' or any equivalent IEC-b
ased, most current and pertaining publication on I.S. installation guidelines.
5-
Warning:
Substitution of components is
NOT
allowed as it may impair the Intrinsic Safety of the unit and/or the Non-Incendive circuit.
DO NO
T
open the unit when either energized or if an explosiv
e
gas/dust atmosphere is present. Disconnect power before servicing. Also read, understand and adhere to the manufactur
er's installation and operating procedures.
6- The maximum power parameters of the COM port (to be used only
in safe/non-hazardous areas) are:
V
ma
x
= 3.0 VDC,
I
max
= 300 µ
A,
P
ma
x
= 240
µW
.
Notes:
Barrier or other
Associate
d
Apparatus
Unspecified
Apparatus
(1
)
Non-Hazardous (Safe) Area
Ground Pat
h
Resistance Must Not Exceed
1
Ω
(2
)
Sensor Type - mA, mV,
POT, RTD,
Ω
, T/C
:
V
oc
or
V
t
= 6.51 VD
C
I
sc
or
I
t
= 35.39 mA
P
o
= 57.6 mW
C
a
or
C
o
= 20 µF, Gr. A/
B
C
a
or
C
o
= 498 µF, Gr. C/
D
C
a
or
C
o
= 998 µF, Gr.
D
L
a
or
L
o
= 25 mH, Gr. A/
B
L
a
or
L
o
= 100 mH, Gr. C/
D
L
a
or
L
o
= 200 mH, Gr.
D
Barrier-to-Xmitter Cable:
≤
3,575 ft, 214.5 nF, Gr. A/
B
≤
103,166 ft, 6.19 µF, Gr. C/
D
≤
423,166 ft, 25.39 µF, Gr.
D
+PS
–PS
1
3
TDZ2
CO
M
{
}
= 30 VD
C
= 110 mA
= 0.825
W
= 5.83 nF
= 0
H
≥
C
i
+
C
cabl
e
≥
L
i
+
L
cabl
e
≥
V
oc
or
V
t
≥
I
sc
or
I
t
I.S. Entity Parameter
s
(Power/Loop, +PS & -PS):
V
ma
x
or
U
i
I
max
or
I
i
P
ma
x
or
P
i
C
i
L
i
C
a
or
C
o
L
a
or
L
o
V
max
or
U
i
I
ma
x
or
I
i
Input device must be"Agency-Approved" per application area (CSA, FM, ISSeP, KEMA
,
LCIE, UL, TestSafe, SIRA, TUV, etc....).
+PS
-PS
(3
)
TDZ2 [HP]: 4-20 mA PC-Programmable Smart
HART Temperature Transmitter w/ Display
+PS
-P
S
COM
THZ2 [HPP]: 4-20mA PC-Programmable
Smart HART Temperature Transmitter
4
3
2
1
1
2
3
4
Caution:
The 'COM' Port Must No
t Be Used In Hazardous 'Classified' Locations.
THZ2
0518
IECEx
Hazardous 'Classified' Locations/Areas
US (NEC 500/505) / Canada (C22.2-1010.1)
Intrinsically Safe & Non-Incendive
Class I, Zone 0, AEx ia IIC, (T4 / T5 / T6)*
Class I; Divisions 1 & 2; Groups A-D
ATEX:
II 1G Ex ia IIC,
II 3G Ex nA IIC, (T4 / T5 / T6)*
*T. Codes: T4@85°C (TDZ
2), T5@85°C/T6@60°C (THZ2
)
Operating Temperature Range
:-
40°
C
≤
Tamb.
≤
+85°
C
For areas classified with "dust-hazard" (Class II/III, Division 1,
Groups E, F & G), these devices must be mounted in approve
d
protective enclosures that are rated and suitable for use in th
e
designated application areas. Use +85°C rated electrical wire.
IECEx:
Ex ia IIC, Ex nA IIC, (T4 / T5/ T6)*