Characteristics

Input Power

Input Frequency

Output

Performance Efficiency

Environmental Conditions

Weight

Specifications

117, 220, or 240 Vac (factory-configured according to customer requirement)

48 to 62 Hz

Supply Type:

  Linear

24 or 42 Vdc, 240 mA (factory-configured according to customer requirement),
adjustable ±5.0% with front panel potentiometers

Regulation:

  0.5% maximum, low line to high line

70% typical, rated at full load

Load:

  1.0% maximum, no load to full load

Ripple: 

 50 mV peak-to-peak, maximum

Isolation:

  Input/Output/Unit Housing = 1100 Vrms

Ambient Temperature Operating Range:  0 t

o +70 °C (+32 to +158 °F)

Effect on Unit:

  ±0.03% per °C over the range specified

765 grams (1 pound, 11 ounces)

Table 1.  DPS 240 Equipment Specifications

EXAMPLE

 

 

OutPut Voltage

DPS  /  24VDC   /  240 MA  /  117AC / -FA / [DIN]

    

  

Unit Type

Current

Power

Options(s)

Housing

Summary of Contents for DPS 240

Page 1: ...DPS 240 Milliamp DIN style Power Supply May 2016 221 703 00 E 240 Milliamp DIN style Power Supply DPS...

Page 2: ...l Assistance and Repair our Quick Ship Facility HR DELIVERY 48 Moore Industries CENTER United States Canada TOLL FREE 1 800 999 2900 United Kingdom FREE PHONE 0800 525107 Australia TOLL FREE 008 25192...

Page 3: ...onnection of calibration equipment and a red LED indicator that lights when dc output is present The terminal blocks three for input and eight for out put can be set into either the front or rear pane...

Page 4: ...according to customer requirement adjustable 5 0 with front panel potentiometers Regulation 0 5 maximum low line to high line 70 typical rated at full load Load 1 0 maximum no load to full load Rippl...

Page 5: ...ws the user to set dc out put to 5 0 of the rated value Using the current limit potentiometer the user can calibrate the unit so that the output voltage stays within the specified range even when inpu...

Page 6: ...ure 1 depicts the correct calibration setup for the DPS 240 Before beginning to the calibration itself connect the unit as shown and set the load to 100 ohms for 24Vdc units or 175 ohms for 42 Vdc uni...

Page 7: ...p Calibration Procedure To calibrate the DPS 240 1 Turn CURRENT LIMIT potentiometer fully clock wise 2 Vary setting of VOLTAGE ADJUST potentiometer from fully clockwise to fully counterclockwise Note...

Page 8: ...epresentative or Moore Industries Customer Service Department The use of 14 22 AWG insulated copper wire is rec ommended in connecting the DPS 240 terminals To avoid transients and stray pick ups it i...

Page 9: ...ction of the DPS 240 DPS CURRENT LIMIT OUTPUT ON T T GND AC ACC DC OUT DC OUT GND AC ACC DC OUT DC OUT AC POWRER SOURCE 117 220 OR 240 VAC 2 WIRE TRANSMITTER CURRENT DRIVEN DEVICE POWER SUPPLY VOLTAGE...

Page 10: ...NOTES...

Page 11: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...

Reviews: