background image

Page 5

DPS

12. Use VOLTAGE ADJUST potentiometer to select

output voltage desired.  Disconnect voltmeter from
terminal blocks, and re-connect leads to “+T” and
“–T” test jacks on front panel of DPS 240.

13. Verify that reading at these test jacks is the same

as for terminal block connections.

14. Remove ac input, and dismantle test setup.

The unit is now calibrated and ready to be placed into
service.

Installation

Installing the DPS 240 consists of physically mounting
the device, and then completing the necessary electri-
cal connections.

Mounting

Although the DPS 240 is designed to employ convec-
tion cooling, it is advised to mount it on a surface
made of material that can serve as a heat sink.  Care
should also be taken to locate the DPS 240 in an area
that is protected from dust, moisture, and corrosive
atmospheres.

Figure 2 shows the outline dimensions of the DPS
240.

To mount the unit, the DIN rail should be positioned so
that the smaller of its two flanges is toward the top
(see figure 2).

Tilt the unit slightly backward, and insert the spring
flanges on the back panel under the top flange of the
DIN rail.  Push inward and down until the DPS 240
snaps into place.

To remove the unit, pull outward (from the bottom)
and up.

Calibration Procedure

To calibrate the DPS 240:

1. Turn CURRENT LIMIT potentiometer fully clock-

wise.

2. Vary setting of VOLTAGE ADJUST potentiometer

from fully clockwise to fully counterclockwise.
Note output reading at each extreme. Available
voltage range will equal ±5.0% of unit’s rated out-
put voltage (23.8 to 25.2 Vdc for 24-Vdc models,
or 39.9 to 44.1 Vdc for 42-Vdc models).

3. Use VOLTAGE ADJUST potentiometer to set out-

put voltage to maximum specified for the unit be-
ing calibrated, ±10 millivolts (24, or 42 Vdc, as
appropriate).

4. Reset load to 91ý, or until the milliammeter reads

264 mA (+10% of the maximum rated current out-
put for the DPS 240).

5. Turn CURRENT LIMIT potentiometer counter-

clockwise until output voltage drops to 23.88 Vdc
for 24 Vdc units, or 41.79 Vdc for 42 Vdc units
(99.5% of appropriate nominal output level ).

6. Reset load so that current output is 240 mA.

7. Short the output.

Red “OUTPUT ON” LED on unit’s front panel will
go out.

8. Hold short circuit in place for 1 minute, then re-

move it.  Observe that the LED turns on, and that
output voltage quickly returns to rated nominal,
±10 mV (23.88 Vdc for 24-Vdc units, or 41.79 Vdc
for 42-Vdc units).

9. Remove load.  Observe that output voltage drop is

less than 100 mV.

10. Re-apply load.  Set it so that current output is 240

mA.  Note output voltage reading at this setting.

11. Vary input voltage ±10%.  Observe that voltage

varies less than 0.5%, low-line to high-line.

Summary of Contents for DPS 240

Page 1: ...DPS 240 Milliamp DIN style Power Supply May 2016 221 703 00 E 240 Milliamp DIN style Power Supply DPS...

Page 2: ...l Assistance and Repair our Quick Ship Facility HR DELIVERY 48 Moore Industries CENTER United States Canada TOLL FREE 1 800 999 2900 United Kingdom FREE PHONE 0800 525107 Australia TOLL FREE 008 25192...

Page 3: ...onnection of calibration equipment and a red LED indicator that lights when dc output is present The terminal blocks three for input and eight for out put can be set into either the front or rear pane...

Page 4: ...according to customer requirement adjustable 5 0 with front panel potentiometers Regulation 0 5 maximum low line to high line 70 typical rated at full load Load 1 0 maximum no load to full load Rippl...

Page 5: ...ws the user to set dc out put to 5 0 of the rated value Using the current limit potentiometer the user can calibrate the unit so that the output voltage stays within the specified range even when inpu...

Page 6: ...ure 1 depicts the correct calibration setup for the DPS 240 Before beginning to the calibration itself connect the unit as shown and set the load to 100 ohms for 24Vdc units or 175 ohms for 42 Vdc uni...

Page 7: ...p Calibration Procedure To calibrate the DPS 240 1 Turn CURRENT LIMIT potentiometer fully clock wise 2 Vary setting of VOLTAGE ADJUST potentiometer from fully clockwise to fully counterclockwise Note...

Page 8: ...epresentative or Moore Industries Customer Service Department The use of 14 22 AWG insulated copper wire is rec ommended in connecting the DPS 240 terminals To avoid transients and stray pick ups it i...

Page 9: ...ction of the DPS 240 DPS CURRENT LIMIT OUTPUT ON T T GND AC ACC DC OUT DC OUT GND AC ACC DC OUT DC OUT AC POWRER SOURCE 117 220 OR 240 VAC 2 WIRE TRANSMITTER CURRENT DRIVEN DEVICE POWER SUPPLY VOLTAGE...

Page 10: ...NOTES...

Page 11: ...R BREACH OF ANY WARRANTY CONCERNING THE GOODS OR SERVICES SHALL BE FOR THE COMPANY AT ITS OPTION TO REPAIR OR REPLACE THE GOODS OR SERVICES OR REFUND THE PURCHASE PRICE THE COMPANY SHALL IN NO EVENT B...

Reviews: