MSST5/10-S UserManual
MSST5/10-S UserManual
If the SCL mode will be used with RS-485 communications, the address of each drive will need to
be set. Select the address character and perform the download. Up to 32 drives can be connected
in this manner on a single serial link.
Refer to the SCL Manual for information on sending commands to drives in a multi-axis serial link.
Transmit Delay
If a two wire RS-485 system will be used, the drive(s) and the host use the same pair of wires to
transmit data. The transmit delay may need to be adjusted in order for the drive to give the host
time to disable its RS-485 driver before responding to a command. If the delay is not adjusted data
from the drive might not be received. Applications using RS-232 or four wire RS-485 are not af-
fected as they use separate wires for transmitting data in each direction.
Multi-axis System with MisNet Hub
This option is selected to configure the drive with the correct power up mode if a MisNet motion
control hub will be used to create a multi-axis system. Hubs can be programmed as a stand alone
multi axis system or as a router for SCL commands from a host system.
Refer to the MisNet Hub Programmer and SCL Programming manuals for more information.