background image

XT0016

7

Installation

CPI [Continuous Pilot Ignition] / IPI [Intermittent Pilot 

Ignition] Jumper Cable Installation

“Why use CPI mode”?

There are several reasons why you may choose to use CPI mode. When 

a flue is cold it can be difficult to light the appliance. It can take a bit of 

time (particularly on tall vents) to initialize vent action. This can result 

in  “lifting”  or  “ghosting”  of  the  flames  during  the  first  two  to  three 

minutes of operation. It is also possible to encounter times when the 

fireplace fails to light successfully. The fireplace will then attempt to 

re-light a second or third time depending on prevailing temperatures 

or altitude. When in CPI mode the pilot also keeps the system warm. 

During a “cold” start, condensation will normally form on the inner glass 

surface of the door. This condensation will quickly dry, however, the 

condensation tends to run down the glass and cause some streaking. 

CPI mode helps to resolve this issue. If CPI mode is used during the 

winter months the energy it takes to run the pilot is partially recovered 

as heat into the building, so it does not waste as much energy as running 

a pilot in the off season.
A connector is supplied with this unit that can be plugged into the 

wire harness connected to the controller. This Jumper Cable gives the 

Remote Control the ability to operate the CPI / IPI switch and set the 

unit to operate in either condition. CPI means “Continuous Pilot Ignition” 

or “Standing Pilot” as it is commonly known. IPI means “Intermittent 

Pilot Ignition”, which only initializes the pilot when you are going to be 

using the appliance.

The difference between IPI and CPI:

IPI (Intermittent Pilot Ignition) Mode:  

is a fuel saving mode in 

which the pilot is only used when the main burner is on. 

CPI (Continuous Pilot Ignition) Mode:  

The pilot runs continuously 

even when the main burner is off. (Typically only used for winter 
months)

Installing the CPI Jumper Cable

1).

 Open the control box drawer.

2).

 Remove the bag containing the Jumper Cable from the wire 

harness connected to the controller.

3).

 Find the corresponding plug attached to the control wire harness 

and connect the CPI jumper.

4). 

See operation section to turn remote into CPI mode. 

Figure 19. 

 Open the control box drawer

Figure 19.b 

 Locate Jumper cable

Figure 19.c 

 Connect CPI

Summary of Contents for Proflame 2 RX 300 LP

Page 1: ...Load with Remote THIS KIT IS FOR USE WITH THE FOLLOWING MODELS RX200 B34DT 2 F B34 TOP VENT ELECTRONIC IGNITION IPI B34DR 2 F B34 REAR VENT ELECTRONIC IGNITION IPI B38DT 2 F B38 TOP VENT ELECTRONIC IGNITION IPI B38DR 2 F B38 REAR VENT ELECTRONIC IGNITION IPI PL38DFN F PL38 ELECTRONIC IGNITION IPI PL38DFL F PL38 ELECTRONIC IGNITION IPI PL42DFN F PL42 ELECTRONIC IGNITION IPI PL42DFL F PL42 ELECTRONI...

Page 2: ...it RFK3002R or RFK3004R required 5 Battery backup for the main burner during power outage Before You Begin Ensure that the power supply has been turned off at the breakerorfusebeforebeginning the installation Shut off the gas supply at the shut off valve and ensure that the main burner and pilot light have been turned off and the fireplace has been cooled off for at least two hours before installa...

Page 3: ... and Sensor Wire from connectors X2 and X3 of the control module 3 Disconnect the wall switch harness from X4 Control Module and discard 4 Remove the Valve Harness from X5 of the control module 5 Remove the connector from X1 of the control module 6 Remove the control module from firebox compartment and discard Note module is attached by velcro strips Figure 3 Powercord in PPO box Figure 4 Control ...

Page 4: ...alve body Use a torque screw driver with Torx T20 bit to tighten the two screws to a torque setting of 25 lb in 5 5 Install the enclosed identification label to the valve body Figure 12 G Figure 11 Stepper Motor Installations Figure 12 Label Installation Figure 13 Identification Label NG Figure 14 Identification Label LP Figure 15 New Control Module Figure 16 X1 plug on control module 3 Connect th...

Page 5: ...N OFF sticker supplied to the switch bracket E Battery Holder Installation 1 Secure the battery holder to the fireplace floor using the supplied velcro strips See Figure 22 Note The velcro strips act as an electrical isolation do not attach the battery holder to any metal part without using the velcro strips or the control module will be damaged 2 Connect the red and black wires from the battery h...

Page 6: ...and ensure no leak 5 Turn the fireplace ON and modulate the flame using the remote control and ensure proper operation see Proflame 2 Operation and Maintenance Manual XG0677 Blue Back lit LCD display On Off Key Thermostat Key Up Down Arrow Key Mode Key Figure 24 Proflame Remote Control G Operation with MAIN Power 1 Remove the four batteries from the battery holder 2 Plug the Control Module Power c...

Page 7: ...ially recovered asheatintothebuilding soitdoesnotwasteasmuchenergyasrunning a pilot in the off season A connector is supplied with this unit that can be plugged into the wire harness connected to the controller This Jumper Cable gives the Remote Control the ability to operate the CPI IPI switch and set the unittooperateineithercondition CPImeans ContinuousPilotIgnition or Standing Pilot as it is c...

Page 8: ...WHITE GREEN Lights ON OFF CONTROL MAIN Power 120VAC 60 Hz 6 Amps SPARK SENSOR RED BLACK BATTERY PACK MAIN ON OFF SWITCH YELLOW GREEN PILOT R ORANGE GREEN BLACK BROWN YELLOW ORANGE 6 10 6 OPTIONAL CPI IPI SWITCH WHITE LED Lights LED1 Red LED LED2 Amber LED SW1 LED o tro e r LED power s pp y white white white BLACK WHITE VARIABLE SPEED COMFORT FANS Multicolored LED Lights Fan Kit only available in S...

Page 9: ...place instructions 10 Loop Pilot wires from behind control board drawer to the front Plug into X2 and X3 8 Place Fan wire on leftside firebox floor with adhesive wire pad For fan Install instructions see Optional fan kit Install Replace instructions 11 Valve wires are plugged into the valve in the Green Red and yellow ports respectively Figure 24 e On Off switch through drawer Figure 24 i LED wire...

Page 10: ...ting screws into the valve body Use a standard screwdriver or T20 Torx bit and tighten to the screws with a fixing torque of 251b in 5 IN THE EVENT THAT THE THREADS OF THE VALVE ARE STRIPPED OR DAMAGED REPLACE THE VALVE 7 Install the enclosed identification label G to the valve body where it can be easily seen 8 Make STEPPER MOTOR and valve electrical connections apply gas to system and relight ap...

Page 11: ...XG2021 11 Notes ...

Page 12: ...XT0016 Installation Maintenance Manual PROFLAME 2 UPGRADE KIT RX 200 NG LP RX 300 NG LP ...

Reviews: