Page 15
PL52DF* Indoor Gas Fireplace
XG0218 - 160215
Installation
20”
56”
A
C
B
Unacceptable vent run
within shaded area.
Acceptable vent run
within non-shaded area.
If your installation does not fall
within the venting graph parame-
ters, please contact a local Montigo
Dealer for Power Venting options.
Notes Wall Mounted Terminations: 5"/10" Top & Rear Vent
■ All dimension lengths for vertical or horizontal runs
are measured from center of the vent pipe.
■ Venting runs must fall within the limits set by the
venting graphs, see
Figure 12.
■ Fireplace must be converted to Rear Vent configuration
prior to running vent, see
Figure 7
and
7a
on
Page
10
.
The Venting Graph
Measure the vertical height from the fireplace hearth to the
centre of the termination and the horizontal run from the
fireplace flue collar to the wall flange of the termination. Plot
on the Venting Graph
Figure 12
with an 'X'.
If the 'X' falls on or above the top boundary of the shaded
area, the installation is acceptable.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the
horizontal run to the wall flange of the vent termination is
138", this would be an acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the
horizontal run to the wall flange of the vent termination is
72",
this would not be an acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is
60" and the horizontal run to the wall flange of the vent
termination is 144",
this would not be an acceptable
installation.
Figure 12.
5"/10" Top or Rear
Vent Venting Graph for wall
mounted terminations
.
Figure 12a. 5"/10"
Top Vented, wall mounted installation with one
90° bend. The vent run must comply with Venting Graph for Top
vent, wall mounted terminations, Figure 12
.
Figure 12b.
5"/10"
Rear Vented, wall mounted Multi-elbow
termination installation. The vent run must comply with the
Venting Graph for Rear vent, wall mounted terminations, Figure
12.
8” Max.
56”
Min.
12”
Max.
Flex or Rigid
Section
27”
Min.
28 3/4”
Heat Shiel
d
Te
rmination
Hearth
Exterior
Wall
Flex section
20” Max. for min Vertical
56” Min.
Note:
Images are shown without screens for clarity
purposes. However, your fireplace should not be operated
without proper installation of screens.
Note:
If power venting, vent run must be reduced to 5"/8"
or 4"/7". contact your Montigo dealer to discuss power
venting options.