Page 11
PL52DF* Indoor Gas Fireplace
XG0218 - 160215
Installation
Figure 8
.
(5"/8") Top vent, Roof mounted
termination
with no offset in vent run.
Figure 8a. (5"/8") Top vent, Roof mounted
with 1 offset
(1 offset= two
90° bends).
Figure 8b. (5"/8") Top vent, Roof mounted
with 2 offsets
(1 offset= two
90° bends).
Roof mounted Terminations
The following details are some possible configurations for
Roof mounted terminations.
Section 3-2: Installing a Roof Mounted Direct Vent
Termination (PVTK-1) for 5"/8"
This section applies to installations where the direct vent termination
will be roof mounted.
Section 3-2-1: Venting Layout
Selection of components and details of venting lay out should adhere to
the following guidelines:
The maximum termination point is 32’ above the fireplace
(NOTE: if the maximum termination height is used, the
flame pattern may be affected).
The Vertical termination must be a minimum 2’ higher than
where the termination exits the roofing materials, (asphalt
shingles, cedar shakes, etc). This distance should be
measured from the high side of the roof slope where the
flue flashing intersects the roofing materials. (see
Figures
8 to 8c
).
Termination location must be a minimum 6’ from a
mechanical air inlet.
For a more detailed diagram of allowed termination
locations, see
Appendix A
.
A maximum of two offsets (each offset is made up of 2-90°
bends) may be made for vertical vent runs.
Firestops must be installed as required by National &
local codes
Ensure all horizontal runs are supported with a minimum
of 3 supports per 10’ of venting.
Install all roof flashing and storm collars as shown.
Support ring
Support plate
Firestop
32’ max.
2’ min.
Obstacle
PVTK1
Termination
8’ min.
Support ring
Support plate
Firestop
32’ max.
2’ min.
PVTK1
Termination
8’ min.
PEXT
PXT-10
Adaptor
Flue
Colla
r
Support straps
or
support plate & rin
2’ min.
Firestop
Firestop
Firestop
32’ max
Support plate
& ring
Obstacle
PVTK1
Termination
8’ min.