Page
XG0204 04/05
Panorama Direct Vented Fireplace
Installation
Vertical Vent Installations
Vertical Terminations must be installed:
•
minimum 2' (two feet) above the highest point where
vent passes through the roof.
•
minimum 6' (six feet) from a mechanical air inlet
•
minimum 18" (1 1/2 feet) from a parapet wall.
Maximum vent height is 30 feet above fireplace.
Note: Flame characteristics will change if the maximum vent
height is used.
Minimum clearances 2" from vent to all combustible materials
must be maintained.
A maximum of two offsets
(each offset has two 90° bends)
may
be made if the length of the offsets does not exceed 25% of the
vertical vent height, when measured center to center of piping.
Example:
Typical vent installation.
30' vertical vent
2 - 2' offsets required
25% of 30' = 7-1/2' max. offset allowed
This venting configuration meets requirements.
A - Termination
PVTK-1
B - Flex sections
PFL-1 (12" section)
PFL-2 (24" section)
PFL-3 (36" section)
PFL-4 (48" section)
C - Solid sections
PEXT-1 (12" section)
PEXT-2 (24" section)
PEXT-3 (36" section)
PEXT-4 (48" section)
D - Support Ring & Plate
PSPXT-7 (8" dia.)
E - Firestop
PS-8 (8" dia.)
F - Roof Flashing
PRF-7 (1/12 - 7/12 pitch)
PRF-12 (7/12 - 12/12 pt.)
Figure 10.
Straight, vertical venting. Using the required PXT-10 adap-
tor.
Figure 12.
Vertical venting using 2 offsets (1 offset= two
90° bends).
Figure 11.
Vertical venting with 1 offset Vertical venting with 1 offset
(1 offset= two
90° bends).