Panorama Direct Vented Fireplace

Appendix A - Termination Locations

A

 =  clearance to the termination frame above grade, veranda, porch, 

deck, or balcony [16 inches (41 cm) minimum] 

B

 =  clearance to door, or sides and top of window, that may be opened 

[16 inches (41 cm) minimum for appliances 

100 000 BTU/H 

(30kW)] 

C

 =  clearance to bottom of  window that may be opened horizontally 

[36 inches (92 cm) minimum for appliances 

100 000 BTU/H 

(30kW)] 

D

 =  no clearance to permanently closed window when installed with 

approved glass penetration termination

E

 =  clearance to permanently closed  window [16 inches 41 cm recom-

mended to prevent condensation on window]

F

 =  vertical clearance to ventilated soffit located above the termination 

within a horizontal distance of 2 feet (61 cm) from the centreline of 

the termination [22 inches (56 cm) minimum]

G

 =  clearance to unventilated soffit  

[16inches (41 cm) minimum to non-combustibles]   

[22 inches (56 cm) minimum to combustibles]

H

 =  clearance to outside corner [9 inches (23 cm) minimum]

I

 =  clearance to inside corner [12 inches (31 cm) minimum]

J

 =  * not to be installed above a meter/regulator assembly within  

40" (103 cm) horizontally from the centreline of the regulator

K

 =  clearance to service regulator vent outlet [3 feet  minimum in the 

United States] [*6 feet  (1.8 m) minimum in Canada]

=  clearance to nonmechanical air supply inlet to building or the 

combustion air inlet to any other appliance [16 inches (41 cm) 

minimum for appliances 

100 000 BTU/H (30kW)]

M

 =  clearance to mechanical air supply inlet  

[*6 feet  (1.8 m) minimum]

N

 = 

 clearance above paved sidewalk or a paved driveway located 

on public property [*7 feet (2.1 m) minimum]

P

 =  clearance under veranda, porch, deck, or balcony  

[16 inches (41 cm) minimum

 to non-combustibles] 

[22 inches (56 cm) minimum

 to combustibles]

Q

 =  clearance above a roof [24 inches (61 cm) minimum]

R

 =  clearance to adjacent walls and neighbouring buildings  

[18 inches (46 cm) minimum]

S

 =  clearance from corner in recessed location  

[12 inches (31 cm) minimum]

T

 =  maximum depth in recessed location 

 [48 inches (122 cm) minimum]

U

 =  minimum width for back wall of recessed location 

 [24 inches (61 cm) minimum]

V

 =  no horizontal clearance between the frames of two terminations 

that are level.

W

 =  horizontal clearance between the frames of two terminations 

that are not level.  [36 inches (92 cm) minimum]

 

a vent shall not terminate directly above a sidewalk or paved 

driveway which is located between two single family dwellings 

and serves both dwellings

   only permitted if veranda, porch, deck, or balcony has an open 

side that is equal to or greater than the depth of the enclosed 

area

*

   as specified in CGA B149 Installation Codes. Note: local Codes 

or Regulations may require different clearances

Summary of Contents for Panorama M38DV-PRC

Page 1: ...a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department For Your Safety Do not store or use gasolineorotherflammable vapors and liquids in the vicinity of this or any other appliance C US Installer Leave this manual with the appliance Consumer Leave this man ual for future reference Check local codes and read all instructions prior t...

Page 2: ... as instructed in this manual Consult your local Gas Inspection Branch on installation require ments for factory built gas fireplaces Installation repairs should be done by a qualified contractor Installations in Canada must conform to the current CAN CGA B 149 1 and 2 Gas Installation Code and local regulations This fire place s fans must be electrically grounded in accordance with CSA C22 1 Cana...

Page 3: ...place opening must not project beyond the shaded area shown in Figure 13b For protection against freezing temperatures it is recommended that outer walls of the chase be insulated with a vapour barrier This will reduce the possibility of a cold air convection current on the fireplace Front View WARNING When this appliance is installed directly on carpeting tile or any combustible material other th...

Page 4: ... psig 3 5 kPa Installation Vent Installation This section covers the installation of direct venting and terminations For a detailed diagram of allowed termination locations see Appen dix A Installation Requirements The M38DV PRC fireplace uses Premium venting components with 5 inner dia 8 outer dia Minimum 2 clearance to combustibles required for vent pipes Use only certified Montigo vent componen...

Page 5: ...ect the fireplace s combustion the maximum horizontal vent run is 16 feet The Venting Graph Measure the vertical height from the fireplace hearth to the centre of the termination and the horizontal run from the from the fireplace flue collar to the wall flange of the termination Plot on the Venting Graph Fig 6 with an X If the X falls on or above the top boundary of the shaded area the installatio...

Page 6: ...no vertical lift is 12 See Figure 7 Example A rigid section and an elbow used in conjunction with 3 ft flex section PFL 3 will when extended in a chase allow for a maximum horizon tal run of twelve and one half feet from the centre of the fireplace to outside wall and a minimum of 7 6 when retracted in opposite direc tion See Figure 8 and 9 C flex sections and D solid sections may be used in conju...

Page 7: ...offsets does not exceed 25 of the vertical vent height when measured center to center of piping Example Typical vent installation 30 vertical vent 2 2 offsets required 25 of 30 7 1 2 max offset allowed This venting configuration meets requirements A Termination PVTK 1 B Flex sections PFL 1 12 section PFL 2 24 section PFL 3 36 section PFL 4 48 section C Solid sections PEXT 1 12 section PEXT 2 24 se...

Page 8: ...moval of glass door Installation Mantels Surrounds NOTE Mantel clearances are for fire hazard prevention to combus tible materials New technology to meet consumer and government demands for the wise use of energy has prompted us to manufacture many models of fireplaces which are hot fuel and energy efficient Please be aware temperatures over the mantel will rise above nor mal room temperature and ...

Page 9: ...h 4 fans for circulating heat into the living space Installations in Canada must be in accordance with CSA C22 1 Canadian Electrical Code Part 1 and or Local Codes Installations in the USA must be in accordance with local codes or in the absence of local codes with the National Electrical Code ANSI NFPA 70 1987 Fan Switch M38DV Removing and Installing the In ner Doors Door Removal The inner combus...

Page 10: ...al The ember material is supplied in two packages Place the material evenly along the front ember burner tube next to log A Refer to figure 15b Burner Adjustment The M38DV PRC is equipped with an adjustable burner allowing you to raise or lower the flames To adjust the flames locate the black knob marked Hi Lo in the centre of the gas control valve See Figure 16 The front burners are not adjustabl...

Page 11: ...l the Fire To Turn Off Gas To Appliance Operation Model M38DV PRC 3 Push in gas control knob slightly and turn clock wise to Off Do not force 4 Replace lower trim 1 Turn off remote switch 2 Remove lower trim 1 STOP Read the safety information above on this label 2 Remove lower trims 3 Push in gas control knob and turn clockwise to OFF 4 Wait five 5 minutes to clear out any gas Smell for gas includ...

Page 12: ... To Turn Off Gas To Appliance 1 STOP Read the safety information above on this label 2 Flip down the lower trims 3 If the switch on the control module is set to Continuous Pilot Off then the pilot will light when the appliance is turned on by the remote switch When switched to Continuous Pilot On then the control module will attempt to light the pilot until it detects that the pilot has been succe...

Page 13: ... area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor What To Do If You Smell Gas Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Immediately call your gas supplier from a neighbour s phone Follow the gas supplier s instructions 1 Turn off remote switch 2 Remove lower trim Gas In...

Page 14: ...s on new metal Glass must be cleaned periodically to remove any film a normal bi product of combustion which may be visible Film can easily be removed by removing the door as shown on page 10 Handle the door carefully and clean it with glass cleaners One of the most effective products is Kel Kem Silicone seals on inner door during initial firing will off gas leaving a visual deposit of a white sub...

Page 15: ...The following is a troubleshooting chart of possible problems PROBLEM CORRECTIVE ACTION Noisy Pilot Flame Locate pilot adjustment screw on the front of the gas control valve Flame is decreased by turning adjustment screw clockwise Pilot won t ignite Disconnect remote wires and try to light pilot If pilot now works remote connections are faulty Check wiring diagram figure 19 Main burner will 1 Chec...

Page 16: ... Compa nies 2 The Montigo Gas Appliance must be subjected to normal use The Gas Appliances are designed to burn gas only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the Gas Appliance will produce excessive temperatures and will result in a fire hazard Limitations On Liability It is expressly agreed and understood that The Companies sole oblig...

Page 17: ...um in the United States 6 feet 1 8 m minimum in Canada L clearance to nonmechanical air supply inlet to building or the combustion air inlet to any other appliance 16 inches 41 cm minimum for appliances 100 000 BTU H 30kW M clearance to mechanical air supply inlet 6 feet 1 8 m minimum N clearance above paved sidewalk or a paved driveway located on public property 7 feet 2 1 m minimum P clearance u...

Page 18: ...gley BC V4W 4A1 When contacting dealer or Montigo please have the following ready Your name and address Part number and description of part or accessories to be replaced Model and serial numbers of your heaters Type of Gas used Natural Gas or LP Propane gas M38DV PRC M38DV PRC I 1 Valve NG RGC1006 RGC1004 2 ValveLPG RGC1005 RGC1003 3 Pilot Ass NG RPA020 RPA003 4 Pilot Ass LPG RPA021 RPA004 5 Piezo...

Page 19: ...Page 19 XG0204 04 05 Panorama Direct Vented Fireplace Notes ...

Page 20: ...XG0204 04 05 Page 20 Panorama Direct Vented Fireplace Notes ...

Page 21: ...XG0204 04 05 Page 21 Panorama Direct Vented Fireplace Notes ...

Page 22: ...Canadian Heating Products Inc Langley BC V4W 4A1 Montigo Del Ray Corp Ferndale WA 98248 XG0204 011707 ...

Reviews: