15
Installation
XG0207 - 170223
Figure 8.
Straight run, Side Vented, wall mounted termination for H*38DF*-ST
Figure 8.
Side Vented, wall mounted Multi-elbow termination installation. Installation for
H*38DF*-ST must have a minimum vertical rise of 48"
Figure 8.
Side Vented, wall mounted Multi-elbow installation
Selection of components and details of venting layout should adhere
to the following guidelines:
• Vent terminations must not be recessed in walls or siding.
• For Heat Shield requirements see Section 3-3.
• Once the proposed venting layout has been determined refer to
graph to ensure the layout is acceptable.
Notes Wall Mounted Terminations: SIDE VENT
• All measurements for vertical or horizontal runs are measured from
center of the vent pipe.
• Venting runs must fall within the limits set by the venting graph.
Example A: (Acceptable Installation)
If the vertical dimension from the hearth is 120" and the horizontal
run to the wall flange of the vent termination is 138", this would be an
acceptable installation.
Example B: (Unacceptable Installation)
If the vertical dimension from the hearth is 48" and the horizontal run
to the wall flange of the vent termination is 96", this would not be an
acceptable installation.
Example C: (Unacceptable Installation)
If the vertical dimension from the floor of the fireplace is 72" and the
horizontal run to the wall flange of the vent termination is 120", this
would not be an acceptable installation.
Side Venting Graph
Measure the vertical height from the fireplace hearth to the centre of
the termination and the horizontal run from the fireplace flue collar to
the wall flange of the termination. Plot on the Venting Grap with an 'X'.
If the 'X' falls on or above the top boundary of the shaded area, the
installation is acceptable.
H38DFST SIDE VENT RUN
Figure 9.
H38DFST Side Vent Venting Graph for wall mounted terminations
0
HEARTH
12
12
0
60
36
84
120
24
72
108
48
96
132
Vertical Height (In.)
Horizontal Run (In.)
36
60
84
108
132
156
24
48
72
96
120
144
168 180
Acceptable vent run
within non-shaded area.
Unacceptable vent run
within shaded area.
A
B
C
Exterior
Wall
Hearth
Hearth
Termination
Flex or Rigid
Heat Sheild
Heat Sheild
PXT Extention
33
½
''
12''
48''
42''
32½''
Max.
48''
Max.
14½''
Min.
33½''
12''
Max.
30''
Max.
192'' Max.
12'' Max. horozontal
run with no vertical lift
Termination
Rigid
Section
Flex
Section