background image

15

Installation

XG0207 - 170223

Figure 8. 

 Straight run, Side Vented, wall mounted termination for H*38DF*-ST

Figure 8. 

  Side Vented, wall mounted Multi-elbow termination installation. Installation for 

H*38DF*-ST must have a minimum vertical rise of 48"

Figure 8. 

   Side Vented, wall mounted Multi-elbow installation

Selection of components and details of venting layout should adhere 

to the following guidelines:
•  Vent terminations must not be recessed in walls or siding.
•  For Heat Shield requirements see Section 3-3.
•  Once the proposed venting layout has been determined refer to 

graph to ensure the layout is acceptable.

Notes Wall Mounted Terminations: SIDE VENT

•  All measurements for vertical or horizontal runs are measured from 

center of the vent pipe.

•  Venting runs must fall within the limits set by the venting graph.

Example A: (Acceptable Installation)

If the vertical dimension from the hearth is 120" and the horizontal 

run to the wall flange of the vent termination is 138", this would be an 

acceptable installation.

Example B: (Unacceptable Installation)

If the vertical dimension from the hearth is 48" and the horizontal run 

to the wall flange of the vent termination is 96", this would not be an  

acceptable installation.

Example C: (Unacceptable Installation)

If the vertical dimension from the floor of the fireplace is 72" and the 

horizontal run to the wall flange of the vent termination is 120", this 

would not be an  acceptable installation.

Side Venting Graph

Measure the vertical height from the fireplace hearth to the centre of 

the termination and the horizontal run from the fireplace flue collar to 

the wall flange of the termination. Plot on the Venting Grap with an 'X'.

If the 'X' falls on or above the top boundary of the shaded area, the 

installation is acceptable.

H38DFST SIDE VENT RUN

Figure 9. 

 H38DFST Side Vent Venting Graph for wall mounted terminations

0

HEARTH

12

12

0

60

36

84

120

24

72

108

48

96

132

Vertical Height (In.)

Horizontal Run (In.)

36

60

84

108

132

156

24

48

72

96

120

144

168 180

Acceptable vent run 

within non-shaded area.

Unacceptable vent run 

within shaded area.

A

B

C

Exterior 

Wall

Hearth

Hearth

Termination

Flex or Rigid

Heat Sheild

Heat Sheild

PXT Extention

33

½

''

12''

48''

42''

32½''  

Max.

48''  

Max.

14½''  

Min.

33½'' 

12''  

Max.

30''  

Max.

192'' Max.

12'' Max. horozontal 

run with no vertical lift

 

Termination

Rigid 

Section

Flex 

Section

Summary of Contents for H38DFSTL

Page 1: ...Propane Gas H38DFSTNI Natural Gas H38DFSTLI Propane Gas Read and understand this manual Improper installation adjustment alteration service or maintenance can cause serious injury property damage or even death For assistance or additional information consult a qualified installer service agency or the gas supplier A barrier designed to reduce the risk of burns from the hot viewing glass is provide...

Page 2: ...on Information See Appendix B The Montigo warranty will be voided by and Montigo disclaims any responsibility for the following actions Modification of the fireplace and or components including Direct Vent assembly or glass doors Use of any component part not manufactured or approved by Montigo in combination with this Montigo fireplace system Installation other than as instructed in this manual C...

Page 3: ...Finishing 25 Mantels Surrounds 25 Fireplace Facing 25 Finishing around the fireplace 25 Flush Finishing the Fireplace 25 Section 7 Screen Installation and Removal 26 Removing the Screen 26 To Install Screens 26 Replacement Screens 26 Section 8 Installing Removing the Door 27 Removing the door 27 Reinstalling the door 27 Section 9 Installing the Accessories 28 H38ST Installing the Logs and Embers 2...

Page 4: ...alinstallations mustconformtothelocalcodesor intheabsenceoflocalcodes to the current version of Canadian Electrical Code CSA C22 1 1 Installations in the USA must conform to the local codes or in the absence of local codes to the current version of National Fuel Gas Code ANSI Z223 1 NFPA 54 Electrical installations must conform to the local codes or in the absence of local codes to the current ver...

Page 5: ...ning proper clearance Firestops installed Exteriorwall roofflashinginstalledandsealedincompliancewithlocalbuildingcode Terminations installed and sealed in compliance with local building code Direct vent termination is highest point in vent assembly Wiring Electrical Section 4 Unswitched power provided to the appliance PPO box Low voltage wire connected to dry contact wall switch non powered Gas S...

Page 6: ...te Sample Figure 1 1 Rating Plate for standing pilot Figure 1 2 Rating Plate for IPI electronic ignition LBL1205 V6 1 Stand Pilot Screen DEC06 2014 Teklynx LabelView Demo LB1223 V5 1 SIT IPI with screen DEC06 2014 Teklynx LabelView Demo ...

Page 7: ...1 43 5 16 640 25 3 16 927 36 1 2 1030 40 9 16 175 6 7 8 927 36 1 2 127 5 203 8 959 37 3 4 305 12 610 24 HS38DF ST DIMENSIONS TOLERANCES ARE IN METRIC MM 1 6 MM IMPERIAL FRACTIONAL 1 16 THE INFORMATION CONTAINED IN THIS DRAWING IS THE SOLE PROPERTY OF CANADIAN HEATING PRODUCTS ANY REPRODUCTION IN PART OR AS A WHOLE WITHOUT THE WRITTEN PERMISSION OF CANADIAN HEATING PRODUCTS IS PROHIBITED PROPRIETAR...

Page 8: ...r shelves over the fireplace Top vent Figure 3 b Combustible Framing for shelves over the fireplace Side vent Figure 3 b Non Combustible Framing with alcove above fireplace Right side Combustible Framing above fireplace Left side see figure 2 Top Vent A B C D E H38DFST 40 42 N A 23 40 H42DFST 45 49 46 24 45 1 Min Non combustible nailing flange supplied Both sides typical Non combustible materials ...

Page 9: ...ons the minimum clearance is 2 from the Side of the fireplace to a wall and 12 clearance from the top of the fireplace to the underside of any combustible shelf materials For Top Vent applications the minimum clearance is 2 from the Side of the fireplace to a wall and 19 to the underside of any combustible shelf materials 1 clearance is maintained on sides and bottom of vent runs and 2 above horiz...

Page 10: ... the termination location has been established refer to the appropriate section below for installation details All fireplaces shipped from the factory are top vent Silicone application is NOT required when joining Montigo vent pipes and components Section 3 1 Converting to Side Vent Use the following instructions to convert a unit for side vent use Remove the Side flue cover and gasket 5 and 8 on ...

Page 11: ...st be a minimum 18 from a parapet wall For a more detailed diagram of allowed termination locations see Appendix A A maximum of two offsets each offset is made up of 2 90 bends may be made for vertical vent runs Firestops must be installed as required by National local codes Ensure all horizontal runs are supported with a minimum of 3 supports per 10 of venting Install all roof flashing and storm ...

Page 12: ...lation XG0207 170223 Figure 6 d Side vent Roof mounted venting 1 90 bend Storm collar Support plate 32 max Roof flashing MVTK1 Termination Support ring PEXT Solid Sections 2 min 12 max Firestop Firestop 90 Elbow ...

Page 13: ... the interior side of the studs concrete or finished wall construction using a minimum of 4 screws 3 Insert the termination into the MOSR frame as shown here from the inside and attach to the MOSR by installing a min quantity of 4 bolts into the threaded nuts on the MOSR Frame Installation of termination frame at time of framing in masonry Terminations with a BSR frame allow the installation of th...

Page 14: ...flange of the termination Plot on the Venting Graph with an X If the X falls on or above the top boundary of the shaded area the installation is acceptable H38DFST TOP VENT RUN Example A Acceptable Installation If the vertical dimension from the hearth is 114 and the horizontal run to the wall flange of the vent termination is 168 this would be an acceptable installation Example B Unacceptable Ins...

Page 15: ... dimension from the hearth is 48 and the horizontal run to the wall flange of the vent termination is 96 this would not be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termination is 120 this would not be an acceptable installation Side Venting Graph Measure the v...

Page 16: ...ination Plot on the Venting Graph with an X If the X falls on or above the top boundary of the shaded area the installation is acceptable H42DFST TOP VENT RUN Example A Acceptable Installation If the vertical dimension from the hearth is 120 and the horizontal run to the wall flange of the vent termination is 138 this would be an acceptable installation Example B Unacceptable Installation If the v...

Page 17: ...tallation If the vertical dimension from the hearth is 48 and the horizontal run to the wall flange of the vent termination is 96 this would not be an acceptable installation Example C Unacceptable Installation If the vertical dimension from the floor of the fireplace is 72 and the horizontal run to the wall flange of the vent termination is 120 this would not be an acceptable installation Side Ve...

Page 18: ...egrity of internal supports For flex venting place the springs supplied with the pipe kit between the outer and inner pipes to keep the pipes separate and avoid any possible hot spots Montigo recommends the use of a flex section for the final pipe connected directly to the fireplace offering greater flexibility of installation and absorption of movement Firestops must be installed as required by N...

Page 19: ...VA AD M1 not required when using raw flex 58DVA 36FO 36 Section 58DVA 60FO 60 Section 58DVA 120FO 120 Section 4DVKIT58X01 4DVKIT58X01 5 4DVKIT58X02 4DVKIT58X03 4DVKIT58X04 4DVKIT58X06 Rigid Pipe Extension PXT12 12 f f PXT20 20 f f 58DVA 08A 12 58DVA 16A 20 5DLT 12 5DLS1 12 5DLT2 20 5DSL2 20 5DAL 3 to 10 5DT AJ12 12 Rigid Telescopic Pipe 58DVA 17TA 58DVA 24TA 5DLA30 Elbows 5 8 Vent PEL 90MM m m 90º...

Page 20: ...llars Reduce horizontal run by 36 for each 90 offset after the first one Support straps OR Support ring and plates Support straping Must convert from flex to rigid before termination Support ring and plates Support horizontal section every 2 with plumbers strapping Flex sections can be connected with a coupler providing 3 screws are used on each side and the seam is sealed with high temperature si...

Page 21: ...er section from the outside of the structure To complete the installation fasten the Heat Shield Outer Section Termination frame to the structure Figure 15 e RHS101 Installation Figure 15 c RHS101 Installation Install by sliding Outer Section over vent pipe where it passes through the combustible construction Figure 15 a RHS8 Installation Install by sliding over vent pipe where it passes through t...

Page 22: ...ce depending on the model of the unit Use only low voltage wire and DO NOT connect any external power to the remote switch Ifanyoftheoriginalwiresuppliedwiththeapplianceisreplaced it must be replaced with the same type or its equivalent NOTE The switch location must not exceed 30 from the fireplace 1 5V AA type 1 5V AA type 1 5V AA type 1 5V AA type BLACK WHITE GREEN To PPO SPARK SENSOR RED BLACK ...

Page 23: ... remote operating instructions In order to start your pilot turning the main burner on with the switch remote or thermostat and then turning it off will reactivate the continuous pilot mode and reset the seven day timer A jumper is supplied with this unit that can be plugged into the wire harness connected to the controller This jumper cable gives the Remote Control the ability to operate the POD ...

Page 24: ...NY KIND TO TEST FOR LEAKS PRESSURE REQUIREMENTS Gas Pressure Natural Gas Propane Minimum inlet pressure 5 5in w c 11in w c Manifold pressure 3 5in w c 10in w c Section 5 Installing the gas line After gas line is connected each appliance connection valve and valve train MUST be checked while under normal operating pressure with either a Liquid Solution or Leak Detection Device to locate any source ...

Page 25: ...talled over the face of the unit as shown below Please be aware that the temperature of the fireplace face will be extremely hot and could be subject to cracking in seams of concrete board or tile installed directly on the face Please refer to the flush face finishing guide for more detailed instructions Figure 21 ddd Flush facing vs Standard vs High style HIGH STYLE FINISHING STANDARD FINISHING F...

Page 26: ... after the fireplace has been turned off Safety screens are mandatory while glass is hot and can reduce the risks of severe burns Please keep children away from the fireplace at all times CAUTION NOTICE Screen Bottom Tabs Screen Tab Receptacles Upper Screen Studs Upper Screen Stud Catch Left Side Detail Left Side Detail Removin The Safe To Remove t Simply gra outer corn with your finger and you On...

Page 27: ...oor on either side usually midway and lift upward lift the door carefully up and away from the front of the fireplace Place the door aside in a safe place while maintenance and or cleaning is being performed Removing the door The doors are removed in a few simple steps Follow these below to remove the horizontal access panel unlatch the door buckles and remove the door Replace in reverse order Rei...

Page 28: ...ion Place Logs C on top of Logs A Indentations on top of Logs A INSTALLING THE EMBER MATERIAL The ember material is supplied in two packages Place the material evenly forward of both Log stands under logs A and B also forward from Logs C D Refer to figure 25b Ensure the burner holes are free of ember material after placing the embers STEP 4 Completed Installation Figure 22 c Figure 22 c Figure 22 ...

Page 29: ...y pose potential safety hazards damage to the appliance and void manufacturer s warranty Linear Conv Installing the Firestones or optional Fireglass TheHL DF STfireplaceissuppliedwithfirestones RemovetheDoor s as shown on page 24 Follow these instructions to ensure all parts are removed or replaced as required Once the glass door s is removed place the firestones randomly across the pan as describ...

Page 30: ...F unless knob is pushed in slightly Do not force Standing Continuous Pilot Ignition SIT NOVA 820 with American Flame Electronic Ignition For Your Safety READ BEFORE LIGHTING C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call a qualified service technician Force or attempt to repair may result in a fi...

Page 31: ... the Troubleshooting section Repeat step 5 9 If the system will not function correctly follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier 1 STOP Read the safety information above on this label 2 Remove the lower Horizontal access panel 3 Turn ON manual ON OFF switch located below the horizontal access panel if available 4 Turn Incoming gas valve t...

Page 32: ...oflame 2 Control Module 4 Wiring Harness 5 Variable Speed fans If applicable 7 Proflame 2 remote control 8 Battery Pack 9 Manual override switch NOTE Can not be used with home automation systems SW1 Programing Button LED1 Red Diagnostic Light LED2 Amber Programing Remote Control Light Blue back lit LCD display On Off key Thermostat key Up Down arrow key Mode key Not Used Not Used CPI mode optional...

Page 33: ...ur 4 times to indicate transmitter s command is accepted The System is now initialized Temperature Indication Display With the system in the Off position press the Thermostat Key and the Mode Key at the same time Look at the LCD screen on the Remote Control to verify that a C or F is visible to the right of the Room Temperature display Turn On the Fireplace With the system Off turn the master over...

Page 34: ...o show that the room thermostat is On and the set temperature is now displayed To adjust the set temperature press the Up or Down Arrow Keys until the desired set temperature is displayed on the LCD screen of the Transmitter Smart Thermostat Remote Control Operation The Smart Thermostat function adjusts the flame height in accordance to the difference between the set point temperature and the actu...

Page 35: ...s to turn on off or adjust the fan speed A single beep will confirm reception of the command Disabling Thermostat Some jurisdictions and bedroom installations require the thermostat to be disabled 1 Partially take out one battery see Figure 27k 2 Insert the battery while holding down the thermostat button The remote screen will display Clr while the button is held down See Figure 27l 3 To enable t...

Page 36: ...uring the initial firing Silicone seals will off gas leaving a visual deposit of a white substance on combustion chamber walls This can easily be removed using normal household products Use a vacuum cleaner or whisk broom to keep the control compartment burner and firebox free from dust and lint Figure 28 Hi Lo Adjustment on the SIT Nova 820 gas valve Figure 28 b Hi Lo Adjustment on the SIT Profla...

Page 37: ...d Pressure are within acceptable limits Pilot lights but Main burner will not Light and igniter continues to spark 1 Check the Pilot Flame Sensor Rod and clean with steel wool or similar 2 Check the Pilot hood and clean with steel wool if dirty 3 Adjust pilot flame using the pilot adjustment screw if the pilot flame is too long or too short Flame should fully engulf the sensor rod and must be stab...

Page 38: ...2 Thermopile RPG001 RPG001 Piezo Ignitor PIEZO PIEZO Pilot Tubing RPTA03 RPTA03 Door RDTH38 RDTH42 Replacement Screen RSCH38 RSCH42 Replacement Parts List SIT IPI Proflame 2 Part H38DFST H42DFST Log Set RLGS47 RLGSH42ST NG Gas Valve hi low RGC3044 Propane Gas Valve hi low RGC3045 NG Gas Valve with stepper motor RGC3033 Propane Gas Valve with stepper motor RGC3034 NG Pilot Assembly RPA035 Propane P...

Page 39: ...ng fireplace penetration of an exterior building envelope Dimension A X 75 min overhang depth The overhang must extend at least 75 of the roof line height A Height is measured from bottom of fireplace opening to the ceiling Follow all product installation instructions including framing clearances to combustibles mantel heights Facing Requirements venting installation etc Use supplied safety screen...

Page 40: ...mbustion air inlet to other appliance for appliance 100 000 BTU H 30 KW 12 inches 12 inches M clearance to forced air supply inlet 6 feet 3 feet above air inlet N clearance above paved sidewalk or paved driveway located on public property 7 feet 7 feet P clearance under veranda porch deck or balcony 22 inches to combustibles 16 inches to non combustibles 22 inches to combustibles 16 inches to non ...

Page 41: ...um LP only Burning conventional fireplace fuels such as wood coal or any other solid fuel will cause damage to the appliance produce excessive temperatures will result in a fire hazard and void all warranties This warranty is transferable The appliance must remain in its original place of installation to be valid If the components of the appliance covered by this warranty are found to be defective...

Page 42: ...ritten consent of The Companies The Companies shall in no event be responsible for any warranty work done without first obtaining the Companies written consent The Companies employees and dealers have no authority to make any warranties to neither alter this warranty nor authorize any remedies in addition to or inconsistent with those stated within this warranty IF WARRANTY SERVICE IS NEEDED To ma...

Page 43: ...The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Appendix C Amendment Gas Fireplace Equipment sold in the State of Massachusetts 5 08 Modifications to NFPA 54 Chapter 10 4 INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless upon ...

Page 44: ...XG0207 170223 Installation Maintenance Manual H38DFST H42DFST H38DFST H42DFST See Through Gas Fireplace See Through Gas Fireplace ...

Reviews: