Lagged housing Version Mounting:  

(See Figure 6)

1)

 Select a mounting location in accordance with the Pre-

    Installation Recommendations.

2)

 Cut a hole into the side/top of the vessel corresponding to 

    the coupling used.  

3)

 Weld coupling to the vessel wall.  

4)

 Insert probe through coupling and thread unit tightly into 

    place by gripping and rotating the 15/16 inch (24 mm) 

    wrench flats provided on fitting closest to mounting point.  

    Do not use sealant tapes (e.g. Teflon tape) or putties.  If flats

    are inaccessible due to tank insulation, thread unit into place

    by gripping and rotating lagging pipe with a strap/pipe 

    wrench. Continuity between sensor mounting point and vessel

     wall must be maintained to assure proper probe operation.

3

MECHANICAL INSTALL ATION

Standard, Food Grade, Stub, Cable Extension and Remote

Probe Mounting:  

(See Figures 3, 4 & 5)

1)

 Select a mounting location in accordance with the Pre-

    Installation Recommendations.

2)

 If using a welded coupling, cut a hole into the side/top of the 

     vessel corresponding to the mounting connection (i.e. 1-1/2” 

     BSPT, 1-1/4” NPT or 3/4” NPT). If using a Monitor mount-

    ing plate, cut a 2-1/2 inch (64 mm) center hole and six 11/32

    inch (9 mm) mounting holes (for 5/16” bolts) on a 7 inch (178

    mm) bolt circle.  Use mounting plate gasket as a template.

3)

 Weld coupling or attach mounting plate to vessel wall.  

4)

 Insert probe through coupling.  Do not use sealant tapes (e.g.

     Teflon tape) or putties. When using the 1-1/2” BSPT or 

    1-1/4” NPT connection, grease threads with anti-seize then

    thread unit tightly into place by gripping and rotating hous-

    ing.  When using the 3/4” NPT connection, thread unit tight-

    ly into place by gripping and rotating 15/16 inch (24 mm) 

    wrench flats provided on fitting.  Continuity between sensor

    mounting point and vessel wall must be maintained to 

    assure proper probe operation.

Figure 4

Figure 3

Figure 5

Figure 6

DIMENSIONS ARE ShOwN IN INChES wITh MILLIMETER EquIVALENT IN bRACKETS

Summary of Contents for TrueCap MK-2

Page 1: ...o will ensure proper operation of the equipment and the safety of all personnel Before discarding shipping container please inspect it thoroughly and verify that all parts ordered are accounted for So...

Page 2: ...low into and out of the ves sel Insure that the expected swing of the cable will not touch the vessel 3 Driven Shield Penetration Select a location which ensures that the driven shield section protrud...

Page 3: ...ion in accordance with the Pre Installation Recommendations 2 If using a welded coupling cut a hole into the side top of the vessel corresponding to the mounting connection i e 1 1 2 BSPT 1 1 4 NPT or...

Page 4: ...ion and the mains outputs Remove electronics 4 backpanel screws prior to drilling holes 3 The Remote Electronics for Hazardous Locations has three conduit entrances one of which is plugged at the fact...

Page 5: ...DV B0051 3 50 x 3 00 A 09 13 16 ISOLATED LINES LOAD L L LOAD LINES ISOLATED L L DCV L1 N ACV RECOMMENDED NOT CRITICAL NO2 NC2 COM2 WIRING DIAGRAM ADV B0051 3 50 x 3 00 A 09 13 16 ISOLATED LINES LOAD L...

Page 6: ...ON LEDS RED PUSHBUTTON CALIBRATION LED YELLOW DETECTION LED GREEN CALIBRATION LEDS RED SE PUSHBUTTON CALIBRATION LED YELLOW DETECTION LED GREEN CALIBRATION LEDS RED S PUSHBUTTON CALIBRATION LED YELLOW...

Page 7: ...ion 2 Set the time delay desired from 25 to 15 seconds 3 Select sensitivity 1 2 3 or 4 Figure 10 provides a guide for initial setup This may have to bere selected depending upon the actual application...

Page 8: ...should periodically be observed for any signs of contamination caused by improper enclosure protection i e insure cover is fully engaged and that wire entries are properly sealed Cleaning Requirements...

Page 9: ...31 x 50 SLOT 7 9 x 12 7 31 x 50 SLOT 31 x 50 SLOT 7 31 x 50 SLOT 7 31 x 50 SLOT 7 9 31 x 50 SLOT 7 9 31 x 50 SLOT 7 9 x 31 x 50 SLOT 7 9 x 31 x 50 SLOT 7 9 x 1 31 x 50 SLOT 7 9 x 12 31 x 50 SLOT 7 9 x...

Page 10: ...y Switch selectable 0 5pf 2 6pf 8 3pf 18 0pf Stability 0 01pf per degree F 0 018pf per degree C 0 5pf setting Time Delay 0 25 to 15 sec single turn adj for delay to activate delay to de activate Fail...

Reviews: