5.
Overload Delay
:
Setting
:
10~300(Second)
Default
:
40
Description
:
When overload occurres, timer starts before activating protection
6.
Short Detect
:
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates AC short protection
7.
Short protect:
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop)
Default
:
4
Description
:
Setup the action when AC short occurs
8.
Short Set Point
:
Setting
:
1~31
1~5(A)
2~10(A)
3~15(A)
4~20(A)
6~30(A)
8~40(A)
10~50(A)
12~60(A)
15~75(A)
16~80(A)
20~100(A)
30~150(A)
40~200(A)
50~250(A)
60~300(A)
80~400(A)
100~500(A)
120~600(A)
150~750(A)
160~800(A)
180~900(A)
200~1000(A) 240~1200(A)
300~1500(A)
320~1600(A)
400~2000(A)
500~2500(A) 600~3000(A)
640~3200(A)
800~4000(A)
1000~5000(A)
Description
:
When
current
is
above
the setting, controller outputs trip signal, setup range is
related to the CT ration setup.
9.
Short Delay
:
Setting
:
0.1~1.0(Second)
Default
:
0.2
Description
:
When AC short occurres, timer starts before activating protection
12.
.......................................................................................................................
RPM
1.
RPM Mul. Factor
Setting
:
1~200
Default
:
60
Description
:
Please use value calculated in next parameter setting
2.
RPM Div. Factor
Setting
:
1~200
Default
:
40
Description
:
The R.P.M. Mul. and Div. are the ratio of engine revolution versus total number