![Monicon GTR-680 User Manual Download Page 15](http://html1.mh-extra.com/html/monicon/gtr-680/gtr-680_user-manual_1827047015.webp)
[15]
Description
:
Setup the action when input 4 activates
25.
In4 Switch Type
Setting
:
NC/NO
Default
:
Normal Open
Description
:
Setup Input 4 to normally close or normally open
26.
Input4 Delay
Setting
:
0.2~5.0(Seconds)
Default
:
0.4
Description
:
When input 4 activates, timer starts before activating protection
6.
.........................................................................................................................
Auxiliary Output
1.
Output 0 function
Setting
:
1~45
1.All errors
2. Trip
3.Preheat
4.Idle
5.Reset
6.Main breaker On
7.Main breaker hold
8. Genset power normal
9.Engine running
10.Over crank
11.Over speed
12.Over frequency
13.Low frequency
14.Low oil
pressure(switch)
15. High water
temperature(switch)
16.High AC voltage
17.Low AC voltage
18.Overload
19.Short circuit
20.Low battery voltage
21.High battery voltage
22.Input 0 activate
23.Input1activate
24.Input 2 activate
25.
Input 3 activate
26.Sensor fault
27.High water temp.
28.Low oil pressure
29.Low fuel level
30.High fuel level
31.
System not in AUTO
32.System in AUTO
33.Manual Start
34.AUTO Start
35.Standby mode
36.Pre-heat
37.Pre-fuel
38.Cranking
39.Crank cycle
40.System normal
41.System Alarm
42.System Trip
43.Engine shutdown
44.Engine Cooling
45. Reverse power
Default
:
36.
Description
:
Setup the function for output 0
2.
Output 1 function
Setting
:
1~45
Default
:
1.
Description
:
Setup the function for output 1
3.
Output 2 function
Setting
:
1~45
Default
:
5.
Description
:
Setup the function for output 2
4.
Output 3 function
Summary of Contents for GTR-680