![Monicon GTR-680 User Manual Download Page 13](http://html1.mh-extra.com/html/monicon/gtr-680/gtr-680_user-manual_1827047013.webp)
[13]
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates input1 function
8.
Input1 Name
:
1.Emergency Start 2.User Define 3.Low battery Voltage 4. System fault
5.High fuel level 6. System trip 7.Insulation Fail 8.Cooling failure 9.Malfunction warning
10.Charge fail 11.Over load 12.Low water temperature 13.Preheat
Default
:
4.
Description
:
Define function for input 1
9.
In1 Protection
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop
Default
:
Stop
Description
:
Setup the action when input1 activates
10.
In1 Switch Type
Setting
:
NC/NO
Default
:
Normal Open
Description
:
Define input1 type to normally close or normally open
11.
In1 delay
Setting
:
0.2~5.0(Seconds)
Default
:
2.0
Description
:
When input1 activates, timer starts before activating protection
12.
Input 2 Detect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates input2 function
13.
Input 2 Name
Setting
:
1.Low coolant level 2.User Define 3.Low battery Voltage 4. System fault 5.High
fuel level 6. System trip 7.Insulation Fail 8.Cooling Fan failure 9.Malfunction warning
10.Charge fail 11.Over load 12.Low water temperature 13.Preheat
Default
:
8.
Description
:
Define function for input 2
14.
In2 Protection
Setting
:
1.Warning 2.Alarm 3.Trip 4.Stop
Default
:
2
Description
:
Setup the action when In2 activates
15.
In2 switch type
Setting
:
NC/NO
Default
:
Normal Open
Description
:
Setup input2 to normally close or normally open
Summary of Contents for GTR-680