![Monicon GTR-680 User Manual Download Page 18](http://html1.mh-extra.com/html/monicon/gtr-680/gtr-680_user-manual_1827047018.webp)
[18]
Default
:
12
Description
:
Setup DC voltage in 12V or 24V
2.
Batt. Fault Alarm
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates battery error protections
3.
L batt Set Point
Setting
:
8.4~12/16.8~24(V)
Default
:
10.8/20
Description
:
When battery voltage is below setting, controller displays low DC volt
warning.
4.
H batt Set Point
Setting
:
12~16.8/24~33.6(V)
Default
:
14.4/28.4
Description
:
When battery voltage is above setting, controller displays high DC volt
warning.
5.
Weak Batt. Detect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates weak battery protection
6.
W. Batt. Set Point
Setting
:
4.8~8.4/9.6~16.8(V)
Default
:
8.4/9.6
Description
:
When battery voltage is below setting, controller displays battery warning.
7.
Charge failed
Setting
:
9.6~14.4/19.2~28.8(V)
Default
:
12.6/22.6V
Description
:
When voltage is out of range, controller displays charge fail.
10.
.......................................................................................................................
AC Voltage
1.
System AC Volt
Setting
:
110/120/190/208/220/380V/440/480/660/3300/4160/6600/7620/11400
Default
:
380V
Description
:
Setup Genset AC voltage
2.
Hi ACV Protect
Setting
:
Disable/ Enable
Default
:
Enable
Description
:
Activates high voltage protection.