10
54D0700
BDV Series Gas Fireplace
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
The appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring, the
appliance shall be installed on a metal, wood or noncombustible material
panel extending full width and depth of the appliance.
W
ARNING
cLEARANcES
cLEARANcES tO cOMBuStIBLES
MANtEL cLEARANcES
NOtE:
The combustible area above the facing must not protrude more than 3/4" from the
facing. If it does, it is considered a mantel and must meet the mantel requirements listed in
this manual.
12"
Maximum
Depth
11" Minimum
71" Minimum
Minimum 4"
From Both
Side Walls
FP2092
mantel clearance
Combustible Mantel
Ceiling
FP2092
Figure 5 - Clearances
4"
3"
2.5"
4.5"
45°
3.5"
3.5"
1"
1.5"
1.5"
FP2093
mantel leg clearance
11/08
Wall
Combustible
Material Area
FP2093
Figure 5a - Mantel Clearances