background image

34                                                                                                                                                                                 

44D0060

44D0060                                                                                                                                                                                                    

35

OBSERVED PROBLEM

ODS/pilot  lights,  but  flame 
goes  out  when  control  knob  is 
released.

Burner does not light after ODS/
pilot is lit.

Burner  backfires  during  com-
bustion.

Slight  smoke  or  odor  during 
initial operation.

Logs appear to smoke after ini-
tial operation.

Heater  produces  a  whistling 
noise when burner is lit.

No gas to pilot. 

POSSIBLE CAUSE

1.  Control knob not fully pressed in.
2.  Control knob not pressed in long enough.

3.  Manual shutoff valve not fully open.
4.  Thermocouple  connection  loose  at  control 

valve.

5.  Pilot flame not touching thermocouple, which 

allows  thermocouple  to  cool,  causing  pilot 
flame to go out. This problem could be caused 
by  either  low  gas  pressure,  or  a  dirty  or 
partially clogged ODS/pilot.

6.  Thermocouple damaged.
7.  Control valve damaged.

1.  Burner orifice is clogged.
2.  Burner orifice diameter is too small.
3.  Inlet gas pressure is too low.

1.  Manifold pressure is too low.
2.  Burner orifice is clogged.

1.  Burner orifice is clogged or damaged.
2.  Burner is damaged.
3.  Gas regulator defective.

1.   Vapors from paint or curing process of logs.

1.  Turning control knob to HIGH position when 

burner is cold.

2.  Air in gas line.

3.   Dirty or partially clogged burner orifices.

1.  LP-regulator shut down due to inlet pressure 

too high.

REMEDY

1.  Press in control knob fully.
2.  After  ODS/pilot  lights,  keep  control 

knob pressed in for 30 seconds.

3.  Fully open manual shutoff valve.
4.  Hand tighten thermocouple connection 

until snug, then tighten 1/4 turn more.

5.  Contact local gas company.

6.  Replace thermocouple.
7.  Replace control valve.

1.   Clean orifice.
2.  Replace burner orifice.
3.  Contact qualified service person.

1.  Contact local gas company.
2.   Clean burner or replace burner orifice.

1.   Clean burner or replace burner orifice.
2.  Replace burner.
3.  Replace gas regulator.

1.  Problem  will  stop  after  a  few  hours 

of  operation.  Run  the  heater  with  the 
damper open if you have one, or open a 
window for the first few hours.

2.  Log heater is intended to be smokeless. 

Turn  OFF  heater  and  call  qualified 
service person.

1.  Turn control knob to LOW position and 

let warm up for a minute.

2.  Operate burner until air is removed from 

line.  Have  gas  line  checked  by  local 
gas company.

3.   Clean burner or replace burner orifice.

1.  Verify LP tank regulator is installed and 

set at 11" to 13" w.c.

2.  Replace regulator on heater.

TROUBLESHOOTING

If  the  gas  quality  is  bad,  your  pilot  may  not  stay  lit,  the  burners  may  produce  soot 
and  the  heater  may  backfire  when  lit.  If  the  gas  quality  or  pressure  is  low,  contact 
your local gas supplier immediately. 

W

ARNING

Summary of Contents for DEB20

Page 1: ...o not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electric...

Page 2: ...Control 21 Milli Volt Thermostat Control 21 Hi Lo Control 21 Electrical Wiring Milli volt 22 Connecting Remote Receiver 23 Installing Thermostat Sensor 23 Operation of Thermostat Sensor 25 Log Placem...

Page 3: ...reference IMPORTANT Read these instructions carefully before installing or trying to operate this vent free gas heater 1 Due to high temperatures the appliance should be located out of traffic and aw...

Page 4: ...isappear with continued use 20 Input ratings are shown in BTU per hour and are for elevations up to 2 000 feet For elevations above 2 000 feet input ratings should be reduced 4 percent for each 1 000...

Page 5: ...Hand held Remote with receiver GETTING STARTED Carefully inspect the contents for shipping damage If any parts are missing or damaged immediately inform the dealer from whom you purchased the applian...

Page 6: ...20PT THERMOSTAT 28 000 20 000 DEB24PT THERMOSTAT 38 000 30 000 DEB30PT THERMOSTAT 38 000 30 000 NATURAL GAS NOTE An external regulator is required to reduce supply pressure to a maximum of 10 1 2 W C...

Page 7: ...o desired flame height Milli Volt and T Stat control has four 4 positions OFF All gas to the gas logs is shut off at the valve IGN Valve position to light maintain a standing pilot ON Valve position t...

Page 8: ...ces installed in that space An unconfined space is defined as a space whose volume is not less than 50 cubic feet per 1 000 BTU per hour 4 8 m3 per kw of the aggregate input rating of all appliances i...

Page 9: ...ion would be based only on the room with the heater BTU Hr 151 2 x 12 x 8 50 GENERAL INSTALLATION INFORMATION Figure 1 Example of a Large Room with 1 2 Wall Divider Counter Fireplace x 1000 x 1000 528...

Page 10: ...ure for Gas Fired Decorative Type Unvented Room Heaters per IAS Requirement No 2 97 ANSI Z21 91 2001 typically referred to as a Universal Firebox as long as firebox hearth dimensions meet the minimum...

Page 11: ...or bottom surface of the unit Refer to Table The log set should be placed against or as near as possible to the rear wall of the fireplace firebox Depth of fireplace firebox Refer toTable Figure 3 Ref...

Page 12: ...n in Figures 4 through 12 and defined in the fireplace manufacturer s instructions are minimum clearances to maintain when installing this heater Left and right clearances are determined when facing t...

Page 13: ...ese minimum clearances you must operate the heater with chimney flue damper open Refer to Installing Vented Applications found on page 18 HEAT RESISTANT REQUIREMENTS FOR SAFE INSTALLATION MATERIAL MEA...

Page 14: ...ed Observe profile side elevations shown in Figure 7 page 15 elevations shown in Figure 9 page 16 8 to less than 12 Install hood and observe profiles shown Install hood and observe profiles shown in F...

Page 15: ...the wall a maximum of 21 2 at a minimum of 14 above the opening and a maximum of 6 at a minimum of 201 2 above the opening Example A mantel may project from the wall a maximum of 21 2 at a minimum of...

Page 16: ...um of 10 at a minimum of 28 above the CLEARANCES AND HEIGHT REQUIRMENTS Figure 10 is an example of an unsafe mantel installation This mantel projects 4 at 8 above the opening exceeding the maximum acc...

Page 17: ...he top surface of carpeting tile etc See Figure 11 OR The gas log heater may be installed nearer to the floor if a minimum of 14 of noncombustible material such as slate or marble is installed between...

Page 18: ...leaning performed annually after installation Seal any fresh air vents or ash clean out doors located on floor or wall of fireplace If not drafting may cause pilot outage or sooting Use a heat resista...

Page 19: ...logs function as a system If the fireplace is spilling into the room check with a match or a smoke stick reposition the damper clamp until a positive draft is obtained by opening the damper If negati...

Page 20: ...at the Pressure Tapping Point May Be Installed Use new black iron or steel pipe Internally tinned copper or copper tubing can be used per National Fuel Code section 2 6 3 providing gas meets hydrogen...

Page 21: ...place tubing to pressure gauge over test point Use test point OUT closest to control knob After taking pressure reading be sure and turn captured screw clockwise firmly to re seal Do not over torque...

Page 22: ...t one wire to TP TH and one wire to TH or connect the wall switch thermostat to the two male 0 25 terminals on the left side of the unit The color of the wires does not matter Figure 19 Wiring Diagram...

Page 23: ...unit See Figure 20 7 Attach remote receiver with velcro pads Control switch must face forward NOTE Heat reduces battery life You can protect the receiver and extend battery life by mounting the recei...

Page 24: ...sting wiring harness with two 2 0 250 male spade terminals for remote or t stat option See Figures 23 and 24 7 Install knob to shaft of t stat sensor See Figure 23 8 Place thermo bulb in front of the...

Page 25: ...NTACTS READING TERMINALS SHOULD BE A COMPLETE 2 3 CLOSED MINIMUM SYSTEM 175 B THERMOPILE 1 2 OPEN MINIMUM OUTPUT 500 CHECKING SYSTEM OPERATION The milli volt system and individual com ponents may be c...

Page 26: ...r five ceramic fiber logs Do not handle these logs with your bare hands Always wear gloves to prevent skin irritation from ceramic fibers After handling the logs wash your hands gently with soap and w...

Page 27: ...ilot flame If the pilot flame does not touch the thermocouple then the main burner cannot function reliably See Figures 29 and 31 for incorrect shape of pilot flame MILLI VOLT CONTROL AND THERMOSTAT C...

Page 28: ...oper burning will result During manufacturing fabricating and shipping various components of this appliance are treated with certain oils films or bonding agents These chemicals are not harmful but ma...

Page 29: ...or s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the kno...

Page 30: ...ping 7 With the control knob pushed in push and release the piezo ignitor button to light the ODS pilot The pilot is located on the left side of the heater behind the middle log and on the back of the...

Page 31: ...in and release the piezo ignitor button to light the pilot 8 Continue pushing the control knob in for a further 10 seconds to prevent the flame detector from shutting off the gas while the probe is wa...

Page 32: ...t is located on the left side of the heater behind the middle log and in front of the rear log If piezo ignitor does not light the pilot refer to Match Lighting Instructions page 33 8 Hold the gas con...

Page 33: ...take holes clean will result in sooting and poor combustion Inspect and clean all burner ports Inspect ODS pilot for operation and accumulation of lint at air intake holes Verify flame pattern and log...

Page 34: ...2 Replace ignitor 3 Reconnect ignitor cable 4 Free ignitor cable if pinched by any metal or tubing 5 Replace ignitor cable 6 Replace piezo ignitor 1 Ventilate room Stop using odor causing products whi...

Page 35: ...clogged burner orifices 1 LP regulator shut down due to inlet pressure too high REMEDY 1 Press in control knob fully 2 After ODS pilot lights keep control knob pressed in for 30 seconds 3 Fully open...

Page 36: ...MENT PARTS Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury WARNI...

Page 37: ...urner Injector 1 44D0200 44D0202 44D0204 44D0206 9 ODS Pilot Assembly 1 26D2529 26D2530 26D2529 26D2530 10 Control Knob 1 18D0603 18D0603 18D0603 18D0603 11 Rear burner Injector 1 44D0201 44D0203 44D0...

Page 38: ...4D1010K 44D1000K 44D1005K 3 Front Log 1 44D1012K 44D1002K 44D1007K 4 Left Log 1 N A 44D1003K 44D1008K 5 Top Log 1 44D1013K 44D1004K 44D1009K REPLACEMENT PARTS LIST Failure to position the parts in acc...

Page 39: ...44D0060 39 NOTES...

Page 40: ...in accordance with the installation instructions The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with t...

Reviews: