background image

CDVSC7 & CDV7 Series Gas Fireplace

66

69D3011

noTe ReGaRDInG VenTeD pRoDuCTS

This product must be installed by a licensed plumber or gas fitter 
when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 
detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State 
of  Massachusetts  requires  the  damper  to  be  permanently 
removed or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 
bedroom or bathroom in the State of Massachusetts.
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve. 

noTe ReGaRDInG VenT FRee pRoDuCTS

This product must be installed by a licensed plumber or gas fitter 
when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 
bedroom or bathroom regardless of size or type in the State 
of Massachusetts.
Flex  line  installation  must  not  exceed  36  inches  and  must 
have a T shutoff valve.

CaRBon MonoxIDe DeTeCToR RequIReMenTS

() Revise  10.8.3  by  adding  the  following  additional 
requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  every  dwelling,  building  or  structure 
used  in  whole  or  in  part  for  residential  purposes,  including 
those owned or operated by the Commonwealth and where the 
side wall exhaust vent termination is less than seven (7) feet 
above finished grade in the area of the venting, including but 
not limited to decks and porches, the following requirements 
shall be satisfied:
1. 

Installation of carbon monoxide detectors. 

At the time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 
equipment,  the  installing  plumber  or  gas  fitter  shall  observe 
that a hard wired carbon monoxide detector with an alarm and 
battery back-up is installed on the floor level where the gas 
equipment is to be installed. In addition, the installing plumber 
or gas fitter shall observe that a battery operated or hard wired 
carbon monoxide detector with an alarm is installed on each 
additional  level  of  the  dwelling,  building  or  structure  served 
by  the  side  wall  horizontal  vented  gas  fueled  equipment.  It 
shall be the responsibility of the property owner to secure the 
services of qualified licensed professionals for the installation 
of hard wired carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 
hard wired carbon monoxide detector with alarm and battery 
back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 
owner shall have a period of thirty (30) days to comply with the 
above requirements; provided, however, that during said thirty 
(30) day period, a battery operated carbon monoxide detector 
with an alarm shall be installed.

Massachusetts Residents only — please read and follow these special requirements

approved  Carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 
provisions shall comply with NFPA 70 and be ANSI/UL 034 
listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 
minimum height of eight (8) feet above grade directly in line 
with  the  exhaust  vent  terminal  for  the  horizontally  vented 
gas  fueled  heating  appliance  or  equipment.  The  sign  shall 
read,  in  print  size  no  less  than  one-half  (1/)  inch  in  size, 
“GAS  VENT  DIRECTLY  BELOW.  KEEP  CLEAR  OF  ALL 
OBSTRUCTIONS.”
4. 

Inspection.

  The  state  or  local  gas  inspector  of  the  side 

wall  horizontally  vented  gas  fueled  equipment  shall  not 
approve the installation unless, upon inspection, the inspector 
observes  carbon  monoxide  detectors  and  signage  installed 
in  accordance  with  the  provisions  of  48  CMR  5.08()(a)1 
through 4.
(b) 

exemptions:

 The following equipment is exempt from 48 

CMR 5.08()(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 
Required To Be Vented" in the most current edition of NFPA 54 
as adopted by the Board; and
. Product Approved side wall horizontally vented gas fueled 
equipment installed in a room or structure separate from the 
dwelling,  building  or  structure  used  in  whole  or  in  part  for 
residential purposes.
(c)  

Manufacturer requirements — Gas equipment Venting 

System  provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 
a venting system design or venting system components with 
the equipment, the instructions provided by the manufacturer 
for installation of the equipment and the venting system shall 
include:
1. Detailed instructions for the installation of the venting system 
design or the venting system components; and
. A complete parts list for the venting system design or venting 
system.
(d) 

Manufacturer requirements — Gas equipment Venting 

System not provided. 

When the manufacturer of a Product 

Approved side wall horizontally vented gas fueled equipment 
does  not  provide  the  parts  for  venting  the  flue  gases,  but 
identifies “special venting systems,” the following requirements 
shall be satisfied by the manufacturer:
1. The referenced "special venting system" instructions shall 
be  included  with  the  appliance  or  equipment  installation 
instructions; and
. The “special venting systems” shall be Product Approved 
by the Board, and the instructions for that system shall include 
a parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 
all venting instructions, all parts lists for venting instructions, 
and/or all venting design

Summary of Contents for CDV7

Page 1: ...Refer to this manual For assistance or additional information consult a qualified installer service agency or the gas supplier Thisappliancemaybeinstalledinanaftermarket permanently located manufactu...

Page 2: ...rating Instructions Electronic Ignition 35 What To Do If You Smell Gas 35 Lighting Electronic Ignition 35 To Turn Off Gas 35 Check Gas Pressure Signature Command System36 Electrical Installation SCS 3...

Page 3: ...ualified service person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door properly seated and sealed combustion lea...

Page 4: ...Code Approval Direct Vent type appliances draw all combustion air from outside of the dwelling through the vent pipe These appliances have been tested by CSA and found to comply with the established...

Page 5: ...s This appliance is approved to be vented with Simpson Duravent and MHSC Twist Lock Direct Vent Compo nents FP2284a CDV7 controls Off Pilot On Knob Remote Control Switch Receiver Figure 1 CDV7 Series...

Page 6: ...24 000 17 000 2 35 mm CDVR42PSC7 LP 24 000 18 000 1 45 mm CDVR47NV7 Nat 24 000 17 000 2 35 mm CDVR47PV7 LP 24 000 18 000 1 45 mm CDVR47NE7 Nat 24 000 17 000 2 35 mm CDVR47PE7 LP 24 000 18 000 1 45 mm...

Page 7: ...m 20C 518 mm 20C 518 mm F 11Z x 292 mm 14C zn 360 mm 15C v 400 mm 15C v 400 mm 15C v 400 mm G 21Z x 546 mm 21C 546 mm 21M 556 mm 25M 657 mm 31M 810 mm H 21ZB zn 557 mm 21ZB zn 557 mm 25Z v 641 mm 25Z...

Page 8: ...m 39Z zn 992 mm E 15C zn 386 mm 20C 518 mm 20C 518 mm 20C 518 mm F 14C zn 360 mm 15C v 400 mm 15C v 400 mm 15C v 400 mm G 21C 546 mm 21M 556 mm 25M 657 mm 31M 810 mm H 10ZZ zn 272 mm 10ZB zn 278 mm 12...

Page 9: ...R33SC7 does not have standoffs The firebox may be installed directly on a combustible floor or raised on a platform of an appropriate height When the firebox is installed directly on carpeting tile or...

Page 10: ...ries due to heat from appliance Never obstruct the front opening of the fireplace Do not install in the vicinity where gasoline or other flammable liquids may be stored Vent pipe routing See Venting s...

Page 11: ...ent FP2285b CDV33 42 47 Side View mantel clearances NOTE The combustible area above the facing must not protrude more than 3 4 from the facing If it does it is considered a mantel and must meet the ma...

Page 12: ...ng Nailing Flange Screws Screw Nailing Flange Nailing Flanges Drywall Support Tabs Do Not Use for Framing or Header Screw Screw FP2287 Finishing Material NOTE Any wiring i e remote control wall switch...

Page 13: ...re rigid direct vent components can be used All restrictions clearances and allowanc es that pertain to the rigid piping apply to the flexible venting Flex kits may not be modified Flex kits may be ad...

Page 14: ...or assembly above the meter regulator assembly 5 m above the meter regulator assy I Clearance to service regulator vent outlet 3 91 cm 3 91 cm J Clearance to nonmechanical air supply inlet 6 15 cm for...

Page 15: ...e a minimum of 3 914 mm below the termination cap 3 All gravity air intakes within 3 914 mm of a termination cap must be a minimum of 1 305 mm below the termination cap General Information Assembling...

Page 16: ...th twist lock pipe Figure 11 To make it easier to assembly the joints we suggest put ting a lubricant Vaseline or similar on the male end of the twist lock pipe prior to assembly TWL100 Twist Lock Pip...

Page 17: ...fire place in accordance with same EXAMPLE A If the vertical dimension from the floor of the unit is 11 3 4 m the horizontal run to the face of the outer wall must not exceed 14 4 3 m EXAMPLE B If th...

Page 18: ...m require a minimum of 1 clearance to combustibles on all sides of the pipe WARNING Top Vent Horizontal sections of this vent system require a minimum of 3 clearances to combustibles at the top of the...

Page 19: ...Hole opening should be 7Z x 191 mm diameter Step 2 Secure firestop to the inside frame center in the 9B x 9B vent opening Step 3 Measure the horizontal length requirement for the venting including a 2...

Page 20: ...break off the center rib of the supplied flue restrictor The installed part should appear similar to that show n in Figure 20 Since it is very im portant that the venting system maintain its balance b...

Page 21: ...st not be great er than 17 5 2m The maximum number of 45 elbows permitted per in stallation is six 6 These elbows can be installed in either the vertical or horizontal run For each 45 elbow installed...

Page 22: ...244 mm Fireplace Hearth Framing Detail Opening for Noncombustible Wall 7Z x 190 mm Fireplace Hearth FP2293 Figure 26 Locate Vent Opening on Wall 9B 244 mm Step 2 Secure firestop to the inside frame ce...

Page 23: ...Step 1 and 2 on Page 22 Step 3 Install the four 4 spacer springs on the 4 flex vent pipe When installing the spacer springs around the 4 pipe stretch the spring to approximately 15 381 mm wrap the spr...

Page 24: ...tallation 1 26 00 djt Firestop 7 Pipe 7TDVSNORK Snorkel 4 102 mm Clearance Min Window Well Gravel Drain BG402a Figure 31 Below Grade Installation Aminimum of 24 610 mm verti cal pipe must be installed...

Page 25: ...d mark position 3 Cut opening equal to 9C v x 9C v 248 x 248 mm 4 Proceed to plumb for addi tional openings through the roof In all cases the opening must provide a minimum of 1 inch clearance to the...

Page 26: ...re is a room above ceiling level fire stop spacer must be installed on both the bottom ad the top side of the ceiling joists If an attic is above ceiling level an Attic Insulation Shield must be insta...

Page 27: ...incoming gas pressure to between 11 and 13 inches of water If you do not reduce incoming gas pressure burner system regulator damage could occur Install external regulator with the vent pointing down...

Page 28: ...p collects moisture and contaminants and keeps them from going into the burner system gas controls If sediment trap drip leg is not installed or is installed wrong burner system may not run properly N...

Page 29: ...e reading be sure and turn captured screw clockwise firmly to reseal Do not over torque Check test points for gas leaks FP1979 Millivolt gas valve FP1979 Figure 42 Gas Pressure Check at Gas Valve Pres...

Page 30: ...de Figure 43 Wiring Diagram for Wall Switch Electrical installation Remote Wall Switch Position the wall switch Do not extend beyond the 15 feet of wire Optional DC Remote Systems See section entitled...

Page 31: ...nse Ignition Module Synetek Spark FP2295 electronic wiring diagram HI LO EV1 EV2 WARNING Do not connect 110 120 VAC to the Remote Wall Switch The appliance will malfunction Optional Fan Blower Systems...

Page 32: ...ualified service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technici...

Page 33: ...epeat steps 1 and 2 Lighting pilot Figure 47 Pilot Position Check for gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field ma...

Page 34: ...e This switch allows you to turn on and to turn off the main burner without using the gas valve knob Make sure the button is in the ON position to light the main burner Figure 48 Lighting the burner D...

Page 35: ...t the appliance and to replace any part of the control system and any gas control that has been under water Lighting electronic ignition for your safety read before lighting to turn off gas 1 Open low...

Page 36: ...rical Wiring General 1 This fireplace is equipped with the Signature Control valve which operates on 6 volts The 6 volt DC adapter plugs into the fireplace junction box A C power supply Four 4 AA batt...

Page 37: ...o not extend beyond the 15 ft wire cable provided If a longer distance is required the 15 ft may be extended up to 30 ft maximum by using two 2 SCSWEK cables plugged together Route the wire from junct...

Page 38: ...P Plug in Connector Control Board to Command Center OFF LO LED ON HI Master Switch Command Center Optional Wall Switch Plug in Connector Stepper Motor to Control Board DC Power Green Ground Plug in Co...

Page 39: ...control will not work correctly WARNING Electrical connections should only be performed by a qualified licensed electrician Main power supply must be turned off before connecting the fan to the main e...

Page 40: ...NUAL BLOWER 1 This must be done before framing the fireplace When installing the FK 12 blower a wall switch control must be installed to control the blower 2 The fireplace power supply is wired throug...

Page 41: ...llow the gas supplier s instruc tions If you cannot reach your gas supplier call the fire department C Use only your finger to push in the master switch Never use tools If the switch will not function...

Page 42: ...ll gas go to next step 4 Press the master switch to the ON position Within eight 8 seconds it will beep once This indi cates the system is ready 5 Press ON button Sparker will spark and pilot flame wi...

Page 43: ...X X Child Proof Lock out X X X X X LCD Backlight X X X X X Security Codes 16 X X X X X Countdown 6 hr Timer X X X Standard Thermostatic Control Mode X X X Smart Mode Thermostat Auto Flame Blower Modul...

Page 44: ...eeps for RF receiver OFF will be given as confirmation Refer to Figure 60 for location 2 After the RF receiver is on holding the OFF button on the Command Center while turning on the master switch wil...

Page 45: ...en Off 3 Hold the OFF button anytime for three seconds or by turning off the wall switch These two commands of OFF are Memory Off the system will remember all last settings before turning off The next...

Page 46: ...tire surface of the burner with one thin layer of rock wool 3 Place the logs on the burner Refer to the Log Placement Section Light the unit and after 15 minutes check burner flame and glow Adjust emb...

Page 47: ...Rest the narrow end of the top left log behind the center vertical grate bar lava rock and ember placement Sprinkle lava rock on the floor of the inner combustion chamber Evenly distribute the rock Do...

Page 48: ...uum Burner Flame The flames from the burner should be visually checked as soon as the heater is installed and periodically during normal operation In normal operation at full rate and after operating...

Page 49: ...e materials may be used Handle glass door with care to avoid striking or scratching it on hard objects To clean glass door follow Glass Removal procedure outlined in the Final Installation section Fil...

Page 50: ...e thermocouple connection at the gas valve is fully inserted and tight Disconnect the thermocouple from the valve place one millivolt lead wire on the tip of the thermocouple and the other meter lead...

Page 51: ...ame for maximum flame impingement on thermocouple A Check for flue product leak Replace defective pipe sec tion B Check horizontal venting piping is running upward 1 4 per foot Do not run the pipe lev...

Page 52: ...ifies blocked B Check electrical connections between module and pilot operator on gas control C Check for 24VAC across PV MVPV terminals If voltage is correct replace gas control If voltage is not cor...

Page 53: ...ough Battery polarity wrong LED on the Command Center does not show solid green The 5 pin connector on the AC board broken or bent AC plug is plugged to AC mains Battery voltage low Using battery Chec...

Page 54: ...CDVSC7 CDV7 Series Gas Fireplace 54 69D3011 replacement parts firebox components 1 4 2 3 6 6 5 CDVR Series 5 CDVT Series 6 6 12 9 7 10 11 13...

Page 55: ...Left 2 26D7068 26D7068 69D0042 69D0042 69D0042 69D0042 69D0042 69D0042 Cottage Clay 6b Firebrick Right Left 2 20300900 Cottage Clay CDVR33SC7 ONLY 6a Firebrick Right Left 2 54D0285 54D0285 69D0046 69...

Page 56: ...CDVSC7 CDV7 Series Gas Fireplace 56 69D3011 replacement parts Standing Pilot Millivolt control 1 2C 2I 2T 2 4 5 6 3 8 9 7 10 11 12 13 14 693011 CDV millivolt parts...

Page 57: ...1D0048 41D0048 41D0048 41D0048 41D0048 41D0048 41D0048 6 Piezo Igniter 1 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 14D0503 7 Injector 1 58D0371 69D0226 59D0062 69D0079 20H3155 33D4046 20...

Page 58: ...8 41D0048 6 Injector 1 58D0371 69D0226 59D0062 69D0079 20H3155 33D4046 20H3155 33D4046 7 Burner Assembly 1 54D0200 54D0200 54D0001 54D0001 54D0329 54D0329 54D0329 54D0329 8 Venturi 1 69D1119 69D1026 6...

Page 59: ...CDVSC7 CDV7 Series Gas Fireplace 69D3011 59 REPLACEMENT PARTS 1 2 3 4 20 5 6 7 8 9 13 14 15 16 17 693011 cdvrt7 SC parts 12 SIGNATURE COMMAND SYSTEM...

Page 60: ...e Valve Control not shown 1 80D0010 80D0010 80D0010 80D0010 80D0010 80D0010 80D0010 80D0010 11 Wire Command Ctr Control Box 2 1 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 80D0008 not show...

Page 61: ...s REPLACEMENT PARTS Item Description CDVR33SC7 CDVR33 V E 7 CDV R T 36 V E SC 7 CDV R T 42 V E SC 7 CDV R T 47 V E SC 7 1 Rear Log 20301202 54D0121 54D0181 54D0339 54D0339 2 Right Log 54D0147 54D0147...

Page 62: ...nt Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 Twist Lock Elbows 45 Elbow for Vertical Horizontal Offset 7TDV45 45 E...

Page 63: ...rmination Pipe 4 pack 7TDVPA 4 12 18 Adjustable Vent Length 7TDVP1218 35 64 Adjustable Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36...

Page 64: ...CDVSC7 CDV7 Series Gas Fireplace 64 69D3011...

Page 65: ...CDVSC7 CDV7 Series Gas Fireplace 69D3011 65...

Page 66: ...e above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please read and fo...

Page 67: ...Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner assembly...

Page 68: ...NSC7 49 7 CDVR36PSC7 56 1 CDVR42NV7 66 8 CDVR42PV7 68 7 CDVR42NE7 71 0 CDVR42PE7 72 3 CDVR42NSC7 71 0 CDVR42PSC7 72 3 CDVR47NV7 65 6 CDVR47PV7 67 1 CDVR47NE7 69 6 CDVR47PE7 70 6 CDVR47NSC7 69 6 CDVR47...

Reviews: