
Monaco 134 06 05
Technical manual "1303"
7
must comply with Current Building Regulations. If in
doubt, consult your Dealer or local Building Inspector.
• The appliance must not support the weight of the
flue.
• It must be distant from any combustible material
(walls, cross members)
• It must permit easy sweeping.
2.7 Chimney connector
• The connection to the flue must be carried out
according to local building regulations.
• The appliance must be installed as close as possible
to the chimney.
•
Any connection pipe must be suitable for use with
solid fuel burning appliances in accordance with
Approved Document J of the building regulations.
•
The connecting pipe must not reduce in diameter at
any point to less than the diameter of the outlet of the
stove.
• The connection can be either vertical or horizontal.
For horizontal connections, avoid right angle bends.
• The join between the connection pipe and the
stovepipe, and the flue, must be leak tight.
• For the premises equipped with a mechanical
controlled ventilation, the airtightness has to prevent
the exhauster drawing out the smokes from the
exhaust gas pipe.
• The connection pipe and any draught stabiliser must
have access for cleaning.
2.8. Door closing pressure
Figure 7
The closing latch rotates around a pressure screw
positioned cam.
- Loosen pressure screw
1
,
- Turn cam to desired position.
2
,
- Tighten pressure screw
1
.
2.9 Pre-utilisation check
Check that the seals of the smoke-line are in good
condition. Check that the door closes correctly.
Check that the glass is not damaged. Check that the
smoke passages are not obstructed by packaging or
removable parts. Check that all removable parts are
correctly installed.
2.10 Maintenance of the Chimney
Very important
: In order to avoid any incident
(chimney fire, etc...), maintenance tasks must be
carried out regularly. If the appliance is regularly used,
the chimney should be swept several times per year,
together with the stovepipe connection section.
If the chimney catches fire, you must cut off
the flue draught, close the doors and windows,
hatches and keys and call the Fire Brigade
without delay.
DO NOT OPEN THE DOOR OF THE APPLIANCE
(OR AIR INLET) UNDER ANY CIRCUMSTANCES
Chimney condition should be checked at least once
per year by a professional engineer.
1
Pressure screw
2
Cam
Figure 7 - Adjusting of the door closing pressure