Monaco - 134 06 05
6
Technical manual "1303"
2.3 Mounting the flue collar
The stove is supplied with a connection flue spigot with
an inner diameter of 125 mm and an outer diameter
of 139 mm.
2.4 Smoke exit on the top
Figure 4
- The stove is set from the factory with a top outlet.
- Do not remove the cast iron top.
- Remove the cardboard chock from the top (A).
2.5. Smoke exit at rear
Figure 5
-
Do not remove the cast iron top.
- Remove the cardboard chock from the top.
- Remove the infernal baffle
1
.
- Removed the flue spigot
7
.
- Place the seal rope
3
within the groove, fix the
blanking plate
4
and the clamp
5
and ensure a good
tightness.
- Place the seal rope
6
within the groove, screw into
position the spigot
7
and ensure a good tightness
- Refit the flue baffle
1
.
2.6 Flue
Existing flue :
The chimney must comply with Current
Building Regulations. If in doubt, consult your Dealer
or local Building Inspector.
• The flue must be in good condition and must provide
sufficient draught (refer to technical details p. 3).
• The flue must be suitable for the installation of fuel
burning appliances, otherwise it must necessary to
install a tubing.
• The flue must be clean. It should be swept to remove
soot and dislodge tar deposits.
• The flue must be well insulated. If the flue inner wall
surfaces are cold, a good thermal draw is impossible
causing condensation problems (tar formation etc) to
occur.
• The flue must be watertight.
• The flue must not be shared with other appliances.
• The chimney must have a constant cross section.
• When the cross-section of the chimney is too large, it
has difficulties in obtaining a good draught.
• The chimney must be at least 4.5 m (15 ft) high and
be at 40 cm above the ridge of the roof and 8 meters
away from any construction.
• In case of a flat roof or when the roof gradient is
lower than 15°, the stack must be 1,2 m (4 feet) high
at least.
• The capping must not restrain the draught.
• If the chimney has any down draught tendency, due
to its position in relation to nearby obstacles, then
an anti-down draught cowl must be installed on the
chimney or the chimney height must be increased.
• If the chimney draught is excessive or irregular,
a draught stabilizer (barometric damper) must be
installed to the connector pipe it must be visible and
accessible.
Chimney to be built / New flue :
The chimney
1 - Chimney
2 - Funnel-shape fireproof material.
3 - Non-combustible plate
4 - Access to cleaning
5 - Insulation
6 - Plate not removable and ventilated air
Figure 6 - Chimney connector