HEAT EXHAUST CONNECTION NOTES

1. VENT LINE - 

The exhaust vent line required for MOJAVE systems using 

the Heat Exchanger and systems with the Heat Exchanger removed 

have different requirements. 
Use metal pipe on systems without a Heat Exchanger while PVC 

Schedule 40 pipe can be used on systems with a Heat Exchanger.
Do not make a trap in the exhaust vent piping.  Do not use 90

 

ο fittings. 

Also see Exhaust Vent Protection and Ventilation Requirements below.

2. V3, V5 & V7 PUMP EXHAUST VENT CONNECTION - 

Connection between 

the pump and exhaust vent piping is typically made via the supplied 2-inch 

Black Flex tubing.

3. EXHAUST VENT ASSEMBLY - 

The supplied assembly must be 

installed at the

 

lower end of the vent pipe to collect condensation 

produced during pump operation.  The

 

bottom of the Y connector 

should be located 18 inches from floor.  Attach the drain tube to the drip 

leg quick-connect fitting to allow drainage into floor drain/sink.

EXHAUST VENTILATION REQUIREMENTS

V3,V5 & V7 Pump Heat Exchanger Connection

Exhaust Vent Assembly 

supplied with Tank 

Accessory kit.

See Detail & Note 3.

Exhaust Vent 

See Note 1.

Typical Flex 

Tubing

See Note 2.

V3 or V5 Pump Top View

Vent Pipe

Heat 

Exchanger

17-Inch Long 

Flex Tubing

4”

Drip Leg Detail View

2” Flexible Coupler  

2” PVC Reducing Bushing 

3/4” MNPT X 1/4” FNPT PVC Bushing

1/4” MNPT X 1/4” Push Elbow

35”

18”

Exhaust Vent Protection.

If the exhaust piping is venting to the outside of the building, precautions must be taken to protect 

the equipment room from weather elements and animal intrusion.  This can be accomplished by 

using one of the three methods shown on the right.

Wall-Mounted Outside 

Vent Protection

Shroud & 

Screen

Roof-Mounted Outside Vent Protection

Shroud & 

Screen

Screen

Exhaust Vent Requirements.

The MOJAVE equipment must be used in a controlled-temperature environment.  Maintain 

equipment room temperature between 40 and 105 degrees Fahrenheit.  An exhaust fan is 

necessary if room temperature is not maintained by other methods.
Adequate forced ventilation must be provided across the unit by placing an appropriate 

exhaust fan opposite an equivalent air intake vent .  The fan should be placed higher than the 

associated intake vent.  Recommended minimum exhaust fan requirements for each MOJAVE 

unit are listed to the right.

Note:

 Only 1 pump is running when operating in idle mode.

MOJAVE 

Unit

Watts 

(Idle)

Watts 

(Max)

BTU/Hr 

(Idle)

BTU/Hr 

(Max)

V3

886

1,601

3,021

5,462

V5

886

2,245

3,021

7,660

V7

1,200

2,245

3,021

7,660

2V3 & 2V3CT

886

3,202

6,042

10,924

2V5 & 2V5CT

886

4,490

6,042

15,320

2V7

See

Note

1,200

4,490

6,042

15,320

3V5

886

6,735

9,063

22,980

4V5

886

8,980

12,084

30,640

Corporate Headquarters

1295 Walt Whitman Road

 

|

 

Melville, New York 11747- 3062

Phone: 800-247-8324

 

|

 

Fax: 888-247-8481

www.airtechniques.com

MOJAVE is a trademark of Air Techniques, Inc.

 

© 

Air Techniques, Inc. 

• 

P/N H5187, Rev. M 

 February 2018

Summary of Contents for V3

Page 1: ..._____________________ Phone __________________________________________________ Dealer __________________________________________________ Dealer Address __________________________________________________ All installations must conform to local codes All pumps comply with NFPA 99C level 3 requirements System being installed AS CHECKED q V3 q V5 q V7 q 2V3 q 2V3CT q 2V5 q 2V5CT q 2V7 q 3V5 q 4V5 ...

Page 2: ...aust to Outside Vent V3 V5 or V7 Vacuum Pump Heat Exchanger Gate Valve Check Valve Sewer Drain MT10 Separator Tank Gas Typical MOJAVE System Installation Liquids Solids System Components V3 V5 V7 2V3 2V3CT 2V5 2V5CT 2V7 3V5 4V5 V3 Pump Assembly 1 0 0 2 2 0 0 0 0 0 V5 Pump Assembly 0 1 0 0 0 2 2 0 3 4 V7 Pump Assembly 0 0 1 0 0 0 0 2 0 0 MT10 MT12 Tank Assembly 1 1 1 1 0 1 0 0 0 0 CT20 CT22 Tank As...

Page 3: ... in 28 cm 13 5 in 34 cm 3 in 8 cm V3 V5 and V7 Vacuum Pump Dimensions 17 in 43 cm 25 in 64 cm 21 in 53 cm 17 5 in 44 cm 2V3 or 2V5 System Installation Recommended Stacked Pumps with Tank on Side 33 in 84 cm 34 in 86 cm V3 V5 and V7 System Dimensions 23 in 58 cm 50 in 127 cm 2V7 2V3CT or 2V5CT System Installation Recommended Stacked Pumps with CT20 CT22 Tank on Side 34 in 86 cm 50 in 127 cm MT10 MT...

Page 4: ... Height from Riser Trap to Main Line OVERHEAD INSTALLATION Alternate system installation layout should be used only when unable to use the sub floor plumbing layout Ceiling Junction Box See Note 2 1 2 Inch Diameter Riser Minimum Slope 1 4 inch per 10 Feet Main Line Riser for connection to tank input See Note 1 MAIN LINE See Notes 2 3 4 Junction Box See Note 2 MAIN LINE See Notes 2 3 4 5 CONNECTOR ...

Page 5: ...ng water pressure between 20 and 100 psi for daily tank washout Valve location must be no more than 10 feet from the tank installation to allow connection of supplied 10 foot 3 8 inch Poly tubing to the tank washout port Provisions for backflow prevention may be required Check local code requirements E MASTER CONTROLLER ELECTRIC OUTLET Master Controller requires a dedicated standalone 120V 5 AMP o...

Page 6: ... PVC Sch 40 2 PVC Sch 40 One 3 or two 2 PVC Sch 40 One 3 or two 2 PVC Sch 40 One 3 or two 2 PVC Sch 40 One 4 or three 2 PVC Sch 40 Two 3 or four 2 PVC Sch 40 Exhaust Vent Pipe Not Using Heat Exchanger See note 1 2 Metal Pipe 2 Metal Pipe 2 Metal Pipe One 3 or two 2 Metal Pipe One 3 or two 2 Metal Pipe One 3 or two 2 Metal Pipe One 4 or three 2 Metal Pipe Two 3 or four 2 Metal Pipe Minimum Suction ...

Page 7: ...rizontal to Floor 3 PVC or Copper Clean out Plug Used with P N MIK4 Supplied by Plumber Air F l o w 2 PVC or Copper Tubing for Tank Hose Supplied by Plumber Check Valve Side View CT20 TANK INLET CONNECTION DETAIL 6 inch Riser Customer Supplied Tee Connector 3 4 FNPT 2 Flexible Coupling Connector 1 4 inch Vacuum Sample Port to Master Controller Reducing Bushing Swivel Elbow 2 Pipe for connection to...

Page 8: ...ush Elbow 35 18 Exhaust Vent Protection If the exhaust piping is venting to the outside of the building precautions must be taken to protect the equipment room from weather elements and animal intrusion This can be accomplished by using one of the three methods shown on the right Wall Mounted Outside Vent Protection Shroud Screen Roof Mounted Outside Vent Protection Shroud Screen Screen Exhaust Ve...

Reviews: