TREATMENT ROOM PLUMBING INSTALLATIONS

q

  Use only 45° elbows to make turns in main line.

q

  Make sure to use the proper pipe type for associated system.

q

  If piping is diverted to clear an obstruction, DO NOT MAKE A TRAP. 

See detail A, 

Main Line Turn Connections.

q

  DO NOT use standard 90° elbows.

SUB FLOOR INSTALLATION - 

Recommended system installation layout should be used 

whenever possible.

Notes

:

1.

10-foot Maximum Height from Main 

Line to Tank.

2.

Consult Dental Unit Manufacturer's 

Guidelines for correct reduced size 

and height of termination of vacuum 

line inside junction box.

3.

Limit branches. Orient main line 

under junction box or cabinet.

4.

When piping line is above 3/4" I.D. 

or larger, use 45° Y's & elbows only.

5.

Recommend installing separate line 

connection for scavenger when using 

Nitrous scavengers in overhead 

piping installations.

Minimum Slope: 

1/4 inch per 10 Feet

Interior Wall

1/2-Inch Diameter Riser

10-FT Maximum Height 

from Riser Trap to Main 

Line

OVERHEAD INSTALLATION -

Alternate system installation layout should be used only when 

unable to use the sub-floor plumbing layout.

Ceiling

Junction 

Box 

See Note 2.

1/2 - Inch Diameter Riser

Minimum Slope: 

1/4 inch per 10 Feet

Main Line Riser for connection to 

tank input.  See Note 1.

MAIN LINE 

See Notes 2, 3 & 4.

Junction 

Box 

See Note 2.

MAIN LINE

See Notes 2, 3 

4 & 5.

CONNECTOR DETAILS - ALL INSTALLATIONS

Ceiling

Important:

All installation pipes and fittings provided by plumber.

All installations must conform to local codes.

Interior Wall

Main 

Line Turn 

Connection 

See A.

Sub Floor 

Riser 

Connection 

See B.

Riser Trap 

See D.

Overhead Riser 

See C.

Sub Floor Riser to Main Line Detail

1/2 Inch Riser

45°Elbow

45°Y

1/2 Inch 

Diameter

To 

Tank

45°Elbow

1" Min

Main 

Line

Overhead Riser to Main Line Detail

(

Prevents liquids from draining down the 1/2” riser.)

Main Line Turn Connections

45

°

 Elbow

45

°

 Elbow

Clearing & 

Obstruction

Making 

Turns

Riser Trap Detail (45°

 

Elbows)

1/2-Inch 

Riser

To Main 

Line

1/2-Inch

To 

Dental Unit 

Junction 

Box

45°ELL

45°Y

To 

Tank

Main 

Line

1/2 Inch Riser

To Dental Unit 

Junction Box

A

B

C

D

Summary of Contents for V3

Page 1: ..._____________________ Phone __________________________________________________ Dealer __________________________________________________ Dealer Address __________________________________________________ All installations must conform to local codes All pumps comply with NFPA 99C level 3 requirements System being installed AS CHECKED q V3 q V5 q V7 q 2V3 q 2V3CT q 2V5 q 2V5CT q 2V7 q 3V5 q 4V5 ...

Page 2: ...aust to Outside Vent V3 V5 or V7 Vacuum Pump Heat Exchanger Gate Valve Check Valve Sewer Drain MT10 Separator Tank Gas Typical MOJAVE System Installation Liquids Solids System Components V3 V5 V7 2V3 2V3CT 2V5 2V5CT 2V7 3V5 4V5 V3 Pump Assembly 1 0 0 2 2 0 0 0 0 0 V5 Pump Assembly 0 1 0 0 0 2 2 0 3 4 V7 Pump Assembly 0 0 1 0 0 0 0 2 0 0 MT10 MT12 Tank Assembly 1 1 1 1 0 1 0 0 0 0 CT20 CT22 Tank As...

Page 3: ... in 28 cm 13 5 in 34 cm 3 in 8 cm V3 V5 and V7 Vacuum Pump Dimensions 17 in 43 cm 25 in 64 cm 21 in 53 cm 17 5 in 44 cm 2V3 or 2V5 System Installation Recommended Stacked Pumps with Tank on Side 33 in 84 cm 34 in 86 cm V3 V5 and V7 System Dimensions 23 in 58 cm 50 in 127 cm 2V7 2V3CT or 2V5CT System Installation Recommended Stacked Pumps with CT20 CT22 Tank on Side 34 in 86 cm 50 in 127 cm MT10 MT...

Page 4: ... Height from Riser Trap to Main Line OVERHEAD INSTALLATION Alternate system installation layout should be used only when unable to use the sub floor plumbing layout Ceiling Junction Box See Note 2 1 2 Inch Diameter Riser Minimum Slope 1 4 inch per 10 Feet Main Line Riser for connection to tank input See Note 1 MAIN LINE See Notes 2 3 4 Junction Box See Note 2 MAIN LINE See Notes 2 3 4 5 CONNECTOR ...

Page 5: ...ng water pressure between 20 and 100 psi for daily tank washout Valve location must be no more than 10 feet from the tank installation to allow connection of supplied 10 foot 3 8 inch Poly tubing to the tank washout port Provisions for backflow prevention may be required Check local code requirements E MASTER CONTROLLER ELECTRIC OUTLET Master Controller requires a dedicated standalone 120V 5 AMP o...

Page 6: ... PVC Sch 40 2 PVC Sch 40 One 3 or two 2 PVC Sch 40 One 3 or two 2 PVC Sch 40 One 3 or two 2 PVC Sch 40 One 4 or three 2 PVC Sch 40 Two 3 or four 2 PVC Sch 40 Exhaust Vent Pipe Not Using Heat Exchanger See note 1 2 Metal Pipe 2 Metal Pipe 2 Metal Pipe One 3 or two 2 Metal Pipe One 3 or two 2 Metal Pipe One 3 or two 2 Metal Pipe One 4 or three 2 Metal Pipe Two 3 or four 2 Metal Pipe Minimum Suction ...

Page 7: ...rizontal to Floor 3 PVC or Copper Clean out Plug Used with P N MIK4 Supplied by Plumber Air F l o w 2 PVC or Copper Tubing for Tank Hose Supplied by Plumber Check Valve Side View CT20 TANK INLET CONNECTION DETAIL 6 inch Riser Customer Supplied Tee Connector 3 4 FNPT 2 Flexible Coupling Connector 1 4 inch Vacuum Sample Port to Master Controller Reducing Bushing Swivel Elbow 2 Pipe for connection to...

Page 8: ...ush Elbow 35 18 Exhaust Vent Protection If the exhaust piping is venting to the outside of the building precautions must be taken to protect the equipment room from weather elements and animal intrusion This can be accomplished by using one of the three methods shown on the right Wall Mounted Outside Vent Protection Shroud Screen Roof Mounted Outside Vent Protection Shroud Screen Screen Exhaust Ve...

Reviews: