![Moeller XIOC Hardware And Engineering Download Page 32](http://html1.mh-extra.com/html/moeller/xioc/xioc_hardware-and-engineering_1819287032.webp)
Counter module
04/03 AWB2725-1452GB
28
Example of a linear counter, with the functions:
• interrogate comparison value and reference signal
• reset outputs
Ring counter
The counting range is defined by the start and end values, whereby
the start value must be lower than the end value.
As soon as the counter has been enabled, the start value is set and
all incoming pulses will be counted. The following actual values
will be shown, depending on the count direction (up or down).
Example:
• Start value = 10
• End value = 248
An up counter counts up to the end value + 1, and then restarts
from the start value. For a down counter, the next value is the start
value – 1, carrying on to the end value.
As a rule: minimum start value = 0; maximum end value =
FFFFFFFF
hex
.
Parameterizing the comparison value, setting module
outputs
You can set a comparison value, so that an action can be
performed when a defined count value has been reached. The
comparison value must lie between the parameter settings for
start value and end value. It is continuously compared with the
actual value. When equality is achieved, a “Latch” output (=) can
be set. This output is led out directly from the module, for a fast
response. The Equal flag serves as the internal marker for the
“Latch” output. The output and flag remain set until you reset
them.
Figure 39:
Example of a linear counter, with the functions “interrogate comparison value and reference signal” and “reset outputs”
742
0
1
364
365
426
742
743
Enable reference
Enable counter
Encoder pulse
Reference
Preset value: 742
Actual value
Enable Latch/Level output
Level output (>)
Latch output (=)
Reset Latch output
Comp. value: 364
Figure 40:
Counting range of the ring counter
10
11
12
247
248
249
10
11
10
9
248
247
246
11
10
9
Counting up
Counting down
For Immediate Delivery call KMParts.com at (866) 595-9616
Summary of Contents for XIOC
Page 4: ...II For Immediate Delivery call KMParts com at 866 595 9616...
Page 8: ...04 03 AWB2725 1452GB 4 For Immediate Delivery call KMParts com at 866 595 9616...
Page 24: ...04 03 AWB2725 1452GB 20 For Immediate Delivery call KMParts com at 866 595 9616...
Page 52: ...04 03 AWB2725 1452GB 48 For Immediate Delivery call KMParts com at 866 595 9616...