![Moeller XIOC Hardware And Engineering Download Page 26](http://html1.mh-extra.com/html/moeller/xioc/xioc_hardware-and-engineering_1819287026.webp)
Counter module
04/03 AWB2725-1452GB
22
Mode (operating mode) switch
Figure 23:
Mode (operating mode) switch, settings as delivered
h
In order to set the DIP-switches you will first have to take
out the module. But switch off the supply voltage first!
Switch
Position
Function
Chan.
Type of counter input
Mode 1
1
OFF
2-phase counter,
max. 100 kHz
1 + 2
2
OFF
Mode 2
1
ON
1-phase counter,
(pulse-change)
1 + 2
2
OFF
Mode 3
1
OFF
1-phase counter,
(polarity reversal)
1 + 2
2
ON
Mode 4
1
ON
2-phase counter with
4x evaluation, max.
25 kHz
1 + 2
2
ON
Polarity of the reference input (marker input)
3/4
OFF
A voltage on the input
produces a “0” signal
1/2
ON
A voltage on the input
produces a “1” signal
CPU-stop counter
5/6
OFF
CPU-STOP
r
Counter STOP
1/2
ON
CPU-STOP
r
Counter RUN
Linear/ring counter
7/8
OFF
Linear counter
1/2
ON
Ring counter
9/10
OFF
not used
–
ON
2 3
4
5
6
7
8
9 10
1
Figure 24:
Mode 1 (2-phase)
Figure 25:
Mode 2 (1-phase)
Figure 26:
Mode 3 (1-phase)
Figure 27:
Mode 4 (2-phase, with quadruple evaluation)
1
0
1
0
1
3
2
2
1
Phase A
Phase B
Actual value
1
0
1
0
1
3
2
2
1
Phase A
Phase B
Actual value
1
0
1
0
1
2
1
3
2
Phase A
Phase B
Actual value
1
0
1
0
1 2 3 4 5 6 7 8
7 6 5 4 3 2 1
Phase B
Actual value
Phase A
For Immediate Delivery call KMParts.com at (866) 595-9616
Summary of Contents for XIOC
Page 4: ...II For Immediate Delivery call KMParts com at 866 595 9616...
Page 8: ...04 03 AWB2725 1452GB 4 For Immediate Delivery call KMParts com at 866 595 9616...
Page 24: ...04 03 AWB2725 1452GB 20 For Immediate Delivery call KMParts com at 866 595 9616...
Page 52: ...04 03 AWB2725 1452GB 48 For Immediate Delivery call KMParts com at 866 595 9616...