Diagnostic data
29
11/06 AWB1251-1590GB
Meaning of the diagnostics information
The read diagnostics information has the following meaning:
Table 13: Data content of the diagnostics information
Octet 14
Bit 0…1
Status SmartWire module 13
Bit 2…3
Status SmartWire module 14
Bit 4…5
Status SmartWire module 15
Bit 6…7
Status SmartWire module 16
Diagnosticsp
osition
Designation
Designation
Meaning
Explanation/remedy
Response
monitoring activated
The response monitoring in the
SWIRE-GW-DP has been correctly
activated.
Set state
Freeze mode active
The DP master has activated the
synchronous reading of data inputs of
several slaves.
Is not supported.
Function not
supported
The DP master has requested one of the
functions not supported by the
SWIRE-GW-DP.
Check the configuration of the
DP master
Ident no. DP slave
Contains the Ident no.of the
SWIRE-GW-DP: 4D12
hex
–
Configuration error
The DP master has sent an invalid
configuration telegram to the
SWIRE-GW-DP (e.g. incorrect length of
the data inputs and/or data outputs)
Check the configuration of the
DP master
Length of additional
diagnostics
information
Contains the length of the additional
diagnostics information
–
Summary of Contents for SmartWire SWIRE-GW-DP