PROFIBUS-DP functions
Configuration of the DP
master
Always preform the following steps for the configuration of
the higher-level DP master.
X
Append the corresponding GSD file and the bitmap in the
GSD database of the configuration tool of your DP master
to suit the CPU which you are using (
• Motorola based CPU (e.g. for Siemens S7):
– Moel4d12.gsd,
– KM4D12_N.bmp,
– KM4D12_D.bmp.
• Intel based CPU (e.g. for Moeller XC100/200, PS4):
– Moe4d12.gsd,
– KM4D12_N.bmp,
– KM4D12_D.bmp.
X
Add the “SmartWire Gateway (S7/S5)” slave in the
topology of the PROFIBUS segment to be configured.
You will find the slave in the library under “Other field
devices
a
Switchgear”.
X
Assign this slave with the intended slave address.
X
Select for this slave up to 16 of the suggested modules per
SmartWire system for the cyclic data transfer,
section “Slave modules”, page 24.
X
Repeat steps 2 to 4 for every SWIRE-GW-DP slave to be
added to the topology.
X
Save the configuration.
X
Transfer the configuration to the DP master.
h
The monitoring time of the SwartWire slaves is fixed to
400 ms and cannot be changed.