Moeller ESR4-NO-21 Operating Instruction Download Page 3

4

Operating Instruction
ESR4-NO-21, ESR4-NM-21

Basic device for Emergency-Stop and Safety Gate Applications

• 

Basic device to EN 60204-1 and EN 954 -1 for single or dual E-stop monitoring.

• 

EN 954 category 4

• 

Stop category 0 acc. EN 60204-1

• 

Manual or automatic start

• 

Cross monitoring

• 

Feedback loop to monitoring external contactors

• 

2 Enabling paths, 1 signalling path

• 

Rated voltage in the E-stop circuit DC 24 V

• 

Processing of signals from output switching devices (OSSD) of light curtains acc. DIN EN

61496-1.

• 

To connect to load side of safety mats acc. DIN EN 1760-1 (ESR4-NM-21)

• 

Debouncing of inputs (ESR4-NM-21)

Front View

Power

LED green

K1

LED green

K2

LED green

Safety Instructions

Only trained professional electricians may

install, startup, modify, and retrofit this

equipment! Disconnect the device / system

from all power sources prior to starting any

work! If installation or system errors occur,

line voltage may be present at the control

circuit in devices without DC isolation!

Observe all electrical safety regulations

issued by the appropriate technical authorities

or the trade association. The safety function

can be lost if the device is not used for the

intended purpose. Opening the housing or

any other manipulation will void the warranty.

Caution!

Perform the following precautionary steps

prior to installation, assembly, or disassembly:

1. Disconnect supply voltage to the

equipment / system prior to starting any

work!

2. Lockout/tag the equipment / system to

prevent accidental activation!

3. Confirm that no voltage is present!

4. Ground the phases and short to ground!

5. Protect against adjacent live

components using guards and barriers!

6. The devices must be installed in a

cabinet with a protection class of at least

IP 54.

Caution!

Limited contact protection! Protection type

according to DIN EN 60529.

Housing/terminals: IP 40/ IP 20.

Finger-proof acc. to DIN VDE 0106 Part 1.

Description of Device and Function

ESR4-NO-21

This device is a two-channel safety switching device for emergency stop

applications with self-monitoring on each ON-OFF cycle. It conforms to EN 60204-1 and is

equipped with positively driven relays.

Basic function:

After supply voltage has been connected to terminals A1/A2 and the safety

inputs closed, operating the reset button closes the enabling current paths (manual start). When

the safety inputs are opened/de-excited the enabling current paths will open.

Operating modes / system functions

• 

One- or two-channel activation

With single-channel activation both safety channels CH1

and CH2 are connected in parallel, with two-channel activation they are connected

separately.

• 

Without cross monitoring

Both safety channels are connected to positive potential (S12

and S31 to S11).

• 

With cross monitoring

Safety channel CH1 is connected to positive potential (S11 to S12)

and safety channel CH2 to negative potential (S21 to S22).

• 

Manual start

When the safety inputs are closed, a button is used to open reset input S34

(triggering with falling edge) or to close reset input S35 (triggering with rising edge).

• 

Automatic start

Reset input S35 is connected to S33. The device starts with the rising

edge of the signal on safety input S12.

• 

Starting lockout

After supply voltage has been connected and the safety inputs closed, the

enabling paths will not close. Starting is only possible after the reset button has been

operated. For starting lockout the reset inputs have to be activated with the button, as in

manual start mode.

• 

Restarting lockout

No restart after the safety inputs have been opened and closed.

Restarting is only possible after the reset button has been operated. For restarting lockout

the reset inputs have to be activated with the button, as in manual start mode.

• 

OSSD-compatible

OSSD signals from a light barrier or other safety sensors with

semiconductor outputs can be processed. Test pulses < t

TP

do not influence the device

functions. Test pulses > t

TP

can lock the device.

• 

Synchro-check

With two-channel activation both safety channels are monitored together

with synchronous time t

S

. Safety channel CH1 must close before CH2 and bridge S33/S35

must be connected. If CH2 closes before CH1, the synchronous time t

S

=

.

ESR4-NM-21

The functions correspond to those of ESR4-NO-21 without simultaneity monitoring.

The device is suitable for connecting to short-circuit-forming 4-wire switching mats, switching

strips and switching edges (without monitoring resistance). The device must be operated with two

channels and cross monitoring. If there is resistance < 50

/channel and a short circuit between

the channels (S11/S12 and S21/S22) the enabling paths open and the SUPPLY LED flashes.

Input debouncing prevents fast consecutive switching of the enabling outputs when the safety

inputs open for shorter than t

ASP

. When the safety inputs open for longer than t

ASP

the enabling

paths open after t

R

. Restarting is prevented for time t

SP

.

Please observe instructions from safety authorities.

9

Caract

´

ristiques techniques

Circuit d

è

alimentation

ESR4-NO-21

ESR4-NM-21

Tension nominale U

N

AC/DC 24 V

Puissance assign

´

e DC

2,0 W

2,1 W

Puissance assign

´

e AC

2,4 W / 4,4 VA

2,5 W / 4,6 VA

Ondulation r

´

siduelle

2,4 V

SS

Fr

´

quence nominale

50 ... 60 Hz

Plage de la tension de service

0,85 ... 1,1 x U

N

Fusible pour alimentation circuit de commande

r

´

sistant aux courts-circuits (r

´

sistance

PTC)

r

´

sistant aux courts-circuits (fusible

´

lectronique)

Circuit de commande

Tension de sortie nominale S11, S33 contre S21

DC 22 V

Courant de sortie / courant de pointe

100 mA / 2000 mA

100 mA / 200 mA

Plage de la tension d

ê

entr

´

e

High (haut)

DC 17,4 V

a

DC 26,4 V

Low (bas)

DC

ô

3,0 V

a

DC +5,0 V

Courant nominal / courant de pointe S12, S31/S22

40 mA / 100 mA

Courant nominal / courant de pointe S34, S35

5 mA / 50 mA

Temps d

ê

impulsion de test admis t

TP

/ fr

´

quence de test

1000

µ

s /

10 s

-1

Temps de fonctionnement t

A1

S34

20 ms

a

40 ms

Temps de fonctionnement t

A2

S35

200 ms

a

500 ms

20 ms

a

80 ms

Dur

´

e mini de maintien t

M

S34, S35

> 50 ms

Temps de blocage t

SP

---

70 ms

a

130 ms

Temps de fonctionnement du blocage t

ASP

---

> 7 ms

Temps de r

´

armement t

W

40 ms

150 ms

Temps de rel

Ü

chement t

R

K1, K2

< 25 ms

Temps de contr

o

le du d

´

synchronisme

200 ms

--

Circuit de sortie

Contacts de sortie

Equipement des contacts

2 contacts de travail,

a

guidage forc

´

Tension nominale de coupure U

n

AC 240 V / DC 300 V

Courant continu max. I

n

pour chaque contact

6 A

Courant total max. de tous les contacts

12 A

AC-15 : Ue 230 V, Ie 4 A (360 h

-1

) DC-13: Ue 24 V, Ie 4 A (360 h

-1

)

Cat

´

gorie d

ê

utilisation selon IEC 947 - 5 - 1

AC-15 : Ue 230 V, Ie 3 A (3600 h

-1

) DC-13: Ue 24 V, Ie 2,5 A (3600 h

-1

)

Dur

´

e de vie m

´

canique

10 x 10

6

commutations

Contacts de signalisation

Equipement des contacts

1 contact de rupture, parall

e

le,

a

guidage forc

´

Tension nominale de coupure U

n

AC 240 V / DC 300 V

Courant continu max. I

n

pour chaque contact

6 A

AC-15 : Ue 230 V, Ie 4 A (360 h

-1

) DC-13: Ue 24 V, Ie 4 A (360 h

-1

)

Cat

´

gorie d

ê

utilisation selon IEC 947 - 5 - 1

AC-15 : Ue 230 V, Ie 3 A (3600 h

-1

) DC-13: Ue 24 V, Ie 2,5 A (3600 h

-1

)

Dur

´

e de vie m

´

canique

10 x 10

6

commutations

Caract

´

ristiques g

´

n

´

rales

Cheminements et claquage entre les circuits

´

lectriques

selon DIN VDE 0110 partie 1 : 04.97

Surtension transitoire assign

´

e

4 kV

Degr

´

de pollution de l

ê

appareil :

a

l

ê

int

´

rieur /

a

l

ê

ext

´

rieur

2 / 3

Tension assign

´

e

AC 300 V

Classe de protection selon DIN VDE 0470 partie 1 : Bo

ı

tier /

bornes

IP 40 / IP 20

Temp

´

rature ambiante / de stockage

-25 ... +55 / -25 ... +75

²

C

Poids

0,21 kg

Donn

´

es sur les bornes et les connexions

Unifilaire (fil rigide) ou fils de faible diam

e

tre (multibrins)

1 x 0,14 mm

è a

2,5 mm

è

2 x 0,14 mm

è a

0,75 mm

è

Longueur de d

´

nudation

max. 8 mm

Fil

a

faible diam

e

tre (multibrins) avec embout selon DIN

46228

1 x 0,25 mm

è a

2,5 mm

è

2 x 0,25 mm

è a

0,5 mm

è

Couple de serrage max.

0,5

a

0,6 Nm

Summary of Contents for ESR4-NO-21

Page 1: ... marrages intempestifs 3 Assurez vous que la machine est hors tension 4 Reliez les phases a la terre et court circuitez les 5 Couvrez et isolez les pie ces voisines sous tension 6 Le montage des appareils doit tre effectu dans une armoire lectrique avec une classe de protection min IP 54 Attention Protection partielle contre les contacts accidentels Classe de protection selon DIN EN 60529 Boı tier...

Page 2: ...atique ESR4 NM 21 installation 4 A1 A2 S12 S31 S22 S35 Blocage interne K1 K2 13 14 23 24 31 32 tSP temps de blocage tA2 temps de fonctionnement tTP temps dêimpulsion de test tASP temps de fonctionnement du blocage tR temps de relÜchement tW temps de r armement 5 Proper Use The devices are safety switching devices They must only be used as components of safety equipment on machines intended to prot...

Page 3: ...rier or other safety sensors with semiconductor outputs can be processed Test pulses tTP do not influence the device functions Test pulses tTP can lock the device Synchro check With two channel activation both safety channels are monitored together with synchronous time tS Safety channel CH1 must close before CH2 and bridge S33 S35 must be connected If CH2 closes before CH1 the synchronous time tS...

Page 4: ...sleistung DC 2 0 W 2 1 W Bemessungsleistung AC 2 4 W 4 4 VA 2 5 W 4 6 VA Restwelligkeit 2 4 VSS Nennfrequenz 50 60 Hz Betriebsspannungsbereich 0 85 1 1 x UN Sicherung fur Steuerkreisversorgung kurzschlussfest PTC Widerstand kurzschlussfest elektronische Sicherung Steuerkreis Nennausgangsspannung S11 S33 gegen S21 DC 22 V Ausgangsstrom Spitzenstrom 100 mA 2000 mA 100 mA 200 mA Eingangsspannungsbere...

Page 5: ...nbau der GerÖte muss in einem Schaltschrank mit einer Schutzart von mindestens IP 54 erfolgen Funktionsdiagramm bei manuellem Start ESR4 NO 21 Installation 3 A1 A2 S12 S31 S22 S34 K1 K2 13 14 23 24 31 32 tM Mindesteinschaltzeit tA1 Ansprechzeit tTP Testpulszeit tR Ruckfallzeit tW Wiederbereitschaftszeit Funktionsdiagramm bei automatischem Start ESR4 NM 21 Installation 4 A1 A2 S12 S31 S22 S35 Sperr...

Page 6: ...en die beiden SicherheitskanÖle CH1 und CH2 parallel und bei zweikanaliger Ansteuerung getrennt geschaltet Ohne Querschlusserkennung Beide SicherheitskanÖle werden gegen Pluspotential geschaltet S12 und S31 auf S11 Mit Querschlusserkennung Der Sicherheitskanal CH1 wird gegen Pluspotential S11 auf S12 und der Sicherheitskanal CH2 gegen Minuspotential S21 auf S22 geschaltet Manueller Start Mittels e...

Reviews: