Installation
64
05/01 AWB2700-1384GB
Connect all free moving groundable components (e.g. cabinet
doors) with short bonding straps with large surface areas.
If possible, aluminium components should not be used, because
aluminium oxidises easily and is therefore unsuitable for grounding.
PE Connection (Ground)
Between ground and PE connection (ground) a central connection
has to be established.
Mounting Rails
All mounting rails used must be grounded properly.