Technical Data
124
05/01 AWB2700-1384GB
Technical Data
Electronics module
DP-32DI/P-ECO
Operating voltage (U
S
)
24 V DC
Permissible range
18 to 30 V DC
Indication
LED green „RUN“
Operating current (I
S
)
70 mA
Potential separation to field bus
500 V
eff
/min
Inputs (Number)
32 (4x8)
Status ’1’
U
H
min/max
I
H
min/max
15 V DC/30 V DC
1,2 mA/4 mA
Status ’0’
U
L
min/max
-5 V DC/5 V DC
Input delay
approx. 0,5 ms
Synchronisation factor
100%
Indication
LED green „1 to 32“
Diagnosis
see chapter 8
Ambient temperature
- Operating temperature
- Storage temperature
- Relative humidity
0 to +60 °C
-20 to +85 °C
15 to 95 % without dewing
Field bus
Protocol
PROFIBUS DP acc. to EN 50170
Transmission rates
9,6 kBit/s to 1,5 MBit/s
EMV
Interference immunity acc. to EN 50082-1 and 2
Static electricity
8 kV air discharge, 6 kVrelay discharge
acc. to EN 61000-4-2
Electromagnetic fields
10 V/m acc. to ENV 50140
Burst
2 kV acc. to EN 61000-4-4
communication interfaces 2 kV, acc to IEC 801-4
HF unsymmetrical
10 V acc. to ENV 50141,
interference output acc. to EN 50081-2,
requirements acc. to EN 55011, group 1, class A. For
use in living areas (living, business and commercial
areas, small business) an individual authorization is
required
International protection class
IP 20 (DIN 40050/IEC 144)
Summary of Contents for DP-16DI-ECO
Page 12: ...8 05 01 AWB2700 1384GB ...
Page 16: ...12 05 01 AWB2700 1384GB ...
Page 24: ...20 05 01 AWB2700 1384GB ...
Page 62: ...58 05 01 AWB2700 1384GB ...
Page 91: ...Device Data Sets and Type Files 87 05 01 AWB2700 1384GB 9 ...
Page 109: ...Diagnostic Possibilities with S7 and PB DP 105 05 01 AWB2700 1384GB 9 ...
Page 120: ...116 05 01 AWB2700 1384GB ...
Page 146: ...142 05 01 AWB2700 1384GB ...
Page 150: ...05 01 AWB2700 1384GB 146 ...