Mounting/Dismounting
22
05/01 AWB2700-1384GB
General Information
TS 35 Mounting Rail
The mounting rail on which the
WIN
bloc eco modules are mounted
should be installed on a mounting plate (thickness at least 2 mm)
to create a reference potential for the ground connection and
shield. Mounting rails that are not pre-drilled should have holes
drilled up to a max. of 150 mm apart.
Terminal Blocks
WIN
bloc eco base elements are fitted with tension clamp
distribution rails, therefore enabling quick and easy installation.
Each base element consists of a terminal carrier, a quick fit
distribution rail and the locking clips. The terminal carrier itself is
equipped with connections for the bus and the signal connections;
the supplies for the initiators and actuators are made via the
distribution rails. The locking clips are used to secure the electronics
module to the base element.
Figure 3: Base element, consisting of a terminal carrier, distribution rail
and locking clips