background image

7

Backplate Mounting

  1.  It is the responsibility of the installing personnel to select the appropriate fasteners suitable for the wall 

material and construction. Screws driven into wall studs are recommended for maximum security.

  2.  Secure the backplate to wall with fasteners using any shims that may be required. See below for dimensional 

data of the back plate.  

Clarity 4ft Fixtures

Clarity 3ft Fixtures

Clarity 4ft Fixtures

Clarity 3ft Fixtures

  3.  At least two (2) stabilizing fasteners should be located in Area "H" above the backplate hook to keep the 

mounting plate from pivoting forward (Fig. 2). The location of the vertical wall studs are to be determined by 
the installation contractor. The hole in area H must be countersunk and the fastener must be flat head. The 
hardware in area H must be flush to the backplate extrusion as to not interfere with the bed stop option or 
downward travel of the chassis into the mounting plate during installation.

Summary of Contents for Clarity LED

Page 1: ...CLARITY LED INSTALLATION MANUAL ...

Page 2: ...et in connection with installation operation or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s or owner s purposes this matter should be referred to Modular Services Company Disconnect or turn off power before installation or servicing Verify that supply voltage is correct by comparing it with the luminair...

Page 3: ...tion or maintenance Should further information be desired or should particular problems arise which are not covered sufficiently for the purchaser s or owner s purposes this matter should be referred to Modular Services Company Disconnect or turn off power before installation or servicing Verify that supply voltage is correct by comparing it with the product information Make all electrical and grou...

Page 4: ...ng or performing routine maintenance upon this equipment follow these general precautions Installation and service of luminaires should be performed by a qualified licensed electrician Maintenance of the luminaires should be performed by person s familiar with the luminaires construction and operation and any hazards involved Regular fixture maintenance programs are recommended It will occasionall...

Page 5: ...istance Always read the fixtures complete installation instructions prior to installation for any additional fixture specific warnings CAUTION RISK OF PRODUCT DAMAGE Disconnect or turn off power before installation or servicing Verify that supply voltage is correct by comparing it with the luminaire label information Make all electrical and grounded connections in accordance with the National Electric...

Page 6: ...y 4 Review final approved shop drawings and submittal booklet The following documents will provide you with technical details specific to the installation Wiring Diagrams that are on a decal and placed on the fixture The Installation Manual for that specific fixture UNIT INSTALLATION This product must be installed in accordance with the applicable installation code by a person familiar with the co...

Page 7: ... Fixtures Clarity 3ft Fixtures Clarity 4ft Fixtures Clarity 3ft Fixtures 3 At least two 2 stabilizing fasteners should be located in Area H above the backplate hook to keep the mounting plate from pivoting forward Fig 2 The location of the vertical wall studs are to be determined by the installation contractor The hole in area H must be countersunk and the fastener must be flat head The hardware i...

Page 8: ...ture on backplate engaging fixture hook over backplate hook 3 If the bed power interrupt switching bed stop option was ordered see Figure 3 for assembly of the provided spacers over the backplate studs If bed stop option is not provided omit the spacers shown in Figure 3 4 Secure the fixture with the washers and nuts provided 5 If bed stop option is provided test fixture for free vertical movement...

Page 9: ...and number of wires being used 4 If a low voltage controller was ordered refer to the wiring diagram on the controller label for the wiring options 5 Connect the grounding wire of fixture to a proper ground LENS INSTALLATION 1 Orient each lens as shown in Figure 4 Position 1 There is a groove at the front of the lens which runs the length of the lens Install the lens on the groove indicated in Fig...

Page 10: ...ackplate 4 Tighten Phillips screws to secure this setting 5 Test the bed stop s function for operation as per the testing procedure below Testing Functions 1 Test continuity from COM TERMINAL to NO TERMINAL 2 Proper function of the fixture will have continuity with the housing against backplate as shown in Figure 5 Detail B 3 As the housing is moved away from the backplate continuity should be los...

Page 11: ...or a period of 12 months from date of the owner s acceptance to the installing contractor or the date the equipment is put into service whichever comes first Warranty excludes electric lamps and or any material not furnished by Modular Services Warranty does not cover damage due to improper installation and or abuse It is the responsibility of the customer to report any noted product deficiencies ...