20
messages can be set between 0 days (no test message) and 30 days. The
default test interval is set to "0" (no test message).
5.3
INPUT TYPE
The input type defines the character of the additional inputs IN1 and IN2.
This can be Normally Open (NO), Normally Closed (NC), or Analog (AN). If an
input is set to "NO", the alarm will be triggered as soon as the terminals of
the input are closed. If the input is set to NC, the alarm is triggered when the
connection between the input terminals is broken. With AN, the input
measures the input voltage and send an alarm if it falls below the set value.
The default input type is set to "NO" for input 1 and
“
AN
” for input 2
.
5.4
ALARM DELAY TIME
The input delay time defines the time that the input is triggered before an
alarm is initiated. If the input returns to the non-alarm status within the delay
time, no alarm is sent. The time can be set between 0 and 999 seconds. As
default, the input delay time is set to 1 second for input 1 and input 2. For
the water sensor it is 30 seconds. The delay for the temperature alarm is
adjustable in minutes with the factory setting 0.
5.5
INACTIVE TIME
The
“inactive
time”
defines the time an input is not active after an activation.
During the inactive time, no new alarm message will be sent. Only when the
input returned to the non-alarm status, gets activated again and remains
active, an alarm will be sent yet after the inactive time. If the time is set to
“0”
(minutes), the input will be active again immediately after returning to the
non-alarm status. The time can be set between 0 and 60 minutes. As default,
the inactive time is set to
“
0
”.
5.6
ALARM REPEAT TIME
In order to emphasize the urgency of the alarm messages, all alarms can be
repeated. As long as the temperature value or an input has not returned to
the inactive status, the alarm messages will be repeated afte
r the ‘alarm
repeat time
’. The r
epeat interval can be set between 0 (no repeat) and 24
hours. As default the alarm repeat time is set to 4 hours.