TESTING FOR EMERGENCY LUMINAIRES
Recommended routine test procedure in accordance with BS5266
• Daily check – check LED charge indicator is illuminated
• Monthly functional test – simulate a mains supply failure for approx. 30 seconds by
operation of key switch or switching off circuit breaker. Ensure normal supply is restored
after test and ensure charge indicator is illuminated
• Annual 3-hour duration test - simulate a mains supply failure for a 3-hour continuous
test by operation of key switch or switching off circuit breaker. Ensure normal supply is
restored after test and ensure charge indicator is illuminated
• If the luminaire fails any of the above tests, please contact a qualified electrician
Please note: the Switched Live should not be re-energised during the emergency test