ML BT CTEMS Series Installation & Maintenance Manual Download Page 5

  The additional terminal called Slave Live 

(L’)

 is available to enable the sensor to power on additional 

luminaires. A max. LED load of 400W can be controlled by the sensor

 

  Please see DIP Switch Layout to set up sensor

 

  Connect the battery to the inverter

 

  Refasten the LED plate screw 

  Choose the required colour temperature by means of the DIP switch (see Fig. 4) 

  

Fig. 4 

  Reattach the diffuser by rotating clockwise 

  Switch on and check for correct operation, ensuring the green indicator LED is illuminated 

  We recommend, on commissioning the installation, a minimum charge period of 24 hours before 

carrying out an emergency duration test 

Note: this fitting shuts off power to the Lithium Ion battery periodically to prevent overcharging. 

Therefore, the green LED indicator has been set up to indicate that the emergency inverter is in good 

condition, not to indicate that the battery is charging. The installer must ensure that the battery is 

connected. 
SENSOR LAYOUT 

 

DIP SWITCH LAYOUT 

 

 

• If the batteries have been left in a discharged state for an extended period, we 

recommend that one or more charge and discharge cycles are completed which should 

help to restore the battery capacity 

Summary of Contents for BT CTEMS Series

Page 1: ...INSTALLATION MAINTENANCE MANUAL BTxxCTEMS...

Page 2: ...should be read carefully and retained after installation by the end user for future reference and maintenance These instructions should be used to aid installation of the following product BT9CTEMS B...

Page 3: ...plate to the surface Connect the Live brown and Neutral blue to the terminals on the terminal block see Fig 3 This product must be installed in accordance with the latest edition of the IEE Wiring Reg...

Page 4: ...brown Emergency Live L1 and Neutral blue to the terminals on the terminal block see Fig 3 Fig 3 Refasten the LED plate screw Choose the required colour temperature by means of the DIP switch see Fig...

Page 5: ...to the Lithium Ion battery periodically to prevent overcharging herefore the green LED indicator has been set up to indicate that the emergency inverter is in good ondition not to indicate that the ba...

Page 6: ...IP SWITCH LAYOUT DIP SWITCH SETTINGS Detection area Hold time DIP SWITCH SETTINGS Detection area Hold time This is the time period the lamp remains at 100 after no motion is dete...

Page 7: ...nty of 5 years excluding battery from date of purchase Failure to install this product in accordance with the current edition of the IEE Wiring Regulations improper use or removal of the batch codes w...

Page 8: ...not use any source of high pressure washers to maintain or clean this luminaire This product is non dimmable This product should be dismantled for disposal when it reaches the end of its life Plea di...

Page 9: ...re charge indicator is illuminated Annual 3 hour duration test simulate a mains supply failure for a 3 hour continuous test by operation of key switch or switching off circuit breaker Ensure normal su...